<Reference> Size of refrigerant pipes
On-site piping [mm (in)]
Service valve piping [mm (in)]
Liquid
Gas
Liquid
Gas
P200
ø9.52 (ø3/8)
ø22.2 (ø7/8)
ø9.52 (ø3/8)
¡ĭ
P250
*1
ø9.52 (ø3/8)
*2
ø12.7 (ø1/2)
P300
*3
ø9.52 (ø3/8)
*4*6
ø12.7 (ø1/2)
P350
ø12.7 (ø1/2)
ø28.58 (ø1-1/8)
¡ĭ
P400
*5
ø12.7 (ø1/2)
ø28.58 (ø1-1/8)
*6
ø15.88 (ø5/8)
P450
ø15.88 (ø5/8)
P500
ø15.88 (ø5/8)
¡ĭ
On-site piping [mm (in)]
Service valve piping [mm (in)]
Liquid
Gas
Liquid
Gas
EP200
ø9.52 (ø3/8)
ø22.2 (ø7/8)
ø9.52 (ø3/8)
¡ĭ
EP250
*1
ø9.52 (ø3/8)
*2
ø12.7 (ø1/2)
EP300
*3
ø9.52 (ø3/8)
ø28.58 (ø1-1/8)
*4*6
ø12.7 (ø1/2)
EP350
ø12.7 (ø1/2)
¡ĭ
ø28.58 (ø1-1/8)
EP400
*5
ø12.7 (ø1/2)
*6
ø15.88 (ø5/8)
EP450
ø15.88 (ø5/8)
EP500
ø15.88 (ø5/8)
ø15.88 (ø5/8)
*1 When the piping length from the outdoor unit to the farthest indoor unit is less than 90 m (295 ft)
*2 When the piping length from the outdoor unit to the farthest indoor unit is 90 m (295 ft) or more
*3 When the piping length from the outdoor unit to the farthest indoor unit is less than 40 m (131 ft)
*4 When the piping length from the outdoor unit to the farthest indoor unit is 40 m (131 ft) or more
*5 When the unit is used alone
*6 When the unit is used in combination with other outdoor units
・
When expanding the on-site piping, satisfy the minimum insertion depth requirement as follows.
Pipe size [mm (in)]
Minimum insertion depth [mm (in)]
ø5 (ø1/4) or more, less than ø8 (ø3/8)
6 (1/4)
ø8 (ø3/8) or more, less than ø12 (ø1/2)
7 (5/16)
ø12 (ø1/2) or more, less than ø16 (ø11/16)
8 (3/8)
ø16 (ø11/16) or more, less than ø25 (ø1)
10 (7/16)
ø25 (ø1) or more, less than ø35 (ø1-7/16)
12 (1/2)
ø35 (ø1-7/16) or more, less than ø45 (ø1-13/16)
14 (9/16)