2. Installing the indoor unit

1

2

3

4

6

2.1. Check the indoor unit accessories (Fig. 2-1)

The indoor unit should be supplied with the following spare parts and accessories
(contained in the inside of the intake grille).

Accessory name

Q’ty

1

Washer

4 pcs

2

Washer (with insulation)

4 pcs

3

Pipe cover

2 pcs

4

Band

4 pcs (Long)   2 pc (Short)

5

Screw

4 pcs  M5 

×

 0.8 

×

 30   2 pcs  M4 

×

 12

6

Glass tube

1pc

7

Plate for conduit

1pc

Fig. 2-1

5

7

2.2. Service space (Fig. 2-2)

• The dimensions of ceiling opening can be regulated within the range shown in

following diagram; so center the main unit against the opening of ceiling, ensuring
that the respective opposite sides on all sides of the clearance between them be-
comes identical.

A

Air intake

B

Air outlet

C

Ceiling panel

D

Min. 7-7/8 in. (200 mm)

E

Suspension bolts W3/8 or M10

F

Grille

2.3. Ceiling openings and suspension bolt installation

locations (Fig. 2-3)

• Make an opening in the ceiling 17 in 

×

 37-7/8 in (430 mm 

×

 960 mm) in size. This

functions as a check window and will be needed later during servicing.

• If the dimensions are not accurate, when the grille is installed there may be gaps

between it and the indoor unit. This may result in dripping water or other problems.

• When deciding on placement, consider carefully the space around the ceiling and

make your measurements generous.

• Ceiling types and building construction differ. Therefore you should consult with the

builder and decorator.

A

The centers of the ceiling opening and the indoor unit should be aligned.

1

Outer side of grille

2

Ceiling opening

3

Bolt pitch

4

Electric box

• Using the installation template (top of the package) and the gauge (supplied as an

accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge are shown.)

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the field.

• After suspending the indoor unit, you will have to connect the pipes and wiring

above the ceiling. Once the location has been fixed and the direction of the pipes
has been determined, place the refrigerant and drainage pipes, the wiring for the
remote controller, and the wiring that connects the indoor and outdoor units in their
desired locations before suspending the indoor unit. This is especially important in
cases where the ceiling is already in existence.

C

A

D

A

B

4-5/16

(110)

9-1/16(230)

E

F

9-1/16(230)

Fig. 2-2

Fig. 2-3

in (mm)

in (mm)

Содержание Air-Conditioners For Building Application

Страница 1: ...NSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners For Building Application INDOOR UNIT PMFY P NBMU E ...

Страница 2: ... install the indoor unit where such dripping can cause damage When installing the unit in a hospital or communications office be prepared for noise and electronic interference Inverters home appliances high fre quency medical equipment and radio communications equipment can cause the air conditioner to malfunction or breakdown The air conditioner may also affect medical equipment disturbing medica...

Страница 3: ...heck window and will be needed later during servicing If the dimensions are not accurate when the grille is installed there may be gaps between it and the indoor unit This may result in dripping water or other problems When deciding on placement consider carefully the space around the ceiling and make your measurements generous Ceiling types and building construction differ Therefore you should co...

Страница 4: ...D Secure front panel here E Make these surfaces are flush with each other 0 1 8 in 0 3 mm Fig 2 7 K L M J H I in mm in mm Fig 2 4 Fig 2 5 D Ceiling panel E Rafter F Beam G Roof beam H Use inserts rated at 250 350 lbs 100 150 kg each procure locally I Suspension bolts 3 8 M10 procure locally J Steel reinforcing rod K C channel L Channel suspension bracket M M10 suspension bolt 2 4 Unit suspension p...

Страница 5: ...not contain any harmful contaminants such as sulfuric com pounds oxidants debris or dust Warning When installing or moving the air conditioner use only the specified refriger ant R410A to charge the refrigerant lines Do not mix it with any other refriger ant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards P06 P...

Страница 6: ... at the transparent check window and the outlet of the drainage pipe 4 Stop the test run Don t forget to turn off the power Fig 4 3 Fig 4 1 Fig 4 2 A Ceiling panel B Max 23 5 8 in 60 cm C Position of drain outlet D Make as short as possible Max 6 in 15 cm E Make as small as possible F Downward slope 1 100 or more G Make as great as possible Min 4 in 10 cm H Drainage pipe vertical section I Water b...

Страница 7: ... the M1 and M2 on indoor unit TB5 to a M NET remote controller Non polarized 2 wire DC 24 to 30 V between M1 and M2 M NET remote controller A Terminal block for indoor transmission cable B Terminal block for outdoor transmission cable C Remote controller Constraints on transmission cable Fig 5 3 Longest wiring length L1 L2 L4 or L1 L3 or L2 L3 L4 less than 656 ft 200 m Length between indoor unit a...

Страница 8: ...tion pitch 5 6 Remote controller For wired remote controller 1 Installing procedures Fig 5 5 1 Select an installing position for the remote controller The temperature sensors are located on both remote controller and indoor unit s Procure the following parts locally Two piece switch box Thin copper conduit tube Lock nuts and bushings 2 Seal the service entrance for the remote controller cord with ...

Страница 9: ...eed button Make sure that the wind speed is switched 6 Check operation of the outdoor unit fan 7 Release test run by pressing the ON OFF button Stop 8 Register a telephone number The telephone number of the repair shop sales office etc to contact if an error occurs can be registered in the remote controller The telephone number will be displayed when an error occurs For registration procedures ref...

Страница 10: ... press the intake grille on the place marked Push until you hear it snap into place 7 4 Checks after installing Check that there are no gaps between the indoor unit and the front panel and between the front panel and the ceiling surface If there are gaps the wind may come in and condensation may result Check that the air filter is in place 7 3 Installing the grille Open the intake grille by pressi...

Страница 11: ......

Страница 12: ...his manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U635H01 ...

Отзывы: