* Main and sub system controllers (M-NET)

AG-150A is for exclusive use as a main SC. AG-150A cannot be used as a sub SC.

• Main system controller (Main SC)

Main SC refers to a controller that controls all other system controllers including the units they control. If a given system has 
only one system controller, that controller becomes the main controller. Group settings and interlock settings can only be made 
from a main controller.

• Sub system controller (Sub SC)

Sub controller refers to a system controller that is controlled (including the units it controls) by a main system controller.

NOTES

* Up to three PAC-YG50ECA controllers can be connected to each AG-150A unit.
* Main system controllers (e.g., AG-150A) cannot be connected to an M-NET system that is controlled by an Expansion controller.

NOTES

The following types of configurations are not possible.
• A sub controller can only control the groups that are under the control of its main controller.

• No groups can be placed under the control of more than one main system controller.

• No sub system controllers can be placed under the control of more than one main system controller.

AG-150A, PAC-YG50ECA etc.

Range of units the main SC 

controls (M-NET)

Group

Group

Group

AG-150A is for exclusive use as a main SC. AG-150A cannot be used as a sub 
SC or controlled from another main SC.

Range of units the 

sub SC controls

Group

Group

Group

Main system 
controller

Sub system 
controller

Group

Group

Group

Main system 
controller 1

Main system 
controller 2

Group

Group

Group

Group

Main system 
controller 1

Sub system 
controller

Main system 
controller 2

WT05368X08.fm  Page 9  Thursday, March 17, 2011  9:21 AM

Содержание AG-150A

Страница 1: ...m with connection to a PAC YG50ECA Expansion controller 22 8 Initial Setting 23 9 Test Run 24 10 System Configuration Example 25 1 System with connection to a PAC YG50ECA Expansion controller 25 2 Using multiple system controllers 25 3 To control a Mr Slim 25 4 To control a K control model 25 11 External input output usage 26 1 External signal input function 26 2 External signal output function 27...

Страница 2: ...ts Do not install this controller in a place that has the potential for steam or dew formation Steam or dew formation may cause an electric shock or a unit malfunction Do not install this controller where an acid or alkaline solution or special chemical spray is used frequently to avoid electric shock or malfunction When installing the controller in a hospital or communication facility take approp...

Страница 3: ...version 2 10 or later Hereinafter Centralized controller AG 150A AG 150A A unless otherwise specified will be called AG 150A 2 Parts List No Description Usage Qty 1 AG 150A or AG 150A A Centralized controller 1 2 A type Installation plate Use to attach the AG 150A or AG 150A A using the B type installation plate or the Electric box PAC YG83UTB sold separately on the wall or in the control board 1 ...

Страница 4: ...72 10 3 4 146 5 3 4 167 6 5 8 Back View 290 8 11 1 2 273 10 3 4 250 9 7 8 200 7 7 8 147 5 13 16 ø6 1 4 ø4 3 16 163 4 6 7 16 167 6 5 8 175 8 6 15 16 300 11 13 16 278 10 15 16 250 9 7 8 200 7 7 8 6 1 4 4 3 16 152 6 163 4 6 7 16 167 6 5 8 185 7 5 16 A type installation plate B type installation plate Unit mm in ...

Страница 5: ...can be controlled 1 Specification 2 Parts names and functions 4 Product Features Item Specifications Power supply M NET Terminal 17VDC 32VDC Power supply PAC SC51KUA Controller drive 24VDC Temperature Operating 0 40 C 32 104 F For indoor installation only To be used in an business office or similar environment Non operating 20 60 C 4 140 F Humidity 30 90 RH No condensation Weight 2 1kg 4 6 lbs Dim...

Страница 6: ... attachment A type PAC YG85KTB sold separately is used to attach the controller V V FG Connects to power supply unit PAC SC51KUA that supplies 24 VDC power V 24VDC terminal V 0V terminal FG Functional earthing terminal ground CN1 Connects to the M NET cable when the mounting attachment A type PAC YG85KTB sold separately is used to attach the controller Do not use this terminal when a PAC YG50ECA E...

Страница 7: ...units depends on the number of channels used 1 50 Pl controller PAC YG60MCA Assign an arbitrary but unused address to the PI controller after assigning an address to all units to be assigned an address between 1 and 50 1 50 Al controller PAC YG63MCA Assign an arbitrary but unused address to the AI controller after assigning an address to all units to be assigned an address between 1 and 50 1 50 MA...

