6. Electrical work

F

A

H

C

D

E

G

I

I

I

H

B

B-1.

B-2.

Fig. 6-8

A

AB

TB6

B

Fig. 6-7

J

H

Fig. 6-9

6.7. Remote controller

1) Installing procedures

(1) Select an installing position for the remote controller. (Fig. 6-7)
The temperature sensors are located on both remote controller and indoor unit.

s

Procure the following parts locally:

Two piece switch box
Thin copper conduit tube
Lock nuts and bushings

A

Remote controller profile

B

Required clearances surrounding the remote controller

C

Installation pitch

(2) Seal the service entrance for the remote controller cord with putty to prevent pos-

sible invasion of dew drops, water, cockroaches or worms. (Fig. 6-8)

A

For installation in the switch box:

B

For direct installation on the wall select one of the following:

• Prepare a hole through the wall to pass the remote controller cord (in order to run

the remote controller cord from the back), then seal the hole with putty.

• Run the remote controller cord through the cut-out upper case, then seal the cut-

out notch with putty similarly as above.

B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:

(3) For direct installation on the wall

C

Wall

D

Conduit

E

Lock nut

F

Bushing

G

Switch box

H

Remote controller cord

I

Seal with putty

J

Wood screw

2) Connecting procedures (Fig. 6-9)

1

Connect the remote controller cord to the terminal block.

A

To TB5 on the indoor unit

B

TB6 (No polarity)

3) Temperature display setting

The initial temperature display setting is °C. Please change the setting to °F. Refer to
“Function selection of remote controller (Section 8)” in the operation manual for the
indoor unit.

4) Two remote controllers setting

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For
setting procedures, refer to “Function selection of remote controller” in the operation
manual for the indoor unit.

1-3/16

(30)

1-3/16

(30)

1-37/64 (46)

1-3/16

(30)

4-23/32 (120)

3-9/32 (83.5)

A

B

C

inch (mm)

7. Test run

7.1. Before test run

s

After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

7.2. Test run (Fig. 7-1)

The following 3 methods are available.

1

Turn on the power at least 12 hours before the test run.

2

Press the [TEST] button twice. 

 “TEST RUN” liquid crystal display

3

Press the [Mode selection] button. 

 Make sure that wind is blown out.

4

Press the [Mode selection] button and switch to the cooling (or heating) mode.

 Make sure that cold (or warm) wind is blown out.

5

Press the [Fan speed] button. 

 Make sure that the wind speed is switched.

6

Check operation of the outdoor unit fan.

7

Release test run by pressing the [ON/OFF] button. 

 Stop

8

Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an error
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the opera-
tion manual for the indoor unit.

Note:
• If an error code is displayed on the remote controller or if the air conditioner

does not operate properly, refer to the outdoor unit installation manual or
other technical materials.

• The OFF timer is set for the test run to automatically stop after 2 hours.
• During the test run, the time remaining is shown in the time display.
• During the test run, the temperature of the indoor unit refrigerant pipes is

shown in the room temperature display of the remote controller.

• When the VANE or LOUVER button is pressed, the message “NOT AVAIL-

ABLE” may appear on the remote controller display depending on the indoor
unit model, but this is not a malfunction.

Fig. 7-1

A

ON/OFF button

B

Test run display

C

Indoor temperature liquid line
temperature display

D

ON/OFF lamp

E

Power display

F

Error code display

Test run remaining time dis-
play

G

Set temperature button

H

Mode selection button

I

Fan speed button

M

TEST button

˚F

˚F

SIMPLE

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

TEST RUN
COOL, HEAT

A

F

C

E

D B

M

I

H G

Содержание City Multi PCFY-P NGMU-E

Страница 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners For Building Application INDOOR UNIT PCFY P NGMU E ...

Страница 2: ...t or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home a...

Страница 3: ...2 3 4 5 6 7 Fig 3 1 Fig 3 2 Fig 3 3 E D H C W A B U N IT 3 2 Preparation for installation Fig 3 2 Must be installed at least 8 ft 2 4 m above floor or grade level 3 2 1 Suspension bolt installing spacing inch Models A B C P15 36 23 32 39 5 8 8 9 32 P24 48 13 16 51 9 16 8 9 32 P30 48 13 16 51 9 16 10 5 8 P36 60 29 32 63 3 4 10 5 8 3 2 2 Refrigerant and drain tubing location inch Models D E F P15 5 ...

Страница 4: ...the wall 2 Installing the suspending bracket first onto the ceiling Fig 3 8 Installing procedures 1 Remove the suspending brackets U shaped washers and suspending bracket holding screws from the unit 2 Adjust the suspending bracket holding bolts on the unit 3 Attach the suspending brackets to the suspending bolts 4 Set hook the unit to the suspending brackets Be sure to install the U shaped washer...

Страница 5: ...ailable insulation materials heat resistant to 212 F 100 C or more thickness of 1 2 in 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam insu lation materials specific gravity of 0 03 thickness of 23 64 in 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut Use two wrenches to tighten piping connecti...

Страница 6: ...r left side tubing installation Fig 5 1 For left side tubing be sure to insert the rubber plug into the right drain port Install the drain tubing as it slopes continuously downward After completion of work check that correct drain is available from the outflow port of the drain tubing A Drain pan B Plug Fig 5 1 4 Installing the refrigerant piping 4 3 Indoor unit Fig 4 3 Installing procedures 1 Sli...

Страница 7: ...a 1 25 mm2 junction cable 1 MA Remote controller Fig 6 3 Connect the 1 and 2 on indoor unit TB15 to a MA remote controller Non polar ized 2 wire DC 9 to 13 V between 1 and 2 MA remote controller 2 M NET Remote controller Fig 6 4 Connect the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire DC 24 to 30 V between M1 and M2 M NET remote controller A Terminal block for ind...

Страница 8: ...ntroller If you want to sense room temperature with the built in sensor in a remote controller set SW1 1 on the control board to ON The setting of SW1 7 and SW1 8 as neces sary also makes it possible to adjust the air flow at a time when the heating thermom eter is OFF Fig 6 6 Address board 6 Electrical work G I J J J K K K K J J L K H 1 3 L1 L2 L4 r L3 2 Remarks Fig 6 5 Constraints on transmissio...

Страница 9: ...the power supply or control wiring wrong polarity and no disconnection of one phase in the supply s Use a 500 volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1 0 MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Ω...

Страница 10: ......

Страница 11: ......

Страница 12: ...his manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U668H01 ...

Отзывы: