Chapter 5: RTU Startup
1. Power the Mission RTU with the 12 VDC battery only. Connect the black lead first,
then the red lead (see Figure 6). The LCD will illuminate the start up screen. Once
the radio sequence is complete, you will hear three beeps from the buzzer. This
indicates the unit has connected to Mission servers. Allow the unit about two minutes
to perform its power-up sequence and synchronization to the network. If the RTU
does not connect after two attempts, contact Technical Support.
Figure 6:
Battery Wiring
2. Check the wiring connections before powering the pump station. If the wiring is
correct, power the pump station, and immediately focus on the mainboard. Check
to ensure the Mission RTU is still operating. If a wiring mistake has been made,
it will be evident. If there appears to be a mistake, immediately remove power. If
everything is correct, proceed to testing the RTU.
Warning:
Risk of explosion if battery is replaced by an incorrect type. Dispose of
used batteries in accordance with local regulations.