Страница 8: ...at exceeds the 10 m limit should be included in the maximum total line length of 500 m and in the power supply distance of 200 m NOTES Apply following precautions when using the K transmission converter model PAC SC25KAA discontinued and controlling the M NET model and K control model with the same controller Refer to the K transmission converter PAC SC25KAA installation manual for details 1 Centr...

Страница 9: ...ne in each outdoor unit refrigerant system Set the centralized control switch SW2 1 on the outdoor units on the M NET line to ON Refer to the outdoor unit Installation Manual for the details of the dipswitch settings TB7 TB3 ME R2 TB7 TB3 ME ME 000 051 TB7 TB3 ME ME TB7 TB3 ME ME 001 101 103 101 103 101 103 106 002 006 007 008 009 010 003 004 005 001 002 003 004 005 001 002 003 004 005 056 057 051...

Страница 10: ...g AG 150A cannot be connected to an M NET system that is controlled by an Expansion controller NOTES The following types of configurations are not possible A sub controller can only control the groups that are under the control of its main controller No groups can be placed under the control of more than one main system controller No sub system controllers can be placed under the control of more t...

Страница 11: ... supply unit PAC SC51KUA turned off Do not put the signal wire and power wire in the same conduit When routing the cable from the top of the controller let the cable hang down below the connector before connecting it to the terminal block or connector as shown in the figure below to prevent water from running down the cable and causing electric shock or fire 1 By embedding the centralized controll...

Страница 12: ...d NOTES When installing two or more controllers side by side and horizontally ensure that there is at least 130 mm 5 1 8 in or more between the units When installing two or more controllers vertically ensure that there is at least 150 mm 5 15 16 in between units otherwise it will be hard to remove the cover The amount of space required on the left of the controller is the amount necessary to conne...

Страница 13: ... NET transmission cable Type of the cable Shielded cable which comply with the following specifications or equivalent CPEVS φ1 2mm to φ1 6mm CVVS 1 25mm to 2mm AWG16 to 14 CPEVS PE insulated PVC jacketed shielded communication cable CVVS PVC insulated PVC jacketed shielded control cable PE Polyethylene PVC Polyvinyl chloride DC power cable The DC power cable should comply with both local standards...

Страница 14: ... and horizontally ensure that there is at least 130 mm 5 1 8 in or more between the units When installing two or more controllers vertically ensure that there is at least 150 mm 5 15 16 in between units otherwise it will be hard to remove the cover The amount of space required on the left of the controller is the amount necessary to connect disconnect the USB drive If the specified amount of space...

Страница 15: ...ion cable terminal A B both non polarity and S Connect the DC power cable from the power supply unit PAC SC51KUA to the 24VDC power supply terminal block of the controller There is V and V polarity CAUTION Do not connect the AC power cable to the M NET and POWER 24VDC terminal blocks of the controller It may cause a failure When leading the cable out from above seal the port so that water does not...

Страница 16: ...e hard to remove the cover The amount of space required on the left of the controller is the amount necessary to connect disconnect the USB drive If the specified amount of space is not available use a USB extension cable The amount of space required under the controller is the amount necessary for the mounting dismounting of the controller cover Back of controller M NET transmission cable DC powe...

Страница 17: ...er cable from the power supply unit PAC SC51KUA to the 24VDC power supply terminal block of the controller There is V and V polarity 8 Securely seal the cable lead in port with putty to prevent dew water and insect etc from entering 9 Install the controller on the mounting attachment B type PAC YG81TB with the four M4 rounded screws supplied with the PAC YG81TB 0 Replace the AG 150A surface cover ...

Страница 18: ...tallation Manual for details 8 Securely seal the cable lead in port with putty to prevent dew water and insect etc from entering 9 Remove the AG 150A surface cover NOTES When installing two or more controllers side by side and horizontally ensure that there is at least 130 mm 5 1 8 in or more between the units When installing two or more controllers vertically ensure that there is at least 250 mm ...

Страница 19: ... cover c Attach the power supply unit cover with the two screws Supplied with PAC YG85KTB M NET transmission cable supplied with PAC YG85KTB DC power cable supplied with PAC YG85KTB NOTE When using an LAN and external signal I O refer to section 11 External input output usage DC power cable supplied with PAC YG85KTB M NET transmission cable supplied with PAC YG85KTB M4 roundhead screw supplied wit...

Страница 20: ...nd insects etc from entering Seal the space between the control board and conduit with putty NOTES When installing two or more controllers side by side and horizontally ensure that there is at least 130 mm 5 1 8 in or more between the units When installing two or more controllers vertically ensure that there is at least 150 mm 5 15 16 in between units otherwise it will be hard to remove the cover ...

Страница 21: ...f the above is not feasible Refer to section 2 14 8 Remove the AG 150A surface cover 9 Install the AG 150A on the A type installation plate with the M4 roundhead screws supplied 0 Replace the AG 150A surface cover a Connect the power supply unit and centralized controller NOTE When using an LAN and external signal I O refer to section 11 External input output usage Unit mm in Control board A type ...

Страница 22: ... CN1 CN2 24VDC M NET A B S V V FG M NET Output CN1 CN2 TB2 TB3 24VDC Power supply unit PAC SC51KUA Cable clamp Centralized controller AG 150A Front view M NET transmission line Centralized control line Function earthing ground line Use a ring terminal to connect to the terminal block DC power supply line Polarized M NET transmission A B line Non polarity Shield Centralized controller Back view DC ...

Страница 23: ...ntirely over the LAN Connect the LAN from the AG 150A to the PAC YG50ECA via a switching HUB FG V V A B S CN1 CN2 24VDC M NET A B S V V FG M NET Output CN1 CN2 TB2 TB3 24VDC Centralized controller AG 150A Front view Switching HUB PAC YG50ECA Outdoor unit LAN Cable clamp DC power supply line 24VDC Polarized Power supply unit PAC SC51KUA Centralized controller Back view Power supply unit DC power su...

Страница 24: ...ssary 2 Clock setting 1 Touch Date and time on the Initial Settings window 2 Change other settings as necessary by touching the desired items and touch Save Settings to save the changes 3 Unit information settings 1 1 Touch Unit Info on the Initial Settings window 2 Set the Expansion Controller setting to Do not use 2 Set the Expansion Controller setting to Use 3 3 Change other settings as necessa...

Страница 25: ... settings screen After the setting is completed the Test run button will appear on the Operation screen 3 Select the group to be tested on the Monitor Operation screen and run the test 4 Check for proper operation of each air conditioning unit during test run e g check to see if cold or warm air comes out of the supply air outlet on each indoor unit 5 After confirming that all units are operating ...

Страница 26: ...92 168 1 212 000 Expansion controller PAC YG50ECA 192 168 1 213 000 M NET M NET M NET ON OFF remote controller etc 201 M NET adapter K transmission converter Model name PAC SC25KAA Indoor units 50 units Indoor unit 20 units Indoor unit address 01 20 Group 1 Group 20 Mr Slim outdoor unit M NET adapter M NET adapter 2 units M NET adapter address 21 22 Group 21 22 Indoor unit M NET 20 units Indoor un...

Страница 27: ...lter reset from the local remote controller will be prohibited 3 Set the pulse width contact ON time to 0 5 to 1 sec 11 External input output usage NOTES When using a PAC YG50ECA Expansion controller connect the external input output adapter to the external input terminal on the Expansion controller not to the AG 150A Make necessary settings for each Expansion controller from the AG 150A on the Ne...

Страница 28: ...eration status of DIDO controller is not output Operation signal is output during an error No 2 Black ON OFF No 3 Brown Malfunction normal CN5 Red Orange Max 10m 32 ft X1 X1 Run stop or Emergency stop Power supply 12VDC or 24VDC This unit 9 8 7 6 5 1 Use relays X1 X2 Y1 and Y2 that meet the following specifications Contact rating Rated voltage 12VDC Rated current 0 1A Minimum applicable load 1mA a...

Страница 29: ...ht cable Category 5 or later For a description of the IP address setting method refer to section 8 Initial Setting LAN is 100 BASE TX specification NOTE When connecting the external input output cables to connector CN5 on the controller punch out the knockout hole 12 LAN connection function CAUTION Perform the LAN wiring before controller installation and wire up to the body by the same method as ...

Страница 30: ... This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide resonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harm...

Страница 31: ......

Страница 32: ...tions Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K ...

Страница 33: ...ingsmills Hotel Scotland AG150 Instruction Book Web User WT05492X13 AG150 Instruction Book Web Maintenance WT05490X14 AG150 Instruction Book Web Initial WT05491X14 AG150 Instruction Book WT05369X15 AG150 Installation Manual WT05368X08 AG150 Declaration of Conformity EUT10014A ...

Страница 34: ......

Отзывы: