89
V/F pattern
4
4.5 V/F pattern
4.5.1
Base frequency, voltage (Pr. 3, Pr. 19, Pr. 47)
* The parameters can be set when
Pr. 160 User group read selection
= "0"
(Refer to page 190)
(2) Set multiple base frequencies
(Pr. 47)
⋅
When you want to change the base frequency when switching two motors with one inverter, use the
Pr. 47
Second V/F
(base frequency)
.
⋅
Pr. 47
Second V/F (base frequency)
is valid when the RT signal is ON.
Purpose
Parameter that must be Set
Refer to Page
Set motor ratings
Base frequency, base
frequency voltage
Pr. 3, Pr. 19, Pr. 47
Select a V/F pattern according to
applications
Load pattern selection
Pr. 14
Use special motor
Adjustable 5 points V/F
Pr. 71, Pr. 100 to Pr. 109
Used to adjust the inverter outputs (voltage, frequency) to the motor rating.
Parameter
Number
Name
Initial Value
Setting Range
Description
3
Base frequency
60Hz
0 to 400Hz
Set the frequency when the motor
rated torque is generated. (50Hz/60Hz)
19
*
Base frequency voltage
9999
0 to 1000V
Set the base voltage.
8888
95% of power supply voltage
9999
Same as power supply voltage
47
*
Second V/F (base frequency)
9999
0 to 400Hz
Set the base frequency when the RT
signal is ON.
9999
Second V/F invalid
(1) Setting of base frequency
(Pr. 3)
⋅
When operating a standard motor, generally set the rated
frequency of the motor to
Pr. 3
Base frequency
. When running
the motor using bypass operation, set
Pr. 3
to the same value
as the power supply frequency.
⋅
If the frequency given on the motor rating plate is "50Hz" only,
always set to "50Hz". Leaving the base frequency unchanged
from "60Hz" may make the voltage too low and the torque
insufficient. It may result in an inverter trip due to overload.
Caution must be taken especially when
Pr. 14
Load pattern
selection
= "1" (variable torque load).
⋅
When using the Mitsubishi constant-torque motor, set
Pr. 3
to
60Hz.
REMARKS
⋅
The RT signal acts as the second function selection signal and makes the other second functions valid.
(Refer to page 125)
⋅
In the initial setting, the RT signal is assigned to the RT terminal. By setting "3" to any of
Pr. 178 to Pr. 189 (Input terminal function
selection)
, you can assign the RT signal to the other terminal.
Pr.19
Output voltage (V)
Output frequency
(Hz)
Pr.3
Pr.47
Содержание 700 Series
Страница 11: ...MEMO ...
Страница 23: ...12 MEMO ...
Страница 341: ...330 MEMO ...
Страница 365: ...354 MEMO ...
Страница 379: ...368 MEMO ...
Страница 397: ...386 MEMO ...
Страница 414: ...403 MEMO ...