Contenido

1. Medidas de seguridad  ............................................................... 45

1.1. Antes de la instalación y de las conexiones 

eléctricas...................................................................... 45

1.2. Antes de la instalación  ................................................ 45
1.3. Antes de la instalación (traslado) - trabajo eléctrico .... 46
1.4. Antes de iniciar el funcionamiento de prueba  ............. 46

2. Espaciado .................................................................................. 47
3. Lista de piezas ........................................................................... 49
4. Modelos aplicables  .................................................................... 50
5. Preparación para la instalación  ................................................. 50

6. Procedimientos de instalación ....................................................51
7. Instalación del calefactor de panel  .............................................51
8. Cableado eléctrico ......................................................................52
9. Diagrama de cableado eléctrico y ajustes de los interruptores 

DIP  .............................................................................................54

10. Reensamblaje  ............................................................................54
11. Confirmación de un funcionamiento correcto .............................54
12. Los siguientes síntomas no son indicios de avería.  ...................55
13. Valoración de las averías  ...........................................................56

* Para obtener más información no incluida en este manual, consulte el Manual de instalación de la unidad exterior.
• Utilice el bloque de terminales suministrado para el calefactor de panel.
• Hay que configurar los interruptores para utilizar el calefactor de panel.
• Se recomienda usar una cubierta antinieve.
• Si el calefactor de panel se instala en un lugar donde el viento le sopla directamente, instale una protección cortavientos para 

lograr un efecto de calefacción suficiente.

1. Medidas de seguridad

1.1. Antes de la instalación y de las 

conexiones eléctricas

Símbolos utilizados en el texto

Advertencia:

Describe precauciones que deben tenerse en cuenta para evitar el riesgo
de lesiones o muerte del usuario.

Precaución:

Describe  las  precauciones  que  se  deben  tener  para  evitar  daños  en  la
unidad.

Símbolos utilizados en las ilustraciones

ADVERTENCIA DE ALTO VOLTAJE:

La caja de control incluye piezas con alto voltaje.

Al  abrir  o  cerrar  el  panel  frontal  de  la  caja  de  control,  no  permita  que
entre en contacto con ninguno de los componentes internos.

Antes  de  inspeccionar  el  interior  de  la  caja  de  control,  desconecte  la
unidad, manténgala así durante al menos 10 minutos y confirme que el
voltaje entre FT-P y FT-N en la placa INV haya bajado a 20 V CC o menos.
(Llevará  alrededor  de  10  minutos  descargar  la  electricidad  después  de
cortar el suministro eléctrico).

Advertencia:

La  instalación  del  aire  acondicionado  debe  correr  a  cargo  del
distribuidor o de un técnico autorizado.

- Una instalación incorrecta realizada por el usuario puede provocar fugas de

agua, descargas eléctricas o fuego.

Este  aparato  no  debe  ser  utilizado  por  personas  (niños  incluidos)  con
capacidades  físicas,  sensoriales  o  mentales  reducidas,  o  falta  de
experiencia y conocimiento, a menos que sean supervisadas o instruidas
en cuanto al uso del aparato por una persona que se responsabilice de
su seguridad.

Este aparato está destinado a ser utilizado por usuarios expertos o que
hayan recibido formación en las tiendas, en la industria ligera y en las
granjas, o para uso comercial por parte de personas no profesionales.

Utilice los cables especificados para la instalación eléctrica. Realice las
conexiones  asegurándose  de  que  cualquier  tracción  de  los  cables  no
afectará a los terminales.

- La  conexión  y  fijación  inadecuadas  pueden  provocar  calor  y  causar  un

incendio.

Utilice siempre los accesorios especificados por Mitsubishi Electric.

- Solicite a un técnico autorizado que instale los accesorios. Una instalación

incorrecta  realizada  por  el  usuario  puede  provocar  fugas  de  agua,
descargas eléctricas o fuego.

No repare nunca la unidad. Si la unidad requiere reparación, avise a su
distribuidor.

- Si la unidad se repara incorrectamente, pueden producirse fugas de agua,

descargas eléctricas o fuego.

Si el cable de alimentación eléctrica está dañado, deberá ser sustituido
por el fabricante, su agente de servicio o personas con una cualificación
similar con el fin de evitar riesgos.

Para reducir el riesgo de descarga eléctrica, no instale la unidad cuando
esté lloviendo.

