background image

INSTALLATION 
INSTRUCTIONS

RTI-265  RemoteTrouble  Unit
RAM-265 Remote Trouble & Alarm Unit

The RTI-265 Remote Trouble Unit provides remote trouble annunciation for the FA-
262/265 fire alarm control panels. The RAM-265 Remote Trouble and Alarm Unit 
provides remote trouble annunciation for the FA-262/265 series fire alarm control 
panels. A maximum of four RTI-265 and four RAM-265 units can be connected to each 
control panel.

SPECIFICATIONS

Green AC ON indicator

Yellow Common Trouble 
indicator

Trouble Silence pushbutton

Lamp Test function

Communications: DAT & CLK 
from control panel

Standby current: 15 mA

Voltage:  24 V

DC

Up to 8 addressable units
(4 of each type)

Supervised

Power: AUX & COM from control 
panel

NOTE: 

This component must be included in the control panel battery 

calculation. Refer to the Standby Battery Calculation Sheet included 
with the control panel.

RTI-265

RAM-265

Alarm current: 25 mA max.

Single gang mounting

2 3/4 x 4 1/2” (70 mm x 115 mm)

Alarm current: 40 mA max.

Double gang mounting

4 1/2 x 4 1/2” (115 mm x 115 mm)

Alarm & Supervisiory LED/Zone

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

In no event shall Mircom be liable for any direct, indirect or consequential damages, 
loss of anticipated profits, loss of time or any other losses incurred by the buyer in 
connection with the purchase, installation or operation or failure of this product.

Important!

Mircom recommends that the entire system be completely tested on a regular basis. 
However, despite frequent testing, and due to but not limited to criminal tampering or 
electrical disruption, it is possible for this product to fail to perform as expected.

LT-2030MIR Rev. 1

Canada

25 Interchange Way
Vaughan, ON, L4K 5W3
Tel: (905) 695-3545
Fax: (905) 660-4113
www.mircom.com

USA

60 Industrial Parkway PMB 278
Cheektowaga, NY, 14227
Tel: 1-888-MIRCOM5
Fax: 888-660-4113

Отзывы: