10. System control (Fig. 10-1)

9.3. Refrigerant collecting (pump down)

Perform the following procedures to collect the refrigerant when moving the indoor
unit or the outdoor unit.

1

Before collecting the refrigerant, first make sure that the all of the SW5 DIP switches
for function changes on the control board of the outdoor unit are set to OFF. If all of the
SW5 switches are not set to OFF, record the settings and then set all of the switches
to OFF. Start collecting the refrigerant. After moving the unit to a new location and
completing the test run, set the SW5 switches to the previously recorded settings.

2

Supply power (circuit breaker).

* When power is supplied, make sure that “CENTRALLY CONTROLLED” is not

displayed on the remote controller. If “CENTRALLY CONTROLLED” is dis-
played, the refrigerant collecting (pump down) cannot be completed normally.

3

After the liquid stop valve is closed, set the SWP switch on the control board of the
outdoor unit to ON. The compressor (outdoor unit) and ventilators (indoor and
outdoor units) start operating and refrigerant collecting operation begins. LED1
and LED2 on the control board of the outdoor unit are lit.

* Set the refrigerant address using the DIP switch of the outdoor unit.

1

Wiring from the Remote Control

This wire is connected to TB5 (terminal board for remote controller) of the indoor unit
(non-polar).

2

When a Different Refrigerant System Grouping is Used.

Up to 16 refrigerant systems can be controlled as one group using the slim MA re-
mote controller.

Note:
In single refrigerant system (twin/triple/quadruple), there is no need of wiring

2

.

A

Outdoor unit

B

Indoor unit

C

Master remote controller

D

Subordinate remote controller

E

Standard 1:1 (Refrigerant address = 00)

F

Simultaneous twin (Refrigerant address = 01)

G

Simultaneous triple (Refrigerant address = 02)

ON

OFF

3

4

5

6

E

 SW 1 - 3 ~ 6

ON

OFF

3

4

5

6

F

 SW 1 - 3 ~ 6

ON

OFF

3

4

5

6

G

 SW 1 - 3 ~ 6

Operation according to switch setting

ON

OFF

Start

Normal

Clear

Normal

Settings for outdoor unit ad-
dresses 0 to 15

SW1
Function table

<SW1>

Function

1 Compulsory de-

frosting

2 Error history clear
3
4
5
6

ON

1 2 3 4 5 6

OFF

TB4

TB5

TB1

TB4

TB5

TB4

TB1

TB4

TB1

TB4

TB4

TB5

1

1

2

2

A

A

B

B

B

B

B

B

C

D

A

F

G

E

SW1
function
settings

Fig. 10-1

Refrigerant sys-
tem address set-
ting

* Only set the SWP switch (push-button type) to ON if the unit is stopped. How-

ever, even if the unit is stopped and the SWP switch is set to ON less than
three minutes after the compressor stops, the refrigerant collecting operation
cannot be performed. Wait until compressor has been stopped for three min-
utes and then set the SWP switch to ON again.

4

Because the unit automatically stops in about two to three minutes after the refrig-
erant collecting operation (LED1 and LED2 are lit), be sure to quickly close the
gas stop valve. When LED1 and LED2 are lit and the outdoor unit is stopped, open
the liquid stop valve completely, and then repeat step 

3

 after three minutes have

passed.

* If the refrigerant collecting operation has been completed normally (LED1 and

LED2 are lit), the unit will remain stopped until the power supply is turned off.

5

Turn off the power supply (circuit breaker).

* Note that when the length of the extension piping is long, it may not be possi-

ble to perform a pump-down operation. When performing the pump-down op-
eration, make sure that the low pressure is lowered to near 0 MPa (gauge).

11. Information on rating plate

Model

Refrigerant (R410A)

kg

Allowable pressure (Ps)

Net weight

kg

RP200, 250

10.5

HP:3.6 MPa (36 bar), LP:2.3 MPa (23 bar)

198

MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION, SHIZUOKA WORKS

18-1, OSHIKA 3-CHOME, SURUGA-KU, SHIZUOKA CITY, JAPAN

9. Special Functions

Содержание 250 YHA-A

Страница 1: ...English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners PUHZ RP200 250 YHA A FOR INSTALLER ...

Страница 2: ... it with any other refrig erant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories are incorrectly in stalled water leakage electric shock or fire may result Do not alter the unit Cons...

Страница 3: ... in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Contact your nearest dealer for any questions Tools for R410A Gauge manifold Fl...

Страница 4: ...e overall height of the unit add the dimen sion shown as h in the drawing on the left to L1 and L2 on Table 2 Table 2 mm L1 L2 450 100 2 4 2 When installing multiple outdoor units Fig 2 8 When installing multiple units make sure to take into consideration factors such as providing enough space for people to pass through ample space between blocks of units and sufficient space for air flow as shown...

Страница 5: ...openings at the base of the unit Note 1 Always use care when transporting a unit by forklift on rainy days as slip page can occur 2 Never use dangerous sudden movements such as accelerating or applying the brakes suddenly or turning the steering wheel quickly when transporting the unit by forklift 3 2 Transporting by pallet truck Fig 3 2 When using a pallet truck to transport the unit insert the f...

Страница 6: ... stalled has sufficient strength If the surface is not strong enough the unit could fall over and cause damage or injury Make sure that the unit is installed so that it will be able to withstand earth quakes and strong winds Damage or injury could occur if the unit tips over due to an earthquake or strong wind Be sure to install the unit in a sturdy level surface to prevent rattling noises during ...

Страница 7: ...ne foam insu lation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut A Use two wrenches to tighten piping connections B Use leak detector or soapy water to check for gas leaks after connections are com pleted Apply refrigerating machine oil over the entire flare seat surface C Do not apply...

Страница 8: ...air from the refrigerant lines After the valve work is completed tighten the valve caps to the correct torque Valve size Tightening torque N m kgf cm Valve cap Service port cap 3 8 ø9 52 22 28 220 280 12 16 1 2 ø12 7 25 31 250 310 120 160 1 ø25 4 36 44 360 440 11 5 13 9 115 139 Failure to replace and tighten the caps may result in refrigerant leakage In addition do not damage the insides of the va...

Страница 9: ... less 41 50 m and less 51 60 m and less 61 70 m and less 71 120 m and less 0 9 kg 1 8 kg 2 7 kg 3 6 kg 1 2 kg 2 4 kg 3 6 kg 4 8 kg Outdoor unit RP200 RP250 At time of shipping kg 10 5 10 5 No additional charge necessary Calculate the amount of additional refrigerant charge using formula provided below Main piping Liquid line size ø9 52 overall length 0 09 Gasline ø28 58 m 0 09 kg m Branch piping L...

Страница 10: ...ner from the pipes The existing piping can be reused After flaring the pipes again connect the new air conditioner The existing pipes cannot be reused Use new pipes 5 Installing the refrigerant piping 5 8 For twin triple quadruple combination Fig 5 8 When this unit is used as a FREE COMPO MULTI unit install the refrigerant piping with the restrictions indicated in the drawing on the left In additi...

Страница 11: ...ting cords shall not be lighter than polychloroprene sheathed flexible cord Design 245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied The earth wire should also be thicker than the power supply cord so that it can stand any surge of electricity when trouble occurs 7 2 Field electrical wiring If the wiring connecting t...

Страница 12: ...ended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malfunction Perform the following procedures 1 Remove the wires from the compressor and measure the insulation resistance of the compressor 2 If the insulation resistance is below 1 MΩ the compressor is faulty or the resist ance dropped due the accumulation of refrigerant in...

Страница 13: ...W4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from the check valve due to the small differ...

Страница 14: ...ltaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 ON OFF 3 4 5 6 E SW 1 3 6 ON OFF 3 4 5 6 F SW 1 3 6 ON OFF 3 4 5 6 G SW 1 3 6 Operation according to switch setting ON OFF Start Normal Clear Normal Settings for outdoor unit ad dresses 0 to 15 SW1 Function table SW1 Function 1 Compulsory de frosting 2 Error history clear 3 4 5 6 ON 1 2 3 4 5 6 OFF TB4 TB5 TB1 TB4 TB...

Страница 15: ......

Страница 16: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U638H03 ...

Отзывы: