(M) Monitor display and monitor output signal
348
Monitor description list (Pr.52, Pr.774 to Pr.776)
• Set the monitor to be displayed on the operation panel and the parameter unit in
Pr.52, Pr.774 to Pr.776
.
• Refer to the following table to find the setting value for each monitoring. The value in the Pr. setting column is set in each of
the parameters for monitoring (
Pr.52, Pr.774 to Pr.776
) to determine the monitor item. The value in the RS-485 column is
used for the RS-485 communication special monitor selection. The value in the MODBUS RTU column is used for the
MODBUS RTU real time monitor. (The items marked with “—" cannot be selected. The circle in the negative indication (-)
column indicates that the indication of negative signed numbers is available.)
Monitor item
Increment
and unit
Pr. setting
RS-485
MODBUS
RTU
Negative
indication
(-)
Description
Output frequency/
speed
0.01 Hz/1
1/0/100
H01
40201
Displays the inverter output
frequency.
Output current
0.01 A/
0.1 A
2/0/100
H02
40202
Displays the inverter output current
effective value.
Output voltage
0.1 V
3/0/100
H03
40203
Displays the inverter output voltage.
Fault display
—
0/100
—
—
Displays 8 past faults individually.
Frequency setting
value/speed setting
0.01 Hz/1
5
H05
40205
Displays the set frequency
Running speed
1 (r/min)
6
H06
40206
Displays the motor speed (by the
Pr.37, Pr.144
settings). (Refer to
The actual motor speed by encoder
signal is used during encoder
feedback control and vector control.
Motor torque
0.1%
7
H07
40207
Displays motor torque as a
percentage (0% under V/F control),
considering the rated torque as
100%.
Converter output
voltage
0.1 V
8
H08
40208
Displays the DC bus voltage value.
Regenerative brake
duty
0.1%
9
H09
40209
Brake duty set in
Pr.30
and
Pr.70
Electronic thermal
O/L relay load
factor
0.1%
H0A
40210
Displays the motor thermal
cumulative value, considering the
thermal operation level as 100%.
Output current peak
value
0.01 A/
0.1 A
H0B
40211
Saves and displays the output current
monitor peak value.
(Cleared with each start.)
Converter output
voltage peak value
0.1 V
H0C
40212
Saves and displays the DC bus
voltage peak value.
(Cleared with each start.)
Input power
0.01 kW/0.1
kW
H0D
40213
Displays the power at the inverter
input side.
Output power
0.01 kW/0.1
kW
H0E
40214
Displays the power at the inverter
output side.
Load meter
0.1%
17
H11
40217
Displays torque current as a
percentage, considering
Pr.56
setting
value as 100% (motor rated torque is
considered as 100% during
Sensorless vector and vector
control).
Motor excitation
current
0.01 A/
0.1 A
18
H12
40218
Displays the motor excitation current
Position pulse
—
19
H13
40219
Displays the number of pulses per
motor rotation during orientation
control and position control. (Displays
the voltage monitor when a vector
control compatible option is not
connected.)
Cumulative
energization time
1 h
20
H14
40220
Displays the cumulative energization
time since the inverter shipment.
Check how many times the monitor
value exceeded 65535 h with
Pr.563
.