6.  Troubleshooting

When an error occurs, the following screen will appear and the operation LED will blink. 
Check the error status, stop the operation, and consult your dealer.

Error code, error unit, refrigerant address, unit model name, and serial number will appear.

The model name and serial number will appear only if the information have been registered.

Press the [F1] or [F2] button to go to the next page.

Before you ask for repair service, check the following points:

State of Machine

Remote Controller

Cause

Troubleshooting

It does not run.

Ruled line and clock are not 

displayed.

No display appears even when 

the [ON/OFF] button is pressed.

Power failure

Press the [ON/OFF] button after power restoration.

The power supply is turned OFF.

Turn the power supply ON.

The fuse in the power supply is gone.

Replace fuse.

The earth leakage breaker is gone.

Put in the earth leakage breaker.

Air flows out but it does 

not cool enough or heat 

enough.

The liquid crystal display shows 

that it is in the state of operation.

Improper temperature adjustment

After checking the set temperature and inlet 

temperature on the liquid crystal display, refer to 

section 3.3 "Set temperature", and operate the 

adjustment button.

The filter is filled with dust and dirt.

Clean up the filter.

(Refer to section 5 "Caring for the machine".)

There are some obstacles at the air inlet 

and outlet of the indoor and outdoor units.

Remove.

Windows and doors are open.

Close.

Cool air or warm air does 

not come out.

The liquid crystal display shows 

that it is in operation.

The restart-preventing circuit is in operation 

for 3 minutes.

Wait for a while.

(To protect the compressor, a 3- minute restart-

preventing circuit is built into the indoor unit. Therefore, 

there are occasions sometimes when the compressor 

does not start running immediately. There are cases 

when it does not run for as long as 3 minutes.)

Indoor unit operation was restarted during 

the heating and defrosting operation.

Wait for a while.

(Heating operation starts after ending defrosting 

operation.)

It runs briefly, but soon 

stops.

The “CHECK” and check code 

flash on the liquid crystal display.

There are some obstacles at the air inlet 

and outlet of the indoor and outdoor units.

Rerun after removal

The filter is filled with dust and dirt.

Rerun after cleaning the filter. (Refer to section 5 

"Caring for the machine".)

The sound of the exhaust 

and rotation of the motor 

can still be heard after 

stop of running.

All lights are out except the ruled 

line and clock.

Fri

When other indoor units are engaged in 

cooling operation, the machine stops after 

running a drain-up mechanism for 3 

minutes when air-cooling operation is 

stopped.

Wait for 3 minutes.

The sound of the exhaust 

and the rotation of the 

motor can be heard 

intermittently after stop of 

running.

All lights are out except the ruled 

line and clock.

Fri

When other indoor units are engaged in 

cooling operation, drained water is brought 

in. If the drain water is collected, the 

drain-up mechanism initiates a draining 

operation.

It soon stops. (If the noise occurs more than 2-3 times 

in an hour, ask for repair service.)

Warm air comes out 

intermittently when the 

thermostat is OFF or 

during fan operation.

The liquid crystal display shows 

that it is in the state of operation.

When other indoor units are engaged in 

heating operation, the control valves are 

opened and closed from time to time to 

maintain the stability of the system.

It soon stops. (If the room temperature rises 

uncomfortably high in a small room, stop operation.)

•  If operation stops due to a power failure, the [restart-preventing circuit at power failure] operates and disables unit operation even after power restoration. In this case, 

press the [ON/OFF] button again and start operation.

If malfunctions persist after you have checked the above, turn the power supply OFF and contact your dealer with information about the product name, the nature of the 

malfunction, etc. If the display of error information flashes, tell the dealer contents of the display (error code). Never attempt to repair by yourself.

Содержание CITY MULTI PEFY-P100VMA-E3

Страница 1: ...fe and correct use please read this operation manual thoroughly before operating the air conditioner unit en Air Conditioners INDOOR UNIT PEFY P20 25 32 40 50 63 71 80 100 125 140VMA E3 PEFY P20 25 32 40 50 63 71 80 100 125 140VMAL E3 ...

Страница 2: ...n la parte inferior Ingresso aria nella parte inferiore Luchtinlaat aan de onderkant Entrada de ar na parte inferior Είσοδος αέρα από κάτω Воздухозаборник внизу Alttaki hava girişi Přívod vzduchu ve spodní části Prívod vzduchu na spodnej strane Légbeömlő nyílás az alsó oldalon Wlot powietrza z dołu Vstop zraka na spodnji strani Luftintag på undersidan Ulaz za zrak na dnu Вход за въздух от долната ...

Страница 3: ...ions of the function buttons change depending on the screen Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen When the system is centrally controlled the button function guide that corresponds to the locked button will not appear Main display Main menu Cursor Page Menu screen Function button F1 Main display Press to change the o...

Страница 4: ... appears here Appears when the buttons are locked Appears when the On Off timer Night setback or Auto off timer function is enabled appears when the timer is disabled by the centralized control system Appears when the Weekly timer is enabled Appears while the units are operated in the energy save mode Will not appear on some models of indoor units Appears while the outdoor units are operated in th...

Страница 5: ...nstruction concerning use of the appliance by a person responsible for their safety This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial use by lay persons Do not use a leak detection additive Do not use refrigerant other than the type indicated in the manuals provided with the unit and on the nameplate Doing so may cause the un...

