![Mitsubishi Electric AJ65BT64DAV/DAI Скачать руководство пользователя страница 25](http://html.mh-extra.com/html/mitsubishi-electric/aj65bt64dav-dai/aj65bt64dav-dai_user-manual_238810025.webp)
3. SPECIFICATIONS
MELSEC-A
3-10
3.5
I/O Signals to the Master Station
Assignment of the I/O signals and function of each signal are explained.
3.5.1
I/O signal list
The AJ65BT-64DAV/DAI uses 32 input points and 32 output points for exchanging signals with the
master station.
*
1
The allocation of the I/O signals and the name of each signal are listed in Table 3.4.
An RX device indicates an input signal from the AJ65BT-64DAV/DAI to the master module, and a RY
device indicates an output signal from the master module to the AJ65BT-64DAV/DAI.
Table 3.4 I/O signals
Signal direction:
AJ65BT-64DAV/DAI
→
Master
Signal direction:
Master
→
AJ65BT-64DAV/DAI
Device No.
Signal name
Device No.
Signal name
RXn0 RYn0
CH.1 Analog output
enable/disable flag
RYn1
CH.2 Analog output
enable/disable flag
RYn2
CH.3 Analog output
enable/disable flag
RYn3
CH.4 Analog output
enable/disable flag
to
RYn4
Offset/gain value selection
RXnF
Unusable
RYn5
to
RYnF
Unusable
RX (n+1) 0
to
RX (n+1) 7
Unusable
RY (n+1) 0
to
RY (n+1) 7
Unusable
RX (n+1) 8
Initial data processing request
flag
RY (n+1) 8
Initial data processing complete
flag
RX (n+1) 9
Initial data setting complete flag
RY (n+1) 9
Initial data setting request flag
RX (n+1) A
Error status flag
RY (n+1) A
Error reset request flag
RX (n+1) B
Remote READY
RX (n+1) C
to
RX (n+3) F
Unusable
RY (n+1) B
to
RY (n+3) F
Unusable
n: The address allocated to the master station in the station number setting
*1 Although the number of occupied stations for the AJ65BT-64DAV/DAI is
2, inputs, RX(n+2) 0 to RX(n+3)F, are not used.
However, devices for inputs, RX(n+2) 0 to RX(n+3)F, and outputs,
RY(n+2) 0 to RY(n+3) F, are reserved in the master module or CPU
module. When creating a program, pay attention to device allocation.
Point
If a device not allowed to use is turned on/off from the sequence program, the function of the
AJ65BT-64DAV/DAI is not guaranteed.
Downloaded from
Содержание AJ65BT64DAV/DAI
Страница 2: ...Downloaded from ManualsNet com search engine ...
Страница 11: ...A 9 MEMO Downloaded from ManualsNet com search engine ...
Страница 13: ...1 OVERVIEW MELSEC A 1 2 MEMO 1 Downloaded from ManualsNet com search engine ...
Страница 15: ...2 SYSTEM CONFIGURATION MELSEC A 2 2 MEMO 2 Downloaded from ManualsNet com search engine ...
Страница 43: ...5 PROGRAMMING MELSEC A 5 6 3 Program example Downloaded from ManualsNet com search engine ...
Страница 61: ...Downloaded from ManualsNet com search engine ...