20
→
Control modes
Control details
2. Fan
Remarks
2-3. Thermo OFF mode
When the thermoregulating function changes to OFF, the
indoor fan operates in [Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
No drain pump operation
However, when the control changes from COOL or DRY
operation, the drain pump operates for 3 minutes.
(1) Initial setting : OFF
→
HEAT···[last setting]
When changing the mode from exception of HEAT
to HEAT operation. ···[Downward C]
(2) Vane position :
Horizontal
→
Downward A
→
Downward B
→
Downward C
→
Swing
(3) Restriction of vane position
The vane is horizontally fixed for the following modes.
(The control by the remote controller is temporally invalidated
and it is controlled by the unit.)
•Thermo OFF
•Hot adjuster [Extra low] mode
•Heat defrost mode
3. Drain pump
4. Vane control
(Up/ down vane
change)
From the preceding page