Nunca  intente  reparar  la  unidad  si  no  dispone  de  las  cualificaciones
necesarias. Si el acondicionador de aire requiere reparación, avise a su
distribuidor, contratista o técnico cualificado en refrigeración.

- Si la unidad se repara incorrectamente, pueden producirse fugas de agua,

descargas eléctricas o fuego.

Las  conexiones  eléctricas  deberán  ir  a  cargo  de  un  electricista
autorizado según las “Normas técnicas para instalaciones eléctricas” y
las “Regulaciones de cableado en cada área”, así como las instrucciones
de este manual, y siempre usando una fuente de alimentación dedicada.

- Si  el  amperaje  de  la  fuente  de  alimentación  es  inadecuada  o  el  tendido

eléctrico  es  incorrecto,  pueden  producirse  fugas  de  agua,  descargas
eléctricas o fuego.

Instale  la  tapa  de  terminales  (panel)  de  la  unidad  exterior  de  forma
segura.

- Si la tapa de terminales (panel) no se instala correctamente, pueden entrar

polvo o agua en la unidad exterior provocando fuego o descargas eléctricas.

Cuando  mueva  o  reinstale  el  acondicionador  de  aire,  consulte  con  el
distribuidor o con un técnico autorizado.

- Si el acondicionador de aire se instala incorrectamente, pueden producirse

fugas de agua, descargas eléctricas o fuego.

No reconstruya ni cambie los ajustes de los dispositivos de protección.

- Si  se  cortocircuita  o  manipula  a  la  fuerza  el  interruptor  de  presión,  el

interruptor  térmico,  el  fusible  u  otros  dispositivos  de  protección,  o  si  se
utilizan piezas distintas a las especificadas por  Mitsubishi Electric,  puede
producirse un incendio o explosión.

Para deshacerse de este producto consulte con su distribuidor.

Las  personas  responsables  de  la  instalación  y  del  sistema  deberán
garantizar  la  seguridad  frente  al  riesgo  de  posibles  fugas  de  acuerdo
con la normativa local.

Es necesario vigilar a los niños para impedir que jueguen con la unidad.

1.2. Antes de la instalación

Precaución:

No utilice el equipo de aire acondicionado en entornos especiales.

- Aceite, vapor, gas sulfúrico, etc. pueden reducir de forma considerable el

rendimiento del aparato o deteriorar sus piezas.

Si  instala  la  unidad  en  un  hospital,  una  central  de  comunicaciones  u
otro  lugar  de  características  similares,  proteja  convenientemente  el
aparato para que no produzca ruido.

- El equipo inversor, los generadores, el equipo médico de alta frecuencia o

el de emisión de radio pueden provocar que el aparato funcione de forma
errónea o que no funcione. A su vez, el aire acondicionado puede incidir en
dicho  equipo  creando  ruido  que  distorsione  el  tratamiento  médico  o  la
transmisión de la imagen.

Para reducir el riesgo de lesiones, lleve puesto un equipo de protección
al trabajar en el controlador.

Antes de instalar la unidad, asegúrese de haber leído el 
capítulo de “Medidas de seguridad”.

Las “Medidas de seguridad” señalan aspectos muy 
importantes sobre seguridad. Es importante que se cumplan 
todos.

: Indica una acción que debe evitarse.

: Indica que deben seguirse unas instrucciones importantes.

: Indica una pieza que debe estar conectada a tierra.

: Tenga cuidado con las descargas eléctricas. (Este símbolo aparece en la 

etiqueta de la unidad principal.) <Color: amarillo>

Advertencia:

Lea atentamente las etiquetas adheridas a la unidad principal.

WT09190X01.book  45 ページ  2018年11月29日 木曜日 午前8時59分

Содержание CITY MULTI PAC-PH01EHYU-E

Страница 1: ...er ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit E MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado WT09190X01 book 1 ページ 2018年11...

Страница 2: ...nverter control box by unscrewing the two screws B Remove the cover from main control box by unscrewing the three screws A Top attachment B Bottom attachment C Main control box D Inverter control box Fig 6 0 2 C B B A A A A A A Right side Left side Rear side Fig 6 0 3 A Unscrew the three screws each on the right left and rear fin guards B Remove the metal sheet wiring cover AFin guard BCover wirin...

Страница 3: ...ft side Right side A Unscrew the two screws each on the right and left panels A Left panel B Right panel A A Fig 6 0 5 A Unscrew the two screws on the rear panel A Rear panel Rear side WT09190X01 book 3 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 4: ...1 2 A A A Remove the control box front cover by unscrewing the five screws A Control box front cover C B B A A A A Right side Left side A Unscrew the three screws each on the right and left fin guards B Remove the metal sheet wiring cover AFin guard BCover wiring 1 CCover wiring 4 in case of left side Fig 6 1 3 WT09190X01 book 4 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 5: ...e metal sheet wiring cover A Fin guard B Cover wiring 1 Fig 6 1 5 A Unscrew the two screws each on the right and left panels A Left panel B Right panel A A Left side B A Right side A A Fig 6 1 6 A Unscrew the four screws on the rear panels A Rear panel Rear side WT09190X01 book 5 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 6: ...g 6 2 2 A Remove the control box front cover by unscrewing the five screws A Control box front cover C B B A A A A Left side Right side Fig 6 2 3 A Unscrew the three screws each on the right and left fin guards B Remove the metal sheet wiring cover AFin guard BCover wiring 1 CCover wiring 4 in case of left side WT09190X01 book 6 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 7: ...e metal sheet wiring cover A Fin guard B Cover wiring 1 A A B A Fig 6 2 5 Left side Right side A Unscrew the two screws each on the right and left panels A Left panel B Right panel A A Fig 6 2 6 A Unscrew the two screws on the rear panels A Rear panel Rear side WT09190X01 book 7 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 8: ...the right panel and tighten it with two screws together A Right panel B Panel heater R Right wiring port type wiring color Blue Wiring port B A B A C S module A Attach the rubber spacer to the screw hole B Attach the panel heater to the upper side of the rear panel and tighten it with two screws together Attach the panel heater using the supplied long type M5 screws A Rear panel B Rubber spacer C ...

Страница 9: ...hten it with two screws together Attach the panel heater using the supplied long type M5 screws A Rear panel B Rubber spacer C Panel heater BR Left wiring port type wiring color White D Panel heater BL Right wiring port type wiring color Red Right rear side Left rear side L XL module Wiring port Wiring port WT09190X01 book 9 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 10: ...r wirings so that the wirings run along the left rear pillar D Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar E Place the cover back and fix the cover with the tie band A Unit wiring B Cover C Tie band D Water proof cap on the unit wiring connector E Panel heater wiring F Fin guard G Pillar D C A F F E A G G E E C F A B E A A B...

Страница 11: ...iring connector B Pull up the panel heater wirings so that the wirings run along the right rear pillar C Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin guard E Pillar F Tie band A A B C B F A D A...

Страница 12: ...he water proof cap from the unit wiring connector B Pull up the panel heater wirings so that the wirings run along the right rear pillar C Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin guard E P...

Страница 13: ... 8 1 0 Fig 8 1 0 6 A B C A Rear side A Screw down the metal sheet wiring cover and the fin guard at three points A Fin guard B Cover wiring 1 C Cover wiring 2 WT09190X01 book 13 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 14: ...ft rear pillar D Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar E Place the cover back and fix the cover with the tie band A Unit wiring B Cover C Tie band D Water proof cap on the unit wiring connector E Panel heater wiring F Fin guard G Pillar Fig 8 1 1 2 A B A A C A D Left side A Screw down the metal sheet wiring cover and t...

Страница 15: ...he panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin guard E Pillar F Tie band Fig 8 1 1 4 A B C A Right side A Screw down the metal sheet wiring cover and the fin guard at three points A Fin guard B Cover wiri...

Страница 16: ...g and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin guard E Pillar F Tie band B C C D C B F A A D E E D D D C C B D F E E B D D A A C Left rear side Fig 8 1 1 6 A B D B D A A Rear side A Screw down the metal sheet wiring cover and the fin guard at th...

Страница 17: ...ect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin guard E Pillar F Tie band Fig 8 1 2 2 A B C A A Screw down the metal sheet wiring cover and the fin guard at three points A Fin guard B Cover wiring 1 C...

Страница 18: ...ight rear pillar C Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin guard E Pillar F Tie band Fig 8 1 2 4 A B D B D A A Rear side A Screw down the metal sheet wiring cover and the fin guard at thre...

Страница 19: ...A 2 1 Control Board Control BOX CN510 208 230 V 60 Hz S module L XL module Fig 9 0 1 Fig 9 0 2 Dipswitch settings 1 Set SW4 while the unit is stopped 1 Set the 10th bit of SW6 to ON 2 Set SW4 as shown in the table below to select the setting item No 974 The setting item No will be displayed on LED1 3 Press SWP3 for two seconds or longer to change the settings The settings can be checked on LED3 Se...

Страница 20: ...plate on the main control box cover A Label Fig 10 0 2 Re place all components as they were L XL module Fig 10 1 1 A A Attach the supplied wiring diagram nameplate under the caution plate on the control box front cover A Label Fig 10 1 2 Re place all components as they were WT09190X01 book 20 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 21: ... unit is repaired improperly water leakage electric shock or fire may result If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard To reduce the risk of electric shock do not install the unit when it is raining Never attempt to repair the unit without the proper qualifications If the air conditioner must be...

Страница 22: ...the product Its weight is in excess of 20 kg 45 LBS Some products use PP bands for packaging Do not use any PP bands as a means of transportation It is dangerous Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other injuries Tear apart and throw away plastic packaging bags so that children will not play with them If childre...

Страница 23: ... to the right or left L3 needs to be small 450 17 3 4 450 17 3 4 30 1 3 16 Add the dimension that exceeds the height limit shown as h1 through h3 in the figures to L1 L2 and L3 as shown in the table below When the wall s at the front and or the right left exceed s their height limits When the wall at the rear exceeds its height limit When all walls exceed their height limits Required minimum dista...

Страница 24: ...s L4 need to be small When the distance behind the block of units L2 needs to be small Required minimum distance mm in Required minimum distance mm in L1 Front L2 Rear L4 Between L1 Front L2 Rear L4 Between 450 17 3 4 h1 450 17 3 4 h2 30 1 3 16 450 17 3 4 h1 300 11 13 16 h2 450 17 3 4 When there are walls in the front and rear of the block of units When there is a wall on either the right or left ...

Страница 25: ...R SPACER INSTALLATION MANUAL LABEL WIRING Shape Qty 4 2 1 1 Parts name 1 2 3 4 5 6 PANELHEATER L PANELHEATER R PANELHEATER BL PANELHEATER BR COVER WIRING 2 COVER WIRING 3 Shape Qty 1 1 1 1 2 2 Parts name 7 8 9 0 a CABLE TIE M5 SCREW RUBBER SPACER INSTALLATION MANUAL LABEL WIRING Shape Qty 5 6 4 1 1 Wiring color Yellow Wiring color Blue Wiring color White Paper Wiring color Yellow Wiring color Blue...

Страница 26: ...o not lose these screws Parts name 1 2 3 4 5 6 PANELHEATER L PANELHEATER R PANELHEATER BL PANELHEATER BR COVER WIRING 2 COVER WIRING 3 Shape Qty 1 1 1 1 2 2 Parts name 7 8 9 0 a CABLE TIE M5 SCREW RUBBER SPACER INSTALLATION MANUAL LABEL WIRING Shape Qty 5 6 4 1 1 Unit model Outdoor unit module Bottom surface size W D mm PAC PH01EHYU E S 920 740 PAC PH02EHYU E L 1240 740 PAC PH03EHYU E XL 1750 740 ...

Страница 27: ...r A Unscrew the three screws each on the right and left fin guards B Remove the metal sheet wiring cover A Fin guard B Cover wiring 1 C Cover wiring 4 in case of left side A Unscrew the three screws each on the rear fin guards B Remove the metal sheet wiring cover A Fin guard B Cover wiring 1 A Unscrew the two screws each on the right and left panels A Left panel B Right panel A Unscrew the four s...

Страница 28: ...onnecter C Pull up the panel heater wirings so that the wirings run along the left rear pillar D Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar E Place the cover back and fix the cover with the tie band A Unit wiring B Cover C Tie band D Water proof cap on the unit wiring connector E Panel heater wiring F Fin guard G Pillar A S...

Страница 29: ... Cover wiring 1 C Cover wiring 3 A As with A and B in Fig 8 1 0 1 remove the water proof cap from the unit wiring connector B Pull up the panel heater wirings so that the wirings run along the right rear pillar C Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover wit...

Страница 30: ...emove the water proof cap from the unit wiring connector B Pull up the panel heater wirings so that the wirings run along the right rear pillar C Connect the panel heater wiring and the unit wiring and run the connected wiring between the fin guard and the pillar D As with E in Fig 8 1 0 1 place the cover back and fix the cover with the tie band A Unit wiring B Cover C Panel heater wiring D Fin gu...

Страница 31: ... temperature during the defrost operation outdoor temperature 15 deg The heater does not turn off when TH7 4 C Panel heater OFF conditions are not met Panel heater OFF conditions The outdoor unit is in cooling mode or stop mode or the compressor is stopped or outdoor temperature is above 7 C TH7 7 C and three minutes have passed since the defrost operation is completed The drain water is drained f...

Страница 32: ...t sunlight in midsummer or a burner The heater stops operation for safety purpose when the temperature of the sheet metal becomes too high Change the conditions of this surface to the same conditions as for other surfaces Do structural components move when the heater is removed and swung widely The heating element may have been displaced To prevent empty heating replace the heater with a new one 3...

Страница 33: ...adéquats peuvent s échauffer et causer un incendie Utilisez toujours les accessoires spécifiés par Mitsubishi Electric Demandez à un technicien autorisé d installer les accessoires Une installation incorrecte par l utilisateur peut avoir comme conséquence une fuite d eau un choc électrique ou un incendie Ne réparez jamais l appareil Si le climatiseur doit être réparé consultez le distributeur Une ...

Страница 34: ...relais de courants de fugue sur le côté de l unité et en aval du système d alimentation peuvent s activer En fonction de l importance du système séparez le système d alimentation ou coordonnez les disjoncteurs pour garantir la protection du système Arrêtez le fonctionnement et mettez hors tension avant le nettoyage Ne lavez pas le climatiseur Le fait de le laver peut provoquer un choc électrique F...

Страница 35: ...ite ou à gauche L3 doit être faible 450 17 3 4 450 17 3 4 30 1 3 16 Ajoutez la dimension qui dépasse la limite de hauteur indiquée de h1 à h3 dans les figures à L1 L2 et L3 comme indiqué dans la table ci dessous Si la les paroi s à l avant et ou à droite gauche dépasse nt leurs limites de hauteur Si la paroi à l arrière dépasse sa limite de hauteur Si toutes les parois dépassent leurs limites de h...

Страница 36: ...re faibles Si la distance derrière le bloc d appareils L2 doivent être faible Distance minimale nécessaire mm po Distance minimale nécessaire mm po L1 Avant L2 Arrière L4 Entre L1 Avant L2 Arrière L4 Entre 450 17 3 4 h1 450 17 3 4 h2 30 1 3 16 450 17 3 4 h1 300 11 13 16 h2 450 17 3 4 S il y a des parois à l avant et à l arrière du bloc d appareils S il y a une paroi sur le côté droit ou gauche du ...

Страница 37: ...accordement étiquette Forme Qté 4 2 1 1 Désignation de la pièce 1 2 3 4 5 6 Réchauffeur de panneau L Réchauffeur de panneau R Réchauffeur de panneau BL Réchauffeur de panneau BR Cache câble 2 Cache câble 3 Forme Qté 1 1 1 1 2 2 Désignation de la pièce 7 8 9 0 a Collier de serrage Vis M5 Entretoise en caoutchouc Manuel d installation Raccordement étiquette Forme Qté 5 6 4 1 1 Couleur du câble Jaune...

Страница 38: ...on de la pièce 1 2 3 4 5 6 Réchauffeur de panneau L Réchauffeur de panneau R Réchauffeur de panneau BL Réchauffeur de panneau BR Cache câble 2 Cache câble 3 Forme Qté 1 1 1 1 2 2 Désignation de la pièce 7 8 9 0 a Collier de serrage Vis M5 Entretoise en caoutchouc Manuel d installation Raccordement étiquette Forme Qté 5 6 4 1 1 Modèle d unité Appareil extérieur module Taille du fond L P PAC PH01EHY...

Страница 39: ...rcle avant du boîtier de commande en dévissant les cinq vis A Couvercle avant du boîtier de commande A Dévissez les trois vis sur chacune des protections de l ailette droite et gauche B Retirez le cache câble métallique A Protection de l ailette B Cache câble 1 C Cache câble 4 pour le côté gauche A Dévissez les trois vis sur chacune des protections de l ailette arrière B Retirez le cache câble mét...

Страница 40: ...upérieure du panneau arrière et fixez le à l aide des deux vis Fixez le réchauffeur de panneau à l aides des vis longues M5 fournies A Panneau arrière B Entretoise en caoutchouc C Réchauffeur de panneau BR Type de raccordement à gauche couleur du câblage Blanc D Réchauffeur de panneau BL Type de raccordement à droite couleur du câblage Rouge A Coupez le collier de serrage qui fixe le cache du câbl...

Страница 41: ...che câble 2 A Comme pour A et B dans Fig 8 1 0 1 retirez le capuchon étanche du connecteur du câblage de l unité B Tirez les câbles du réchauffeur de panneau vers le haut afin qu ils passent le long du pilier arrière droit C Raccordez le câblage du réchauffeur de panneau et le câblage de l unité puis faites passer le câblage raccordé entre la protection de l ailette et le pilier D Comme pour E dan...

Страница 42: ...l unité B Tirez les câbles du réchauffeur de panneau vers le haut afin qu ils passent le long du pilier arrière droit C Raccordez le câblage du réchauffeur de panneau et le câblage de l unité puis faites passer le câblage raccordé entre la protection de l ailette et le pilier D Comme pour E dans Fig 8 1 0 1 remettez le cache et fixez le à l aide du collier de serrage A Câblage de l unité B Cache C...

Страница 43: ... égale ou inférieure à 40 C Si la résistance est égale à 2880 Ω 7 elle indique la rupture de l un des câbles Le réchauffeur de panneau est froid alors que les conditions d activation ON du réchauffeur sont remplies L unité extérieure fonctionne en aspirant l air extérieur Par conséquent le réchauffeur de panneau a tendance à être froid lorsque l unité extérieure fonctionne Contrôlez le réchauffeur...

Страница 44: ... brûleur Le réchauffeur s arrête par mesure de sécurité lorsque la température de la tôle métallique est trop élevée Placez cette surface dans les mêmes conditions que les autres surfaces Des éléments de structure se déplacent ils en cas de dépose du réchauffeur ou de son pivotement L élément de chauffage peut avoir été déplacé Pour éviter un chauffage à vide remplacez le réchauffeur par un neuf 3...

Страница 45: ...correctamente pueden producirse fugas de agua descargas eléctricas o fuego Si el cable de alimentación eléctrica está dañado deberá ser sustituido por el fabricante su agente de servicio o personas con una cualificación similar con el fin de evitar riesgos Para reducir el riesgo de descarga eléctrica no instale la unidad cuando esté lloviendo Nunca intente reparar la unidad si no dispone de las cu...

Страница 46: ...ona sola no debe cargar con el producto El producto pesa más de 20 kg 45 lb En algunos productos se utilizan cintas de polipropileno PP para el embalaje No utilice bandas de polipropileno como medio de transporte Es peligroso Retire los materiales de embalaje de forma segura Los materiales de embalaje como clavos y otras piezas metálicas o de madera pueden producir cortes u otras heridas Rompa y t...

Страница 47: ...ncia en los lados derecho e izquierdo L3 450 17 3 4 450 17 3 4 30 1 3 16 Sume la dimensión que supera el límite de altura indicada como h1 a h3 en las figuras a L1 L2 y L3 como muestra la siguiente tabla Cuando la s pared es de la parte frontal o derecha izquierda superen sus límites de altura Cuando la pared de la parte posterior supere su límite de altura Cuando todas las paredes superen sus lím...

Страница 48: ...tancia detrás del bloque de unidades L2 Distancia mínima obligatoria mm pulg Distancia mínima obligatoria mm pulg L1 frontal L2 posterior L4 entre L1 frontal L2 posterior L4 entre 450 17 3 4 h1 450 17 3 4 h2 30 1 3 16 450 17 3 4 h1 300 11 13 16 h2 450 17 3 4 Cuando haya paredes en la parte frontal y trasera del bloque de unidades Cuando haya una pared en el lado derecho o izquierdo del bloque de u...

