(C) Motor constant parameters
424
Setting the applied motor
• Refer to the following list and set the parameters according to the applied motor.
For the FR-A860-01080 or lower.
For the FR-A860-01440 or higher.
The same operation is performed for the both settings.
NOTE
• Regardless of the
Pr.71 (Pr.450)
setting, offline auto tuning can be performed according to
Pr.96 (Pr.463) Auto tuning
setting/status
. (Refer to
for offlne auto tuning.)
Pr.71 Pr.450
Motor
Constant value range when
performing offline auto tuning
(increment)
Operational
characteristic of the
electronic thermal O/L
relay
Standard
Constant-
torque
0
(
Pr.71
initial
value)
Standard motor
Pr.82 (Pr.455) and Pr.859 (Pr.860)
• 0 to 500 A, 9999 (0.01 A)
• 0 to 3600 A, 9999 (0.1 A)
Pr.90 (Pr.458) and Pr.91 (Pr.459)
• 0 to 50
Ω
, 9999 (0.001
Ω
• 0 to 400 m
Ω
, 9999 (0.01 m
Ω
Pr.92 (Pr.460) and Pr.93 (Pr.461)
(Induction motor)
• 0 to 6000 mH, 9999 (0.1 mH)
• 0 to 400 mH, 9999 (0.01 mH)
Pr.92 (Pr.460) and Pr.93 (Pr.461)
(PM motor)
• 0 to 500 mH, 9999 (0.01 mH)
• 0 to 50 mH, 9999 (0.001 mH)
Pr.94 (Pr.462)
• 0 to 100%, 9999(0.1%)
• 0 to 100%, 9999(0.01%)
Pr.706 (Pr.738)
• 0 to 5000 mV/(rad/s), 9999 (0.1 mV/(rad/s))
1
Constant-torque motor
2
―
Standard motor
Adjustable 5 points V/F (Refer to
.)
30
Vector control dedicated motor
8090
IPM motor
9090
SPM motor
Standard motor
Pr.82 (Pr.455), Pr.859 (Pr.860),
Pr.90 (Pr.458), Pr.91 (Pr.459),
Pr.92 (Pr.460), Pr.93 (Pr.461),
Pr.94 (Pr.462) and Pr.706 (Pr.738)
• Internal data value 0 to 65534, 9999 (1)
The display increment can be changed in
Pr.684
.
13 (14)
Constant-torque motor
33 (34)
Vector control dedicated motor
8093 (8094)
IPM motor
9093 (9094)
SPM motor
5
Standard motor
Star
connection
Pr.82 (Pr.455) and
Pr.859 (Pr.860)
• 0 to 500 A, 9999 (0.01 A)
• 0 to 3600 A, 9999 (0.1 A)
Pr.90 (Pr.458) and
Pr.91 (Pr.459)
• 0 to 50
Ω
, 9999 (0.001
Ω
• 0 to 400 m
Ω
, 9999 (0.01 m
Ω
Pr.92 (Pr.460) and
Pr.93 (Pr.461)
• 0 to 50
Ω
, 9999 (0.001
Ω
• 0 to 3600 m
Ω
, 9999 (0.1 m
Ω
Pr.94 (Pr.462)
• 0 to 500
Ω
, 9999 (0.01
Ω
• 0 to 100
Ω
, 9999 (0.01
Ω
15
Constant-torque motor
6
Standard motor
Delta
connection
16
Constant-torque motor
―
9999
(initial
value)
No second applied motor