QMT-5300A, QMT-5302 and QZT-5302 Instructions

2

QMT-5300A/QMT-5302 Master Telephone Wiring

Fig

ure 

1 shows the wiring for QMT-5300A and QMT-5302. A Fire Alarm Control Panel’s Detection Zone (should be 

configured as Trouble-Only or Non-Latching Supervisory) is used to annunciate Telephone Trouble. This is 
connected to the QMT-5300A or QMT-5302 TROUBLE terminals (polarity does not matter), and the ELR device for 
that zone is connected to the QMT-5300A or QMT-5302 ELR terminals. DC Power (24 V DC, filtered or unfiltered at 
200 mA) is connected to the 24 V DC terminals.

If the Master Telephone is being used alone as a Single-Zone System, the NP-735 Label is used or Connect label 
from NP-896, and Jumpers are placed on JW1 and JW2 only. The one Telephone Zone connects to the TEL-CKT 
terminals. The 10 Kohm ELR resistor that is shipped with this unit is connected after the last Remote Telephone on 
the Zone and the negative black jumper is removed for Class B.    For Class A wiring, remove both red and black 
jumper wires and wire from OUT + - to the remote telephones and back to RET + -.  

If the Master Telephone is being used as a Multi-Zoned System with QZT-5302s, the NP-736 Label is used or Clear 
All label from NP-896, and a Jumper is placed on JW3 only. The TEL-CKT terminals are left as is.  Telephone Zone 
wiring is done via the QZT-5302s.

Figure 1: QMT-5300A/QMT-5302 Master Telephone Wiring

                                TELEPHONE CIRCUIT
SINGLE ZONE SYSTEM: 

  CLASS B TELEPHONE ZONE FOR FT-300 OR

OTHER COMPATIBLE REMOTE TELEPHONES.  REMOVE THE NEGATIVE

BLACK JUMPER FROM OUT - and RET -TERMINALS.  CONNECT A 10K ELR

RESISTOR AFTER THE  LAST REMOTE TELEPHONE.  FOR CLASS A WIRING

OF TELEPHONE ZONE, WIRE OUT +  -  AND BACK FROM LAST TELEPHONE

TO RET +  -.

MULTI-ZONE SYSTEM:

 DO NOT CONNECT ANY REMOTE TELEPHONES

AND LEAVE RED AND BLACK WIRES CONNECTED AS SHOWN.

ELR

APPROVED ELR

END- OF-LINE

DEVICE FOR

CONNECTED FIRE
ALARM PANEL

TRANSMIT

+

OUT

-

LT

RET

COM

EXT AUDIO

24 VDC

+

-

+

-

TO DETECTION ZONE OF CONNECTED

FIRE ALARM PANEL, TO BE USED TO

ANNUNCIATE TELEPHONE TROUBLE

TR

OU

B

LE

T

E

LEP

H

ONE

 CI

RC

UI

T

+

-

LAMP TEST

CLASS A RETURN FOR 

SINGLE ZONE

 SYSTEM

REMOVE BOTH JUMPERS

WHEN WIRING AS CLASS A

TO LAMP TEST TERMINAL ON QMP-5100A

OR QMP-5101 AUDIO CONTROL MODULE

TO EXT AUDIO TERMINAL ON QMP-5100A

AUDIO CONTROL MODULE

NOT USED

NOT USED

FROM 20.4V DC LOW BATTERY TO 29V

DC UNFILTERED HIGH AC LINE

QMT-5300A or QMT-5302

RED

BLK

16 or 18 AWG ONLY

Содержание QMT-5300A

Страница 1: ...302 and QZT 5302 Firefighters Telephone System LT 674 Rev 2 Dec 2007 Installation Operation Instructions Advanced Life Safety Solutions COMMON TEL TROUBLE LAMP TEST INCOMING CALL MASTER TEL TROUBLE CO...

Страница 2: ......

Страница 3: ...Multi Zone Slide in label NP 896 is provided with the QMT 5302 use the Connect for Single Zone or Clear All label for Multi Zone The QZT 5302 includes blank labels for Telephone Zone information Chas...

Страница 4: ...ter Telephone is being used as a Multi Zoned System with QZT 5302s the NP 736 Label is used or Clear All label from NP 896 and a Jumper is placed on JW3 only The TEL CKT terminals are left as is Telep...

Страница 5: ...ire jumpers found on the positive and negative terminals of the QZT 5302 are removed Note that on each QZT 5302 the associated buttons for Telephone Zones 1 to 12 are numbered left to right where Zone...

Страница 6: ...back On Hook 3 Press the CLEAR ALL button to disconnect all Zones 4 Press LAMP TEST to test all indicators Indicators on QMT 5300A or QMT 5302 Common Tel Trouble This LED will flash amber if there is...

Страница 7: ...erates only by AC power any interruption however brief will render that device inoperative while it does not have power Power interruptions of any length are often accompanied by voltage fluctuations...

Страница 8: ...other noise sources such as stereos radios televisions air conditioners or other appliances or passing traffic Audible notification appliances however loud may not be heard by a hearing impaired pers...

Страница 9: ...ed by failure to provide a suitable installation environment for the products damage caused by use of the products for purposes other than those for which it was designed damage from improper maintena...

Страница 10: ...product will be charged for each replacement unit WARNING Mircom Technologies Ltd recommends that the entire system be completely tested on a regular basis However despite frequent testing and due to...

Страница 11: ......

Страница 12: ...Tel 905 660 4655 Fax 905 660 4113 Mircom 2007 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway PMB 278 Cheektowaga NY...

Отзывы: