Installation
10
Mitsubishi Electric, MA00780C
3. Secure the operator panel in position, using all the fastening holes and the
provided brackets and screws:
4. Connect the cables in the specified order.
Use an M5 screw and a grounding conductor (as short as possible)
with a cross-section of minimum 2.5 mm
2
.
5. Carefully remove the laminated film over the operator panel display, to avoid
static electricity that could damage the panel.
x 14
0.5 - 1.0 Nm
B
C
D
A
Caution
Ensure that the operator panel and the controller system have the
same electrical grounding (reference voltage level), otherwise errors
in communication may occur.
Caution
- Use only shielded communication cables.
- Separate high voltage cables from signal and supply cables.
Caution
- The operator panel must be brought to ambient temperature
before it is started up. If condensation forms, ensure that the
operator panel is dry before connecting it to the power outlet.
- Ensure that the voltage and polarity of the power source is correct.
24V DC
RS422/RS485
24V DC
1
CF
CARD
B
A
C
D
RS232
Controller
Power
Ethernet
Содержание E1151
Страница 1: ...MITSUBISHI ELECTRIC E1151 Installation manual MA00780C 2008 07 English ...
Страница 4: ...Table of Contents Mitsubishi Electric MA00780C ...
Страница 8: ...Safety Precautions 8 Mitsubishi Electric MA00780C ...
Страница 12: ...Installation 12 Mitsubishi Electric MA00780C ...
Страница 14: ...Technical Data 14 Mitsubishi Electric MA00780C ...
Страница 18: ...Operator Panel Drawings 18 Mitsubishi Electric MA00780C 5 2 E1151 Outline Drawing No S 5141 Date 2004 10 26 ...