Torque control under Real sensorless vector control and vector control
187
5
5.4.2
Setting procedure of Real sensorless vector
control (torque control)
Sensorless
Sensorless
Sensorless
Test run
Perform secure wiring.
(Refer to
.)
Make the motor setting.
(Pr.71)
Set the torque command.
(Pr.804)
Set the speed limit.
(Pr.807)
.)
Perform offline auto tuning.
(Pr.96)
(Refer to
.)
Select the control method.
(Pr.800)
(Refer to
)
As required
• Select online auto tuning.
(Pr.95)
(Refer to
.)
• Adjusting the torque control gain manually (Refer to
)
Enable torque control by setting
Pr.800 Control method selection
="11"
(torque control) or "12" (speed/torque switch) and torque control becomes valid.
Set the motor capacity and the number of motor poles.
(Pr.80, Pr.81)
Set "0 (standard motor)" or "1 (constant-torque motor)" in
Pr.71 Applied
motor
.
Set the motor capacity (kW) in
Pr.80 Motor capacity
, and set the
number of motor poles in
Pr.81 Number of motor poles
. (V/F control
is performed when the setting is "9999" (initial value).)
Set the motor overheat protection.
(Pr.9)
Set the rated motor current (A) in
Pr.9 Electronic thermal O/L relay
.
Set the rated motor voltage and frequency.
(Pr.83, Pr.84)
(Refer to
)
Set the rated motor voltage (V) in
Pr.83 Rated motor voltage
, and set the
rated motor frequency (Hz) in
Pr.84 Rated motor frequency