3

(2) Low-pressure twinning kit in CMY-ER200CBK

Use 

1

 in table "(1) Package Contents." Attach items 

j

k

and 

l

 to the stop valve sheet metal and then to the low-

pressure twinning kit to hold it into place.

1. Attach item 

l

 to the stop valve sheet metal. 

2. Attach the packing and saddle. 
3. Secure the low pressure twinning kit.

(3) 

Routing the pipe through the bottom

(1) Braze item 

7

 high-pressure pipe to the refrigerant service valve so 

that the dimples on the pipe are parallel to the edge of the cutout 
hole. Expand the end of the 

¿

eld-supplied pipes

 and braze them to 

item 

7

 high-pressure pipe.

(2) Attach item 

1

 low-pressure twinning kit to the sheet metal of the 

refrigerant service valve with item 

3

 screw

 and braze it to the 

refrigerant service valve.

(3) Braze item 

6

 elbow pipe to the 

¿

eld-supplied pipe 

¿

rst

 and then 

braze it to item 

1

 low-pressure twinning kit.

(4) Flare the 

¿

eld-supplied pipe end

 and braze the pipe to the low-

pressure pipe in the middle.

(5) Wrap the pipe in front of item 

1

 low-pressure twinning kit with item 

9

 pipe cover

 and attach compressor cables to item 

9

 pipe cover 

with item 

4

 cable tie to keep them out of direct contact with the 

pipes.

(4) Routing the pipe through the front

(1) Braze item 

8

 high-pressure pipe to the refrigerant service valve.

(2) Attach item 

1

 low-pressure twinning kit to the sheet metal of the 

refrigerant service valve with item 

3

 screw

 and braze it to the 

refrigerant service valve.

(3) Braze item 

6

 elbow pipe to the 

¿

eld-supplied pipe 

¿

rst

 and then 

braze it to item 

1

 low-pressure twinning kit.

(4) Braze item 

5

 elbow pipe to the low-pressure pipe in the middle. 

(5) Wrap the pipe in front of item 

1

 low-pressure twinning kit with item 

9

 pipe cover

 and attach compressor cables to item 

9

 pipe cover 

with item 

4

 cable tie to keep them out of direct contact with the 

pipes.

(5) Slope of twinning pipes (high-pressure side only) 

Make sure the slope of the twinning pipes are at an angle 
within ±15˚ to the horizontal plane. 
If the slope exceeds the specified angle, the unit may be 
damaged.

Note. Refer to the figure below for the installation position of the twinning pipe.

· Before heating the pipes, place a wet towel on the refrigerant service 

valve to keep its temperature below 120˚C [248˚F].

· Direct the flame away from the cables and sheet metals inside the unit 

so as not to burn them. 

CAUTION

· Before heating the pipes, place a wet towel on the refrigerant service 

valve to keep its temperature below 120˚C [248˚F].

· Direct the flame away from the cables and sheet metals inside the unit 

so as not to burn them. 

CAUTION

j

,

k

,

l

3

3

1

1

3

6

1

3

6

5

8

9

Section to be brazed locally

Connect the pipe so that the 
dimples on the 

7

 high pressure 

pipe are parallel to the edge of 
the cutout hole.

9

  

Wrap the pipe cover here. 
Attach compressor cables to pipe 
cover with cable tie to keep them 
out of direct contact with the pipes.

Wrap the pipe cover here. 
Attach compressor cables to pipe 
cover with cable tie to keep them 
out of direct contact with the pipes.

Field-supplied pipes

Field-supplied 
pipes

Field-supplied pipes

±15

˚

Twinning pipe on the high-pressure side

Slope of the twinning pipe is at an angle within ±15° to the horizontal plane.

Refrigerant 
service valve

Содержание CITY MULTI CMY-ER200CBK

Страница 1: ...ents with bare hands during and immediately after operation In the event of a refrigerant leak thoroughly ventilate the room s Improper installation may result in refrigerant gas leakage and equipment damage s If the wrong twinning pipe or wrong size connecting pipe is used air conditioning performance will suffer s If leaked refrigerant comes in contact with a heat source such as a fan heater sto...

Страница 2: ...the Package Contents The following items are included with the Twinning Kit CMY ER200CBK Verify that all items are present before starting installation Always use the twinning pipes included in the kit when preparing the twinning kit If the field supplied pipes do not fit the parts in the kit use the accessory piping parts listed below 1 Package contents Model 1 Low pressure twinning kit 2 High pres...

Страница 3: ...ze it to item 1 low pressure twinning kit 4 Braze item 5 elbow pipe to the low pressure pipe in the middle 5 Wrap the pipe in front of item 1 low pressure twinning kit with item 9 pipe cover and attach compressor cables to item 9 pipe cover with item 4 cable tie to keep them out of direct contact with the pipes 5 Slope of twinning pipes high pressure side only Make sure the slope of the twinning p...

Страница 4: ...lation covers can shrink Overlap the tape as shown in the left figure so that there will be no gap in between the insulation cover or field installed insulation material 6 The length of the straight pipe between indoor units and the twinning pipe high pressure pipe Use the pipes supplied in the twinning kit and make sure the section of the field supplied pipe that connects to the twinning pipe has at...

Отзывы: