(H) Protective function parameter
334
Disabling the stall prevention operation and fast-response current limit
according to operating conditions (Pr.156)
• Referring to the table below, enable/disable the stall prevention operation and the fast-response current limit operation, and
also set the operation at OL signal output.
When "operation stop at OL signal output" is selected, the inverter stops its operation at the OL signal output (stall prevention stop).
The OL signal and E.OLT are not outputted because fast-response current limit and stall prevention are not operating.
Setting values "100, 101" can be individually set for power driving and regenerative driving. The setting value "101" disables the fast-response
current limit during power driving.
NOTE
• When the load is heavy or the acceleration/deceleration time is short, stall prevention operates and acceleration/deceleration
may not be performed according to the time set. In such case, set the
Pr.156
and the stall prevention operation level to the
optimum values.
• For lift applications, make settings to disable the fast-response current limit. Otherwise, the torque may be insufficient,
causing the load to drop.
Pr.156
setting
Fast
response
current limit
: enabled
: disabled
Stall prevention
operation selection
: enabled
: disabled
OL signal
output
:
operation
continued
:
operation
stopped
Pr.156
setting
Fast
response
current limit
: enabled
: disabled
Stall prevention
operation selection
: enabled
: disabled
OL signal
output
:
operation
continued
:
operation
stopped
Ac
celer
atio
n
Co
ns
ta
nt sp
eed
De
celer
atio
n
Ac
celer
atio
n
Co
ns
ta
nt sp
eed
De
celer
atio
n
0
(initial value)
16
1
17
2
18
3
19
4
20
5
21
6
22
7
23
8
24
9
25
10
26
11
27
12
28
13
29
14
30
15
―
31
100
P
ow
er dr
iv
ing
101
P
ow
er dr
iv
ing
Re
generative driving
―
Re
generative driving