29
Indoor controller board
PMFY-P20VBM-E#2 PMFY-P25VBM-E#2 PMFY-P32VBM-E#2 PMFY-P40VBM-E#2
PMFY-P20VBM-ER3 PMFY-P25VBM-ER3 PMFY-P32VBM-ER3 PMFY-P40VBM-ER3
PMFY-P20VBM-ER4 PMFY-P25VBM-ER4 PMFY-P32VBM-ER4 PMFY-P40VBM-ER4
The voltage range of DC12V in this
page is between DC11.5 V to DC 13.7 V.
CN51
Centrally control
1
-
2
: Control signal
12VDC pulse input (
1
: +)
3
-
4
: Operation indicator
12VDC (
3
: +)
3
-
5
: Malfunction indicator
12VDC (
3
: +)
CN52
Remote indicator
1
-
2
: Status lamp 12VDC (
1
: +)
Fan motor output (SW1-5 OFF)
Thermostat ON (SW1-5 ON)
1
-
3
: Cooling/Dry status lamp
12VDC (
1
: +)
1
-
4
: Heating status lamp
12VDC (
1
: +)
CNMF1, CNMF2
FAN motor
CNMF1
1
-CNMF2
1
: 310-340V DC
CNMF2
7
-
1
: 0-15V DC
CN2M
Connect to the terminal block TB5
(M-NET transmission connecting wire)
24-30V DC (non-polar)
LED2
Power supply for
MA-Remote controller
CN3A
MA-Remote controller
connecting wire
1
-
3
8.7-13V DC (Pin
1
(+))
CN6V1
Vane motor
CN32
Connector
(Remote switch)
SW2
Capacity setting
SW3
Function setting
SW4
Model setting
CN44
Pipe temperature
1
-
2
: thermistor/Liquid
(TH22)
3
-
4
: thermistor/Gas
(TH23)
CN20
Room thermistor (TH21)
CN60
Linear expansion valve
(LEV)
CN31
Drain sensor (DS)
LED1
Main power supply
FUSE
6.3A 250V
CND
Power supply
1
-
3
: 220-240V AC
CNP
Drain pump output (DP)
1
-
3
: 220-240V AC
OC307E