![Mitsubishi Electric 13JZ96 Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/mitsubishi-electric/13jz96/13jz96_user-manual_238802014.webp)
12
3
SPECIFICATIONS
3.1
General Specifications
This section describes the general specifications of the QA1S6ADP-S1.
*1 Do not use or store the programmable controller under pressure higher than the atmospheric pressure of
altitude 0m. Doing so may cause malfunction. When using the programmable controller under pressure,
please consult your local Mitsubishi Electric representative.
*2 This indicates the section of the power supply to which the equipment is assumed to be connected between
the public electrical power distribution network and the machinery within premises. Category
applies to
equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up
to the rated voltage of 300V is 2500V.
*3 This index indicates the degree to which conductive material is generated in terms of the environment in which
the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary
conductivity caused by condensing must be expected occasionally.
Item
Specifications
Operating
ambient
temperature
Température
ambiante de
fonctionnement
0 to 55
0 à 55
Storage ambient
temperature
-20 to 75
Operating
ambient humidity
10 to 90%RH, non-condensing
Storage ambient
humidity
10 to 90%RH, non-condensing
Vibration
resistance
Compliant with
JIS B 3502 and
IEC 61131-2
Frequency
Constant
acceleration
Half
amplitude
Sweep count
Under
intermittent
vibration
10 to 57Hz
0.075mm
10 times each
in X, Y, and Z
directions
57 to 150Hz 9.8m/
Under
continuous
vibration
10 to 57Hz
0.035mm
57 to 150Hz 4.9m/
Shock resistance Compliant with JIS B 3502 and IEC 61131-2 (147m/
, 3 times each in X, Y, and Z directions)
Operating
atmosphere
No corrosive gases
Operating
altitude
0 to 2000m
Installation
location
Inside a control panel
Overvoltage
category
or less
Pollution
degree
2 or less
Equipment class
Class