www.mircom.com
LT-6661
Rev. 1 July 2020
MS-700MP(U) Series
Fire Alarm Manual Station
1
Mircom’s MS-700MP(U) Series Fire Alarm Manual Stations
provide manual fire alarm activation. These high quality, die-cast
metal stations are available as single or dual-action devices. They
are reset with a key. Each station has a permanently attached MP
(Mircom Protocol) addressable module which is configured with a
tool (see LT-6146 MIX-4090 Device Programmer for instructions).
Specifications & Dimensions
Compatible with Mircom Fire Alarm Control Panels
Electrical Rating:
•
Nominal Operating Voltage: 15-30 VDC
•
Maximum alarm current: 3.3 mA
•
Standby current: 2 mA
Dimensions:
•
MS-702MP: 4.93” H x 3.56” W x 2.56” D
•
MS-710MP(U): 4.93” H x 3.56” W x 2.9” D
Installing the manual station
This guide covers these models:
•
MS-702MP Intelligent Key-Resettable Two Stage Manual
Station MP
•
MS-710MP(U) Intelligent Key-Resettable Single Stage Dual
Action Manual Station MP
The suffix
U
indicates a USA version.
Contents of kit
•
MS-702MP: 4 mounting screws, 2 reset keys (black), 2 stage
two keys, 2 plastic rods
•
MS-710MP(U): 4 mounting screws, 2 reset keys (black), 2
plastic rods
A. Wiring
Note:
The maximum wire size is 12 AWG.
1.
Connect the black (
−
) wire from the previous station to
the terminal that is connected to the black (
−
) wire from
the addressable module.
2.
Connect the black (
−
) wire leading the next station to the
other side of the terminal that is connected to the black
(
−
) wire from the addressable module.
Note:
The wires must be on opposite sides of the set screw.
Refer to Figure 2 for the location of the wires.
3.
Tighten the (
−
) terminal.
4.
Connect the red (+) wire from the previous station to the
terminal that is connected to the red (+) wire from the
addressable module.
5.
Connect the red (+) wire leading to the next station to the
other side of the terminal that is connected to the red (+)
wire from the addressable module.
Note:
The wires must be on opposite sides of the set screw.
Refer to Figure 2 for the location of the wires.
6.
Tighten the (+) terminal.
Figure 1: Wiring Diagram
Figure 2: Close-up of terminals showing correct wiring
Notes
• Wire as shown so that supervision of connections is
maintained.
• Maximum wire size: 12 AWG
• ADA compliant. To be installed per ADA 4.27.1 to 4.27.4
inclusive.
• All manual fire alarm stations shall be installed as per the
specific requirements outlined in the UL/ULC codes, as well
as all other applicable national or local codes. Final
acceptance is subject to the local authority having
jurisdiction.
FROM
TO NEXT STATION OR END
OF LINE DEVICE
−
−
+
+
PREVIOUS
STATION
{
{
−
BLACK
+
RED
ADDRESSABLE
MODULE
TO ADDRESSABLE
MODULE
WRONG: BOTH
WIRES ON THE
SAME SIDE OF
THE SET SCREW
TO ADDRESSABLE
MODULE
CORRECT: BOTH
WIRES ON
OPPOSITE SIDES
OF THE SET SCREW
X