4.
OPERATING RANGE
ETHYLENE GLYCOL MIXTURE
Ethylene glycol and water mixtures, used as a heat-conveying fluid,
cause a variation in unit performance. For correct data, use the factors
indicated in the following table.
Freezing point (°C)
0
-5
-10
-15
-20
-25
-30
-35
Ethylene glycol percentage by weight
0
12%
20%
30%
35%
40%
45%
50%
cPf
1
0,985
0,98
0,974
0,97
0,965
0,964
0,96
cQ
1
1,02
1,04
1,075
1,11
1,14
1,17
1,2
cdp
1
1,07
1,11
1,18
1,22
1,24
1,27
1,3
cPf: cooling capacity correction factor
cQ: flow correction factor
cdp: pressure drop correction factor
For data concerning other kind of anti-freeze solutions (e.g. propylene
glycol) please contact our Sales Department.
Encrustation factors
Evaporator
Heat recovery
Desuperheater
f1
fk1
fx1
f2
fk2
fx2
f3
fk3
fx3
(m
2
°C/W) 4,4 x 10
-5
1
1
1
0,99
1,03
1,03
0,99
1,03
1,03
(m
2
°C/W) 0,86 x 10
-4
0,96
0,99
0,99
0,98
1,04
1,04
0,98
1,04
1,04
(m
2
°C/W) 1,72 x 10
-4
0,93
0,98
0,98
0,95
1,06
1,06
0,95
1,06
1,06
FOULING FACTORS
Performances are based on clean condition of tubes (fouling factor =1).
For different fouling values, performance should be adjusted using the
correction factors shown in the following table.
f1 - f2 - f3: capacity correction factors
fk1 - fk2 - fk3: compressor power input correction factors
fx1 - fx2 - fx3: total power input correction factors
Tc OUT [°C]: Heat exchanger temperature on source side (out)
Tev OUT [°C]: Cold exchanger temperature on user side (out)
Limits to exchanger water temperature are valid within the minimum
- maximum water flow range indicated in the Hydraulic Data section.
40
50
15
10
0
-10
20
60
48
30
-8
7
35
45
25
55
5
-5
Tev OUT [°C]
Tc OUT
[°C]
13
NECS_ME_0152_1604_201004_GB
NECS-ME
HFC R410A