Connection of stand-alone option units
66
2.10.2
Connection of the DC reactor
• When using the DC reactor, connect it across terminals P/+ and P1.
For the FR-A860-01080 or lower, the jumper connected across terminals P/+ and P1 must be removed. Otherwise, the
reactor will not be effective.
• Select a DC reactor according to the applied motor capacity. (Refer to
• For the FR-A860-01440 or higher, and when a 75 kW or higher motor is used, always connect a DC reactor.
• Select a DC reactor according to the following table.
The power supply frequency of 60 Hz is assumed.
Class H or higher insulation is recommended.
Select a DC reactor for which its L value does not fall to 50% or below when the inverter overload current rating is 150% (ND rating).
NOTE
• The wiring distance must be within 5 m.
• As a reference, the cable gauge for the connection must be equal to or larger than that of the power supply cables (R/L1, S/
L2, T/L3) and the earthing (grounding) cable. (Refer to
.)
Motor capacity (kW)
Reactor specifications
,
Reactor L value
(mH)
DC reactor
rated current (A)
75
0.616
124
90
0.517
149
110
0.426
182
132
0.351
219
160
0.294
265
185
0.254
307
220
0.214
365
250
0.188
414
280
0.169
464
315
0.150
522
P1
DC reactor
Remove
the jumper
P/+