background image

21 (25)

Master Warranty and Warning Information

not detect smoke or heat from fires on another level of the residence or building. In this 
situation the control panel may not alert occupants of a fire.

Sensors in a nurse call system may fail to be triggered when movement is occurring outside of 
the motion sensors’ range. For example, if movement is occurring on the other side of closed 
doors or on another level of the residence or building the motion detector may not be 
triggered. In this situation the central controller may not register an alarm signal.

Other Impairments

Similarly, Alarm Notification Appliances such as sirens, bells, horns, or strobes may not warn 
or waken a sleeping occupant if there is an intervening wall or door. It is less likely that the 
occupants will be alerted or awakened when notification appliances are located on a different 
level of the residence or premise.

Audible notification appliances may be interfered with by other noise sources such as stereos, 
radios, televisions, air conditioners, appliances, or passing traffic. Audible notification 
appliances, however loud, may not be heard by a hearing- impaired person.

Software

Most 

MGC Systems

 contain software. With respect to those products, MGC does not warrant 

that the operation of the software will be uninterrupted or error-free or that the software will 
meet any other standard of performance, or that the functions or performance of the software 
will meet the user’s requirements. MGC shall not be liable for any delays, breakdowns, 
interruptions, loss, destruction, alteration or other problems in the use of a product arising out 
of, or caused by, the software.

Telephone Lines

Telephone service can cause system failure where telephone lines are relied upon by a 

MGC 

System

. Alarms and information coming from an 

MGC System

 may not be transmitted if a 

phone line is out of service or busy for a certain period of time. Alarms and information may 
not be transmitted where telephone lines have been compromised by criminal tampering, local 
construction, storms or earthquakes.

Component Failure

Although every effort has been made to make this 

MGC System

 as reliable as possible, the 

system may fail to function as intended due to the failure of a component.

Security and Insurance

Regardless of its capabilities, no 

MGC System

 is a substitute for property or life insurance. 

Nor is the system a substitute for property owners, renters, or other occupants to act prudently 
to prevent or minimize the harmful effects of an emergency situation.

Moreover, building automation systems produced by MGC are not to be used as a fire, alarm, 
or life safety systems.

Содержание OpenBAS-HV-WLSTH

Страница 1: ...Installation Manual Wired and Wireless Thermostat Transmitter LT 6131 Rev 1 June 2017 OpenBAS HV WLSTH...

Страница 2: ......

Страница 3: ...s OpenBAS HV WLSTH only 10 3 4 Mounting Plate Dimensions 12 3 5 Mounting 12 4 0 Field Wiring 13 4 1 To Wire the Terminals 13 4 1 1 Required Tools 13 4 2 Power Supply Connection 14 4 3 Wireless Communi...

Страница 4: ...ller 9 Figure 2 Board connections 10 Figure 3 Battery connections 11 Figure 4 Mounting plate back view 12 Figure 5 Power supply 12 VDC 12 VAC 24 VAC 24 VDC 14 Figure 6 Wireless communication 15 Figure...

Страница 5: ...5 25 List of Tables Table 1 Controllers 7 Table 2 Compatible Modules 8...

Страница 6: ...rotocols It can be integrated into any network and used as a standard temperature and humidity transmitter or as a powerful yet easy to set environment HVAC controller It is fully addressable and when...

Страница 7: ...C to 24 V AC DC Battery life is 12 to 18 months 2 1 2 digit LCD display four keyboard operator interface for setpoint and calibration setup Line of sight range of 30 meters and 15 meters indoors 1 RS...

Страница 8: ...e OpenBAS HV FCX Fan Coil or VAV controller for variable air volume VAV applications Two universal inputs 5 digital relay outputs Two analog outputs Two field bus connections with RS 485 driver Can be...

Страница 9: ...oller Note Installation of OpenBAS controllers should be in accordance with the Canadian Electrical Code or the National Electrical Code and comply with all local regulations Final acceptance is subje...

Страница 10: ...Do not use nickel cadmium or lithium batteries Battery life is estimated at 12 to 18 months depending on operating conditions Install the batteries before mounting the OpenBAS HV WLSTH Attention Alwa...

Страница 11: ...the old batteries 2 Dispose of the used batteries promptly Keep away from children Do not disassemble and do not dispose of in fire 3 Connect the new batteries to the connectors shown in Figure 3 Pay...

Страница 12: ...rcom logo is the right way up To mount the controller 1 If you are connecting power or RS 485 to the controller use AWG 22 to 24 Run the wires to the single gang box and then through the wiring hole o...

Страница 13: ...hole on the right side the side with the labels To remove the wire Insert a micro screwdriver into the top hole to release the wire Caution Installation of OpenBAS controllers must be in accordance wi...

Страница 14: ...on If you connect the controller to a power supply disconnect the batteries Do not use batteries and an external power supply at the same time Caution An appropriate UL listed class 2 power supply or...

Страница 15: ...send information to one or more receivers and a receiver can receive information from up to ten different transmitters Each receiver OpenBAS HV VAVFC or OpenBAS HV RF433R is paired with up to 10 trans...

Страница 16: ...485 The list of supported protocols is in chapter 5 4 4 1 RS 485 wiring requirements 22 AWG twisted pair Maximum length 1219 2 m 4000 feet Mircom recommends shielded cable Figure 7 Networking with RS...

Страница 17: ...temperature setpoint In manual mode press this button to increase the fan speed Manual Auto This button switches between manual mode and automatic mode On Off This button turns the HVAC equipment it...

Страница 18: ...lithium batteries Do not use batteries and power supply at the same time Wireless Characteristics OpenBAS HV WLSTH only Frequency 433 MHz Range 15 m 49 ft indoors 30 m 98 ft outdoors with line of sigh...

Страница 19: ...tems have been carefully designed to be as effective as possible However there are circumstances where they may not provide protection Some reasons for system failure include Inadequate Installation A...

Страница 20: ...mage MGC Systems or other electronic equipment After a power interruption has occurred immediately conduct a complete system test to ensure that the system operates as intended Battery Failure If the...

Страница 21: ...ducts MGC does not warrant that the operation of the software will be uninterrupted or error free or that the software will meet any other standard of performance or that the functions or performance...

Страница 22: ...id Warranty This warranty applies only to defects in parts and workmanship relating to normal use It does not cover damage incurred in shipping or handling damage caused by disaster such as fire flood...

Страница 23: ...et fee which MGC has predetermined and which may be revised from time to time will be charged for each unit repaired Products which MGC determines not to be repairable will be replaced by the nearest...

Страница 24: ...s equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment In order to avoid the possibility of exceeding the FCC radio frequency exposure limits human proximity...

Страница 25: ...660 4113 TECHNICAL SUPPORT North America Tel 888 Mircom5 888 647 2665 International Tel 905 647 2665 Mircom 2017 Printed in Canada Subject to change without prior notice www mircomgroup com CANADA Ma...

Отзывы: