(M) Monitor display and monitor output signal
352
Indication with a minus sign is not possible via RS-485 or MODBUS RTU communication.
When using the item as the main monitor data on the LCD operation panel (FR-LU08) or the parameter unit (FR-PU07), use
Pr.774 to Pr.776
or
the monitor function of the FR-LU08 or the FR-PU07 for setting.
The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from
0.
The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.
When using the parameter unit (FR-PU07), "kW" is displayed.
Differs according to capacities. (FR-A860-01080 or lower / FR-A860-01440 or higher)
The setting is available only for standard models.
When the output current is less than the specified current level (5% of the inverter rated current), the output current is monitored as 0 A.
Therefore, the monitored value of an output current and output power may be displayed as "0" when using a much smaller-capacity motor
compared to the inverter or in other instances that cause the output current to fall below the specified value.
Can be changed to the pulse display after the electronic gear using
Pr.430 Pulse monitor selection
. (Refer to
.)
Available when the plug-in option or control terminal option is connected.
Input terminal monitor details ("1" denotes terminal ON, "0" denotes terminal OFF, and "
―
" denotes undetermined value.)
Output terminal monitor details ("1" denotes terminal ON, "0" denotes terminal OFF, and "
―
" denotes undetermined value.)
Option input terminal monitor 1 details (FR-A8AX input terminal status, "1" denotes terminal ON and "0" denotes terminal OFF.)
――
All are OFF
when the option is not connected.
Option input terminal monitor 2 details (FR-A8AX input terminal status. "1" denotes terminal ON, "0" denotes terminal OFF, "
―
" denotes
undetermined value.)
――
All are OFF when the option is not connected.
Option output terminal monitor details (FR-A8AY/A8AR output terminal status. "1" denotes terminal ON, "0" denotes terminal OFF, and "
―
" denotes
undetermined value.)
――
All are OFF when the option is not connected.
The increment is 1 when
Pr.37
= "1 to 9998" or when
Pr.144
= "2 to 12, or 102 to 112". (Refer to
.)
The monitored values are retained even if an inverter fault occurs. Resetting will clear the retained values.
Parameter setting is not available for setting the item as the main monitor data on the LCD operation panel (FR-LU08) or the parameter unit (FR-
PU07). Use the monitor function of the FR-LU08 or the FR-PU07 for setting.
Negative values are not displayed on the operation panel. The values "-1 to -32767" are displayed as "65535 to 32769" on the operation panel.
Setting of
Pr.1018 Monitor with sign selection
is required. Also, it will be displayed without a minus sign on the operation panel. Confirm the
rotation direction with the [FWD] or [REV] indicator.
Second PID set
point
0.1%
92
H5C
40292
Displays the set point, measured
value, and deviation under second
PID control. (Refer to
Second PID
measured value
0.1%
93
H5D
40293
Second PID
deviation
0.1%
94
H5E
40294
Second PID
measured value 2
0.1%
95
H5F
40295
Displays PID measured value even if
PID control operating conditions are
not satisfied while the second PID
control is enabled (
Pr.753
≠
"0").
(Refer to
Second PID
manipulated
variable
0.1%
96
H60
40296
Displays the second PID control
manipulated amount.
(Refer to
Dancer main speed
setting
0.01 Hz
97
H61
40297
Displays the main speed setting
under step control
Control circuit
temperature
1°C
98
H62
40298
Displays the temperature of the
control circuit board.
(Refer to
Without minus sign: 0 to 100°C
With minus sign: -20 to 100°C
b15
b0
―
―
―
―
CS
RES
STP
(STOP)
MRS
JOG
RH
RM
RL
RT
AU
STR
STF
b15
b0
―
―
―
―
―
―
―
―
―
ABC2
ABC1
FU
OL
IPF
SU
RUN
b15
b0
X15
X14
X13
X12
X11
X10
X9
X8
X7
X6
X5
X4
X3
X2
X1
X0
b15
b0
―
―
―
―
―
―
―
―
―
―
―
―
―
―
―
DY
b15
b0
―
―
―
―
―
―
RA3
RA2
RA1
Y6
Y5
Y4
Y3
Y2
Y1
Y0
Monitor item
Increment
and unit
Pr. setting
RS-485
MODBUS
RTU
Negative
indication
(-)
Description