Table1. Function setting options
(5) LOSSNAY setting (CITY MULTI only)
This setting is required only when the operation of CITY MULTI units is interlocked with LOSSNAY
units. This setting is not available for the M/P-series units. Interlock settings can be made for the
indoor unit to which the remote controller is connected. (They can also be confirmed or deleted.)
[Button operation]
Mode No.
Mode
Settings
Setting No.
Unit numbers
01
Automatic recovery after
power failure
Disable
1
Set “Grp.” for the Unit number.
These settings apply to all the
connected indoor units.
Enable (Four minutes of standby time
is required after the restoration of
power.)
2
02
Thermistor selection
(indoor temperature
detection)
Average temperature reading of the
indoor units in operation
1
Thermistor on the indoor unit to which
the remote controller is connected
(fixed)
2
Built-in sensor on the remote controller
3
03
LOSSNAY connection
Not connected
1
Connected (without outdoor air intake
by the indoor units )
2
Connected (with outdoor air intake by
the indoor units )
3
04
Power voltage
240 V
1
220 V, 230 V
2
05
Auto mode
Enable (Automatically the unit
achieves effective energy saving
operation.)
1
Disable
2
07
Filter sign
100 hours
1
Set “1, 2, 3, 4, or All” for the Unit
number.
These settings apply to each indoor
unit.
·
If “1, 2, 3, or 4” is set for the Unit
number, the settings apply only to
the specified indoor unit regardless
of the number of connected indoor
units (one through four units).
·
If “All” is set for the Unit number, the
settings apply to all the connected
indoor units regardless of the
number of connected indoor units
(one through four units).
2500 hours
2
Not displayed
3
08
Fan speed
Silent mode (or standard)
1
Standard (or High ceiling 1)
2
High ceiling (or High ceiling 2)
3
09
Outlet
4 directional
1
3 directional
2
2 directional
3
10
Optional parts
(High-efficiency filter)
No
1
Yes
2
11
Vane
No vanes (or the vane setting No.3 is
effective.)
1
Equipped with vanes (The vane
setting No.1 is effective.)
2
Equipped with vanes (The vane
setting No.2 is effective.)
3
Note:
· Use the centralized controller to make the settings if it is connected.
· To interlock the operation of the indoor units with the LOSSNAY units, be sure to interlock the addresses of ALL
indoor units in the group and that of the LOSSNAY unit.
1
When “Lossnay” on the Settings menu is selected, the remote controller
will automatically begin searching for the registered LOSSNAY
addresses of the currently connected indoor unit.