Installation

4. Connect the cables in the specified order, according to the drawing and steps

below.

Caution:

The operator panel must be brought to ambient temperature before it is started
up. If condensation forms, ensure that the operator panel is dry before connecting
it to the power outlet.

Ensure that the operator panel and the controller system have the same electrical
grounding (reference voltage level), otherwise errors in communication may
occur.

Ensure that the voltage and polarity of the power source is correct.

Separate high voltage cables from signal and supply cables.

Shielded communication cables are recommended.

24V DC

RS422/
RS485
RS232

 24V DC

A

C

D

Controller

Power

B

Ethernet

Connect cable A.

Connect cable B, using an M5 screw and a grounding conductor (as short
as possible), that is sized correctly according to local electrical codes.

Connect cable C.

Connect cable D.

5. Carefully remove the laminated film over the operator panel display, to avoid

static electricity that could damage the panel.

Mitsubishi Electric, MA00815F

9

Содержание E1061

Страница 1: ...E1061 E1063 Installation Manual English MA00815F 2014 12 ...

Страница 2: ...ubishi Electric Automation Inc assumes no responsibility for any errors that may appear in this document Read the entire installation manual prior to installing and using this equipment Only qualified personnel may install operate or repair this equipment Mitsubishi Electric Automation Inc is not responsible for modified altered or renovated equipment Because the equipmenthas a wide range of applica...

Страница 3: ... 10 3 TechnicalData 11 4 ChemicalResistance 13 4 1 MetalCasing 13 4 2 Touch Screen and Overlay Material 13 4 2 1 Autotex F157 207 13 4 2 2 Touch Screen Surface 14 4 2 3 Touch Screen Protector 15 5 Operator Panel Drawings 16 5 1 Communication Ports 16 5 2 E1061 E1063 Outline 17 6 Additional Installation Tips 18 6 1 Grounding the Operator Panel 18 6 2 Ethernet Connection in the Panel 19 6 3 To Achie...

Страница 4: ...a powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open flush with plenty of water and get medical attention The figures in this manualserves an illustrative purpose Because of the many variables associated with any particular installation the supplier cannot assume responsibility for actual use based onthe figures The supplierneither gua...

Страница 5: ...REUSE This product contains a battery this must onlybe changedin an areaknown tobe non hazardous Replace the battery with aCR2450 battery Use of anothertype ofbattery maypresent a risk offire orexplosion Warning Battery may explode if mistreated Do not recharge disassemble or dispose of in fire LA BATTERIEPEUT EXPLOSEREN CAS DE MAUVAISE MANIPULATION NE LA RECHARGEZ PAS NE LA DÉMONTEZ PAS ET NE LA J...

Страница 6: ... poweroutlet Peripheral equipment must be appropriate forthe application and location 1 4 During Use Keep the operatorpanel clean Emergency stopand othersafety functions may notbe controlled from the operator panel Do not use excessive force orsharpobjects when operatingthe touchscreen 1 5 Service and Maintenance Onlyqualified personnel shouldcarry outrepairs The agreed warranty applies Before carr...

Страница 7: ...nch 100 mm 4 0 inch 57 mm 2 24 inch 7 95 inch 5 98 inch Caution The openings on the enclosure are for airconvection Do not cover these openings 2 2 Installation Process 1 Unpackand check the delivery If damage isfound notify the supplier x 4 Panel cut out 180 x 130 mm 7 09 x 5 12 inch Note Place the operator panelon a stable surface duringinstallation Dropping it or letting itfall may cause damage...

Страница 8: ... operator panelistobe situated draw along the outer sides ofthe holesandcutaccording to the markings 3 Secure the operator panel in position usingallthe fasteningholesand the provided brackets and screws x 4 0 5 1 0 Nm Mitsubishi Electric MA00815F 8 ...

Страница 9: ...ise errors in communication may occur Ensure that the voltage and polarity of the powersource is correct Separate high voltage cables from signal and supply cables Shielded communication cables are recommended 24V DC RS422 RS485 RS232 24V DC A C D Controller Power B Ethernet Connect cable A Connect cable B usingan M5 screwand agroundingconductor asshort as possible thatissized correctly accordingt...

Страница 10: ...ections to the Controller For information aboutthe cables to be used when connecting the operator panelto the controller please refer to the helpfile for the driverin question 2 2 3 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurtherdetailsor recommendations please refertothe supplier Mitsubishi Electric MA0...

Страница 11: ... ppm C2 Real time clock battery CR2450 UL and cUL Sanyo or Panasonic Minimum lifetime 3 years Power consumption at rated voltage Normal 0 2 A Maximum 0 4 A For T60c and for T60m with hardware version lower than 07600 Normal 0 25 A Maximum 0 45 A Display 320 x240 pixels T60 TFT LCD 64K colors For T60c transmissive color STN LCD 64K colors for T60m TFT LCD 16 greyscales for T60m with hardware versio...

Страница 12: ...lation 0 to 50 C Horizontal installation 0 to 40 C Storage temperature 20 to 70 C Relative humidity 5 85 non condensed Approvals and certifications Information is available on the web site See section ChemicalResistance for more information Mitsubishi Electric MA00815F 12 ...

Страница 13: ...oric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above chemicals is demanded itis recommended to first test the chemical in a hidden spot of the metal casing The powder paint shows little or no resistance to the followingchemicals at room temperature Acetic acid conc Methyl ethyl ketone Toluene Acetone Nitric acid 30 Trich...

Страница 14: ...l Windex1 Cyclohexanol Persil powderin solution1 Wisk Diacetone alcohol Petroleum spirit1 1 Extremely faintglossingof the texture was noted Autotex withstands DIN 42 115 Part2 exposure of up to 1 hour duration to glacial aceticacid without visible change Autotex is not resistant to high pressure steam at over 100 C orthe following chemicals Concentrated mineral acids Benzylalcohol Concentrated cau...

Страница 15: ...een Protector For harsh environments and exposure tooutdoorconditions it isrecommended to use a protective film toguardthe touch screenfromdamage These optional parts can be ordered from MitsubishiElectric Mitsubishi Electric MA00815F 15 ...

Страница 16: ...Operator PanelDrawings 5 Operator Panel Drawings 5 1 Communication Ports RS 232 RS 422 RS 422 485 RS 485 Ethernet USB Mitsubishi Electric MA00815F 16 ...

Страница 17: ...Operator PanelDrawings 5 2 E1061 E1063 Outline Mitsubishi Electric MA00815F 17 ...

Страница 18: ...aid between the panel s chassis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 Twist the cables onto the 24 V DC feed see 5 in drawingabove 2 turns around the ferrite core provide 4 times the suppressionof1 turn 3 turns around the ferrite core provide 9 times the suppressionof1 t...

Страница 19: ...nithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur Unshielded cabling may even result in fewer communication errors A good solutionmay be touse a shielded Ethernet cable but toconnect the shield at one end only One option istobreak the shield see 3 in ...

Страница 20: ...he shield to the groundviaa 0 1 μ F 250 Vplastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms ofLF thus avoidingthe 50 Hz groundingloops Metal cabinet Metal cabinet Terminal or connector Terminal or connector EMC cable gland Plastic cable gland Shielded cable Shielded cable Short distance Cable clamp in steel 5353 1 Use an E...

Страница 21: ... a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Installinga fan inside the cabinetwill even out the temperature while moving air providesconsiderably better coolingthan stillair Asuitable fan is a120 x120 mm axialfan available in 24 VDC 115 and 230 V AC Install the fan so that it sitsin the cooler a...

Страница 22: ...LVaccording to EN 60950 protection against electric shock andUL 950 Note Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller controller Check that the clearances and creepage distances between 24 V DC and 230 V AC fulfill EN 60950 or UL 950 If not input a separate 24 V unit into the operator panel If there...

Страница 23: ...SB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial risk of problems Groundingcurrents go through communication cables the rearplate of the controller andinternally in the operatorpanel and can cause errors Use external units to improve communication and ...

Страница 24: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120 ohm 120 ohm 5 V 5 V 0 V 0 V 0 V 0 V 0 V 0 V 1 K 1 K 1 K 1 K VCC VCC 120 ohm Inside operator panel Operator panel RS422 CAB8 CAB8 Bus RS485 Shield Bus termination 5358 2 14 15 6 19 7 8 1 2 3 4 5 6 7 8 ...

Страница 25: ...Mitsubishi Electric Automation Inc 500 Corporate Woods Parkway Vernon Hills IL 60061 USA Mitsubishi Electric Europe B V Gothaer Strasse 8 D 40880 Ratingen Germany ...

Отзывы: