21/1531-ANF 901 43 F 2017-04-25
Rack PDM Charger
Installation and Operation Manual
7
2. INSTALLATION AND CONFIGURATION
2.1 RACK PDM CHARGER INSTALLATION
2.1.1 GENERAL
NOTE: The unit shall be installed by authorized personnel only.
•
The units shall be placed in a dry environment with a temperature range from
+5° C up to + 40° C (41° F to 104° F).
•
The units shall be mounted on a vertical wall.
•
Avoid mounting the Rack PDM Charger in a sunlit place. This can affect the
charging capacity.
•
Avoid mounting the Rack PDM Charger where radio/network coverage is not
sufficient. This can reduce the messaging capacity.
•
The unit can be mounted to a vertical wall (concrete or plaster walls only) or be
placed on table if table adapters are used.
•
If the Rack PDM Charger is connected to a power supply via an AC wall plug, serial
power supply connection is not allowed.
•
If the Rack PDM Charger is connected to a power supply via an AC wall plug, the
socket-outlet shall be situated near the equipment and shall be easily accessible.
•
If the Rack PDM Charger is connected to a power supply via a fixed connection, a
readily accessible disconnect device shall be incorporated in the building installation
wiring.
Delivery Includes:
•
Rack PDM Charger
•
Power supply cord including IEC C14 connector (male)
•
Inlet accessory kit including cable support holders and screws
•
Table adapters
NOTE: An extension cord IEC C13 AC connector (female, IEC60320-C13) to wall
socket has to be ordered separately. It shall be connected between the pre-
installed IEC C14 AC connector (male) and the wall socket.
Required Tools etc.
•
Screwdrivers
•
Cutting pliers
•
Multimeter
•
Screws and wall plugs for wall mounting. Make sure the screws and wall plugs have
the correct length for the type of wall used. See example below:
Wall material
Plug length
Screw diameter
Single plasterboard
Thorsman TP1
3.5 – 5 mm
Double plasterboard
Thorsman TP2
3.5 – 5 mm
Concrete
Thorsman TP2
3.5 – 5 mm