VII
Troubleshooting ]
- 14 -
HWE0812B
GB
VII
Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
1) Thermistor characteristic graph
(2) Fan motor (CNMF)
Refer to the page on "DC fan motor (fan motor/indoor control board)."
(3) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
Normal
Abnormal
4.3k
Ω
- 9.6k
Ω
Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Drain sensor (DS)
Thermistor R
0
= 15 k
Ω
3%
Multiplier of B = 3480 k
Ω
2%
0°C 15k
Ω
10°C 9.6k
Ω
20°C 6.3k
Ω
25°C 5.2k
Ω
30°C 4.3k
Ω
40°C 3.0k
Ω
(A) Temperature (°C)
(B) Resistance
(k
Ω
)
Normal
Abnormal
1-5
2-6
3-5
4-6
Open or short
White-Red
Yellow-Brown
Orange-Red
Blue-Brown
200 k
Ω
10%
(A)
Brown
(D)
Orange
(B)
Red
(E)
Yellow
(C)
Blue
(F)
White
Rt = 15 exp { 3480(
) }
1
273+t
1
273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
(A)
(B)
1
2
3
4
5
6
LEV
M
(A)
(B)
(C)
(D)
(E)
(F)
CN60
0000001526.book 14 ページ 2012年9月13日 木曜日 午後7時14分