Mircom MS-700MP Series Скачать руководство пользователя страница 2

MS-700MP(U) Series

Fire Alarm Manual Station

www.mircom.com 

LT-6661

 Rev. 1 July 2020

2

B. Setting the addressable module

Follow the instructions in LT-6146 MIX-4090 Device Programmer.

The factory default address is 255.

C. Mounting

1.

Open the station with the reset key.

2.

Mount the station to a surface mounted box with 2 of the 
included screws. Refer to Figure 3.

D. Inserting the plastic rod

Inside the station, there is an opening below the white PULL 
handle. This is where the plastic rod sits.

1.

Pull down the PULL handle part way.

2.

Carefully insert the plastic rod into the opening below the 
PULL handle.

3.

Move the PULL handle back to the upright position. The 
PULL handle should now be holding the plastic rod in 
place.

4.

Close and lock the station.

Figure 3: Mounting the manual station

Using the manual station in 

case of fire

Activating the alarm

On the MS-702MP, pull down the PULL handle.

ON the MS-710MP(U), push in the PUSH bar, then pull down 
the PULL handle.

The handle is now hanging down. A qualified person must reset 
the station by opening it with the reset key. See 

Resetting the 

manual station

 below.

Activating the stage two alarm (

MS-702MP

 only)

Insert the stage two key into the keyhole above the PULL 
handle, and then turn the key.

The stage two alarm activates immediately.

Note:

The stage two alarm will activate automatically a certain 
amount of time after the handle has been pulled if no 
action is taken. This time is set in the Fire Alarm Control 
Panel.

Resetting the manual station

You use the reset key to open the station in order to reset it.

Note:

Resetting the station does not cancel the alarm at the 
panel.

1.

Open the station with the reset key. The switch is now reset.

2.

If you want to insert a plastic rod, see 

Inserting the plastic 

rod

 above.

3.

Move the PULL handle back to its upright position.

4.

Close and lock the station.

5.

Reset the Fire Alarm Control Panel to cancel the alarm.

Converting Dual Action Manual Stations to Single 
Action (MS-710MP(U)

 

only):

1.

Using a reset key, unlock and open the manual station.

2.

Remove the smaller two screws and accompanying brackets 
fastening the PUSH bar.

3.

Hold the manual station vertically with one hand with the 
keyhole at the bottom. Tilt the manual station towards you 
and remove the PUSH bar.

MANUAL STATION

SINGLE GANG 

BOX

SCREW

SCREW

SCREW HOLE

SCREW HOLE

BACK OF MANUAL STATION

Screws

Screws