37
OCH610G
7KHEODFNVTXDUHŶLQGLFDWHVDVZLWFKSRVLWLRQ
Switch
Pole
Operation by switch
Effective
timing
Remarks
SW22
Wireless
remote
controller
pair No.
Jumper
Function
ON
OFF
1
ņ
ņ
ņ
2
ņ
ņ
ņ
3 Pair No. of wireless remote controller
Depends on the combination
of SW22-3 and 22-4
4 Pair No. of wireless remote controller
• To operate each indoor unit by each remote controller when
installed 2 indoor units or more are near, Pair No. setting is
necessary.
1
Pair No. setting is available with the 4 patterns (Setting patterns A to D).
2
Make setting for SW22 of indoor controller board and the
Pair No. of wireless remote controller.
• You may not set it when operating it by one remote controller.
1
Setting for indoor unit
Set SW22 on the indoor controller board according to the table
below.
2
Wireless remote controller pair No.:
Ɣ6HWWLQJRSHUDWLRQ
1. Press the SET button (using a pointed implement). Check that
the remote controller's display has stopped before continuing.
MODEL SELECT blinks, and the model No. (3 digits)
appears (steadily-lit).
3UHVVWKH0,187(EXWWRQWZLFH7KHSDLU1RDSSHDUVÀDVKLQJ
3. Press the TEMP
buttons to select the pair No. to set.
4. Press the SET button (using a pointed implement). The
set pair is displayed (steadily-lit) for 3 seconds, then
disappears.
Indoor unit SW22
Pair No. of wireless
remote controller
SW22-3
SW22-4
ON
ON
0
Initial setting
OFF
ON
1
ņ
ON
OFF
2
ņ
OFF
OFF
3–9
ņ
Under
operation
or
suspension
<Initial setting>
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
MODEL SELECT
Model No.
Temperature
button
SET button
Pair No.
Minute
button
ON
OFF
1 2 3 4
SWE
Test run
for Drain
pump and
Indoor fan
motor
Connector
Drain pump and indoor fan motor are activated simultaneously after
the connector SWE is set to ON and turn on the power.
The connector SWE is set to OFF after test run.
SWE
OFF
ON
SWE
OFF
ON
Under
operation
<Initial setting>
SWE
OFF
ON