Страница 6: ...the outdoor unit will reduce the unit s efficiency Do not direct the airflow at plants or caged pets Ventilate the room frequently If the unit is operated continuously in a closed room for a long period of time the air will become stale In case of failure Warning Never remodel the air conditioner Consult your dealer for any repair or service Improper repair work can result in water leakage electri...

Страница 7: ...dy directly to cool air for a long time Excessive exposure to cool air is bad for your health and should therefore be avoided When the air conditioner is used together with burners thoroughly ventilate the area Insufficient ventilation can result in accidents due to oxygen deficiency Never place a burner at a place where it is exposed to the airflow from the air conditioner Doing so can result in ...

Страница 8: ...l 3 The same values are used for the set temperature for Cool Dry mode and the cooling set temperature for Auto mode dual set points Likewise the same values are used for the set temperature for Heat mode and the heating set temperature for Auto mode dual set points 4 The cooling and heating set temperatures can be set under the following conditions The cooling set temperature is greater than the ...

Страница 9: ...re used together with the air conditioner special precautions must be taken If the LOSSNAY ventilation unit developed by our company is used you can perform ventilation with less waste For details on this unit consult with your dealer 5 Caring for the machine Always have filter maintenance performed by a service person Before care taking turn the power supply OFF Caution Before you start cleaning ...

Страница 10: ...ting and defrosting operation Wait for a while Heating operation starts after ending defrosting operation It runs briefly but soon stops The CHECK and check code flash on the liquid crystal display There are some obstacles at the air inlet and outlet of the indoor and outdoor units Rerun after removal The filter is filled with dust and dirt Rerun after cleaning the filter Refer to section 5 Caring...

Страница 11: ...munication related businesses If the air conditioner is used in any of the above mentioned environments frequent operational failure can be expected It is advisable to avoid these types of installation sites For further details consult with your dealer Regarding electrical work Caution The electrical work must be undertaken by a person who is qualified as an electrical engineer according to the te...

Страница 12: ...9 0 14 5 18 0 21 0 14 5 18 0 21 0 23 0 28 0 32 0 External static pressure Pa 35 50 70 100 150 2 40 50 70 100 150 3 40 50 70 100 150 3 40 50 70 100 150 3 Sound level Low Middle High 5 dB A 24 28 32 22 28 31 22 28 31 27 32 35 Filter Standard filter P125VMA L E3 P140VMA L E3 Power source 220 240 V 50Hz Cooling capacity 1 Heating capacity 1 kW 14 0 16 0 16 0 18 0 Dimension Height Width Depth mm 250 14...

Страница 13: ...hich can be recycled and reused Electrical and electronic equipment at their end of life should be disposed of separately from your household waste Please dispose of this equipment at your local community waste collection recycling center In the European Union there are separate collection systems for used electrical and electronic product Please help us to conserve the environment we live in Deut...

Страница 14: ...ellung Ниво на звуковата мощност за отделните настройки на оборотите ако е приложимо Müravõimsustase kiiruse kohta kui asjakohane Niveau de puissance acoustique pour chaque réglage de la vitesse si disponible Poziom mocy akustycznej w stosownych przypadkach w zależności od ustawienia prędkości Akustiskās jaudas līmenis attiecīgā gadījumā katram ātruma iestatījumam Geluidsvermogensniveau per snelhe...

Страница 15: ...ations per minute 1595 1595 1735 1645 1645 1730 1780 1740 11 Specific ratio 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 12 Information relevant for facilitating disassembly recycling or disposal at end of life Your product should be disposed of separately from household waste in line with local laws and regulations When this product reaches its end of life dispose of it at your local waste collection point re...

Страница 16: ...ach oblasti obchodu a ľahkého priemyslu izjavlja v skladu z izključno odgovornostjo da so klimatske naprave in toplotne črpalke opisane spodaj za uporabo v stanovanjskih gospodarskih in manjših industrijskih okoljih kizárólagos felelőssége tudatában kijelenti hogy az alábbiakban leírt lakossági kereskedelmi és könnyűipari használatra szánt légkondicionálók és hőszivattyúk niniejszym oświadczamy że...

Страница 17: ...n te voorkomen Geluidsmetingen worden uitgevoerd in overeenstemming met JIS C9612 JIS B8616 ISO 5151 T1 en ISO 13523 T1 ОСТОРОЖНО Утечка хладагента может стать причиной удушья Обеспечьте вентиляцию в соответствии с EN378 1 Обязательно оберните трубы изоляционной обмоткой Непосредственный контакт с неизолированным трубопроводом может привести к ожогам или обморожению Запрещается класть элементы пит...

Страница 18: ... да обвиете тръбите с изолация Прекият контакт с неизолирани тръби може да доведе до изгаряния или измръзвания Никога не слагайте батерии в устата си по каквато и да било причина за да избегнете случайно поглъщане Поглъщането на батерии може да причини задавяне и или отравяне Инсталирайте модула на стабилна подложка за да предотвратите излишен шум или вибрации вследствие експлоатацията Измерваният...

Страница 19: ......

Страница 20: ...n the following EU regulations Low Voltage Directive 2014 35 EU Electromagnetic Compatibility Directive 2014 30 EU Machinery Directive 2006 42 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN KJ79K623H01_en ...

Отзывы: