Twinning pipe(high pressure)

c

e

d

a

b

To BC controller

To BC controller

Twinning kit(low pressure)

Heat source unit 1

Heat source unit 2

1780

20

880

880

1. Confirming the Package Contents

The following items are included with the Twinning Kit (CMY-Q100VBK). Verify that all items are present before starting installation.

❈ 

Always use the twinning pipes included in the kit when preparing the twinning kit.

If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.

(1) Package contents

Model

CMY-Q100VBK

Model

CMY-Q100VBK

1

1

1

1

1

1

1

1

1

1

1

2

1

1

Low-pressure

twinning kit

2

High-pressure

twinning pipe

3

Fixing screw

4

Elbow pipe

Ø22.2 [7/8]

5

Elbow pipe

Ø28.58 [1-1/8]

6

High-pressure

pipe

7

Pipe cover

1

D

ID22.2 [7/8]

-ID25.4 [1]

B

Insulation cover

A

Installation Manual

(this booklet)

0

OD22.2 [7/8]

-ID25.4 [1]

9

OD22.2 [7/8]

-ID19.05 [3/4]

8

OD19.05 [3/4]

-ID15.88 [5/8]

C

Cable tie

(2) List of field-supplied parts

· Refrigerant pipes other than the ones provided in the kit
· Heat-resistant insulation material (for field-supplied refrigerant pipes)
· Insulation cover tape

CMY-Q100VBK

PQRY-P600YSHM-A
PQRY-P300YHM-A
PQRY-P300YHM-A

PQRY-P250YHM-A

PQRY-P250YHM-A

PQRY-P500YSHM-A

Low pressure

Twinning pipe connection size

Heat Source unit 1

Component unit name

Package unit name

BC controller~Twinning pipe

a

b

PQRY-P400YSHM-A
PQRY-P200YHM-A
PQRY-P200YHM-A

High pressure

Low pressure

c

d

High pressure

e

High pressure

Twinning pipe Kit(optional parts)

Twinning pipe~Heat Source unit 1
Twinning pipe~Heat Source unit 2
Twinning pipe~Heat Source unit 2

Heat Source unit 2

PQRY-P450YSHM-A
PQRY-P250YHM-A
PQRY-P200YHM-A

PQRY-P550YSHM-A
PQRY-P300YHM-A
PQRY-P250YHM-A

Ø28.58

(

*

)

Ø22.2

Ø28.58
Ø19.05

Ø22.2

Ø19.05

2. Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1) Pipe size

1

Field-supply the pipes to be connected to the kit.

2

If the pipe was cut with a pipe cutter, remove the

burrs and eliminate foreign materials before
connecting.

On the low-pressure side, the twinning kit connects to

the field-supplied pipes inside the heat source unit.

The distributor on the low-pressure side must be

placed in the heat source unit that has a larger
capacity index of the two, regardless of the relative
positions of the heat source units or their addresses.

If the distributor is placed in the heat source unit that

has a smaller capacity, refrigerant will not be properly
distributed and compressor failure may result.

( If heat source units that have the same capacity are

used in combination, the distributor can be placed in
either heat source unit.)

Choose the correct size pipe using the above table. Connect the field- supplied pipe to the twinning kit for the sizes in the

table that are marked with an asterisk (*).

2

See reverse.

Содержание CITY MULTI CMY-Q100VBK

Страница 1: ...ions or alterations Consult your dealer for repair Improper installation may result in water leakage electric shock or fire In the event of a refrigerant leak thoroughly ventilate the room If refrigerant leaks and comes in contact with an open flame toxic gases will be generated Properly install all parts according to the instructions in the Installation Manual If the wrong twinning pipe or wrong ...

Страница 2: ...kage unit name BC controller Twinning pipe a b PQRY P400YSHM A PQRY P200YHM A PQRY P200YHM A High pressure Low pressure c d High pressure e High pressure Twinning pipe Kit optional parts Twinning pipe Heat Source unit 1 Twinning pipe Heat Source unit 2 Twinning pipe Heat Source unit 2 Heat Source unit 2 PQRY P450YSHM A PQRY P250YHM A PQRY P200YHM A PQRY P550YSHM A PQRY P300YHM A PQRY P250YHM A Ø28...

Страница 3: ... above 120 C 248 F Place a wet towel on the refrigerant service valve before brazing the pipes Direct the blazing torch flame away from the adjacent cables and sheet metal to keep them from being damaged CAUTION 2 Connecting the twinning pipe kit 1 Braze the high pressure pipe 6 to the refrigerant service valve 2 Screw down the low pressure twinning pipe kit 1 to the sheet metal of the refrigerant...

Страница 4: ...Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material field supplied pipe Heat resistant insulation material field supplied Heat resistant insulation material field supplied field supplied pipe field supplied pipe 2High pressure twinning pipe BInsulation cover Tape field supplied To be gap free To be gap fre...

Страница 5: ...Related Links Model Number CMY Q100VBK CMY Q100VBK Installation Manual WT05688X01 ...

Отзывы: