309
Useful functions
4
4.22.7 Setting multiple parameters as a batch (Pr.999)
....
Specifications differ according to the date assembled.
to check the SERIAL number.
(1) Automatic parameter setting
(Pr.999)
⋅
Select which parameters to be automatically set, and set that to
Pr. 999
. Multiple parameter settings are changed
automatically.
Refer to page 312
for the list of parameters that are changed automatically.
⋅
Parameter settings are changed as a batch. Those include parameter settings for the extended PID display, the
Mitsubishi human machine interface (GOT) connection, rated frequency settings of 50Hz/60Hz, and
acceleration/deceleration time increment settings.
⋅
Multiple parameters are changed automatically. Users do not have to consider each parameter number.
(Parameter setting mode)
Parameter
Number
Name
Initial value
Setting range
Description
999
Automatic parameter setting
9999
1
Normal PID setting
2
Extended PID setting
10
GOT initial setting (PU connector)
11
GOT initial setting (RS-485 terminals)
20
50Hz rated frequency
21
60Hz rated frequency
30
Acceleration/deceleration time
(0.1s increment)
31
Acceleration/deceleration time
(0.01s increment)
9999
No action
Pr.999 setting
Description
Operation in the parameter setting
mode
1
Automatically applies the normal PID display settings in parameters
"AUTO"
→
"PId"
→
Write "1"
2
Automatically applies the extended PID display settings in
parameters
"AUTO"
→
"PId"
→
Write "2"
10
Automatically sets the communication parameters for the GOT
connection with a PU connector
"AUTO"
→
"GOT"
→
Write "1"
11
Automatically sets the communication parameters for the GOT
connection with RS-485 terminals
—
20
50Hz rated
frequency
Sets the related parameters of the rated
frequency according to the power supply
frequency
"AUTO"
→
"F50"
→
Write "1"
21
60Hz rated
frequency
—
30
0.1s increment
Changes the setting increments of
acceleration/deceleration time parameters
without changing acceleration/deceleration
settings
—
31
0.01s increment
"AUTO"
→
"T0.01"
→
Write "1"
REMARKS
If the automatic setting is performed, the selected settings including the changed parameter settings will be changed.