WIRING
The line voltage drop can be calculated by the following expression:
Line voltage drop [V] =
Use a larger diameter cable when the wiring distance is long or when it is desired to decrease the voltage drop (torque
reduction) in the low speed range.
Applicable Inverter Type
Cable Sizes
HIV, etc. [mm
2
] *
1
AWG *
2
PVC, etc. [mm
2
] *
3
R/L1,
S/L2,
T/L3
U, V, W P/+, P1
Earth Cable
Gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth Cable
Gauge
FR-A 740-00023–00126-EC
2
2
2
2
14
14
2.5
2.5
2.5
FR-A 740-00170-EC
2
2
3.5
3.5
12
14
2.5
2.5
4
FR-A 740-00250-EC
3.5
3.5
3.5
3.5
12
12
4
4
4
FR-A 740-00310-EC
5.5
5.5
5.5
8
10
10
6
6
10
FR-A 740-00380-EC
8
8
8
8
8
8
10
10
10
FR-A 740-00470-EC
14
8
14
14
6
8
16
10
16
FR-A 740-00620-EC
14
14
22
14
6
6
16
16
16
FR-A 740-00770-EC
22
22
22
14
4
4
25
25
16
FR-A 740-00930-EC
22
22
22
14
4
4
25
25
16
FR-A 740-01160-EC
38
38
38
22
1
2
50
50
25
FR-A 740-01800-EC
60
60
60
22
1/0
1/0
50
50
25
FR-A 740-02160-EC
60
60
60
38
1/0
1/0
50
50
25
FR-A 740-02600-EC
60
60
80
38
3/0
3/0
50
50
25
FR-A 740-03250-EC
80
80
80
38
3/0
3/0
70
70
35
FR-A 740-03610-EC
100
100
100
38
4/0
4/0
95
95
50
FR-A 740-04320-EC
125
150
150
38
250
250
120
120
70
FR-A 740-04810-EC
150
150
150
38
300
300
150
150
95
FR-A 740-05470-EC
2 x 100
2 x 100 2 x 100
60
2 x 4/0
2 x 4/0
2 x 95
2 x 95
95
FR-A 740-06100-EC
2 x 100
2 x 100 2 x 125
60
2 x 4/0
2 x 4/0
2 x 95
2 x 95
95
FR-A 740-06830-EC
2 x 125
2 x 125 2 x 125
60
2 x 250
2 x 250
2 x 120
2 x 120
120
FR-A 740-07700-EC
2 x 150
2 x 150 2 x 150
100
2 x 300
2 x 300
2 x 150
2 x 150
150
FR-A 740-08660-EC
2 x 200
2 x 200 2 x 200
100
2 x 350
2 x 350
2 x 185
2 x 185
2 x 95
FR-A 740-09620-EC
2 x 200
2 x 200 2 x 200
100
2 x 400
2 x 400
2 x 185
2 x 185
2 x 95
FR-A 740-10940-EC
2 x 250
2 x 250 2 x 250
100
2 x 500
2 x 500
2 x 240
2 x 240
2 x 120
FR-A 740-12120-EC
3 x 200
2 x 250 3 x 200
2 x 100
2 x 500
2 x 500
2 x 240
2 x 240
2 x 120
*
1
For the 01800 or less, the recommended cable size is that of the HIV cable (600V class 2 vinyl-insulated cable) with continuous maximum
permissible temperature of 75°C. Assumes that the ambient temperature is 50°C or less and the wiring distance is 20m or less.
For the 02160 or more, the recommended cable size is that of LMFC (heat resistant flexible cross-linked polyethylene insulated cable) with
continuous maximum permissible temperature of 90°C. Assumes that the ambient temperature is 50°C or less and wiring is performed in an
enclosure.
*
2
For the 01160 or less, the recommended cable size is that of the THHW cable with continuous maximum permissible temperature of 75°C.
Assumes that the ambient temperature is 40°C or less and the wiring distance is 20m or less.
For the 01800 or more, the recommended cable size is that of THHN cable with continuous maximum permissible temperature of 90°C.
Assumes that the ambient temperature is 40°C or less and wiring is performed in an enclosure.
(Selection example for use mainly in the Unite States.)
*
3
For the 01160 or less, the recommended cable size is that of the PVC cable with continuous maximum permissible temperature of 70°C.
Assumes that the ambient temperature is 40°C or less and the wiring distance is 20m or less.
For the 01800 or more, the recommended cable size is that of XLPE cable with continuous maximum permissible temperature of 90°C.
Assumes that the ambient temperature is 40°C or less and wiring is performed in an enclosure. (Selection example for use mainly in Europe.)
*
4
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, and a screw for earthing.
For the types 03250 and 03610, screw sizes are different (R/L1, S/L2, T/L3, U, V, W, screw for earthing: M10 / P/+: M12).
For the types 04320 or more, screw sizes are different (R/L1, S/L2, T/L3, U, V, W / screw for earthing.
CAUTION
Tighten the terminal screw to the specified torque.
A screw that has been tighten too loosely can cause a short circuit or malfunction.
A screw that has been tighten too tightly can cause a short circuit or malfunction due to the unit breakage.
Use crimping terminals with insulation sleeve to wire the power supply and motor.
/
3
wire resistance [ m
Ω′
m
]
wiring distance [m]
current [A]
×
×
×
1000
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------