Страница 49: ...TIQUETA DE CABLEADO Forma Cant 4 2 1 1 Nombre de las piezas 1 2 3 4 5 6 CALEFACTOR DE PANEL L CALEFACTOR DE PANEL R CALEFACTOR DE PANEL BL CALEFACTOR DE PANEL BR TAPA DE CABLEADO 2 TAPA DE CABLEADO 3 Forma Cant 1 1 1 1 2 2 Nombre de las piezas 7 8 9 0 a SUJETACABLES TORNILLO M5 ESPACIADOR DE GOMA MANUAL DE INSTALACIÓN ETIQUETA DE CABLEADO Forma Cant 5 6 4 1 1 Color de cableado amarillo Color de ca...

Страница 50: ... de las piezas 1 2 3 4 5 6 CALEFACTOR DE PANEL L CALEFACTOR DE PANEL R CALEFACTOR DE PANEL BL CALEFACTOR DE PANEL BR TAPA DE CABLEADO 2 TAPA DE CABLEADO 3 Forma Cant 1 1 1 1 2 2 Nombre de las piezas 7 8 9 0 a SUJETACABLES TORNILLO M5 ESPACIADOR DE GOMA MANUAL DE INSTALACIÓN ETIQUETA DE CABLEADO Forma Cant 5 6 4 1 1 Modelo de unidad Unidad exterior Módulo Tamaño superficie inferior an pr mm PAC PH0...

Страница 51: ...s derecho e izquierdo B Retire la tapa de cableado de chapa metálica A Guardaaletas B Tapa de cableado 1 C Tapa de cableado 4 en el caso del lado izquierdo A Desatornille los tres tornillos en los guardaaletas posteriores B Retire la tapa de cableado de chapa metálica A Guardaaletas B Tapa de cableado 1 A Desatornille los dos tornillos en los paneles derecho e izquierdo A Panel izquierdo B Panel d...

Страница 52: ...iba de forma que pasen por la columna posterior izquierda D Conecte el cableado del calefactor de panel y el cableado de la unidad y haga pasar el cableado conectado entre el guardaaletas y la columna E Vuelva a colocar la tapa y fíjela con la cinta de sujeción A Cableado de la unidad B Tapa C Cinta de sujeción D Cubierta impermeable del conector del cableado de la unidad E Cableado del calefactor...

Страница 53: ... igual que con A y B en la Fig 8 1 0 1 retire la cubierta impermeable del conector del cableado de la unidad B Tire de los cables del calefactor de panel hacia arriba de forma que pasen por la columna posterior derecha C Conecte el cableado del calefactor de panel y el cableado de la unidad y haga pasar el cableado conectado entre el guardaaletas y la columna D Al igual que con E en la Fig 8 1 0 1...

Страница 54: ...re de los cables del calefactor de panel hacia arriba de forma que pasen por la columna posterior derecha C Conecte el cableado del calefactor de panel y el cableado de la unidad y haga pasar el cableado conectado entre el guardaaletas y la columna D Al igual que con E en la Fig 8 1 0 1 vuelva a colocar la tapa y fíjela con la cinta de sujeción A Cableado de la unidad B Tapa C Cableado del calefac...

Страница 55: ...escongelación Nota La temperatura del calefactor de panel durante la operación de descongelación temperatura exterior 15 grados El calefactor no se apaga cuando TH7 4 C No se cumplen las condiciones de apagado del calefactor de panel Condiciones de apagado del calefactor de panel la unidad exterior está en modo de enfriamiento o parada o el compresor está parado o la temperatura exterior es superi...

Страница 56: ...a de funcionar por razones de seguridad cuando la temperatura de la chapa metálica aumenta demasiado Cambie las condiciones de esta superficie para que sean las mismas que para otras superficies Se mueven los componentes estructurales cuando se quita el calefactor y se balancea ampliamente Puede que se haya desplazado el elemento calefactor Para evitar un calentamiento vacío sustituya el calefacto...

Страница 57: ...WT09190X01 book 197 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 58: ...WT09190X01 book 198 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 59: ...WT09190X01 book 199 ページ 2018年11月29日 木曜日 午前8時59分 ...

Страница 60: ...T09190X01 This product is designed and intended for use in the residential commercial and light industrial environment Please be sure to put the contact address telephone number on this manual before handing it to the customer WT09190X01 book 200 ページ 2018年11月29日 木曜日 午前8時59分 ...