Mircom MS-700MP Series Скачать руководство пользователя страница 1

www.mircom.com 

LT-6661

 Rev. 1 July 2020

MS-700MP(U) Series

Fire Alarm Manual Station

1

Mircom’s MS-700MP(U) Series Fire Alarm Manual Stations 
provide manual fire alarm activation. These high quality, die-cast 
metal stations are available as single or dual-action devices. They 
are reset with a key. Each station has a permanently attached MP 
(Mircom Protocol) addressable module which is configured with a 
tool (see LT-6146 MIX-4090 Device Programmer for instructions).

Specifications & Dimensions

Compatible with Mircom Fire Alarm Control Panels

Electrical Rating:

Nominal Operating Voltage: 15-30 VDC

Maximum alarm current: 3.3 mA

Standby current: 2 mA

Dimensions:

MS-702MP: 4.93” H x 3.56” W x 2.56” D

MS-710MP(U): 4.93” H x 3.56” W x 2.9” D

Installing the manual station

This guide covers these models:

MS-702MP Intelligent Key-Resettable Two Stage Manual 
Station MP

MS-710MP(U) Intelligent Key-Resettable Single Stage Dual 
Action Manual Station MP

The suffix 

U

 indicates a USA version.

Contents of kit

MS-702MP: 4 mounting screws, 2 reset keys (black), 2 stage 
two keys, 2 plastic rods

MS-710MP(U): 4 mounting screws, 2 reset keys (black), 2 
plastic rods

A. Wiring

Note:

The maximum wire size is 12 AWG.

1.

Connect the black (

) wire from the previous station to 

the terminal that is connected to the black (

) wire from 

the addressable module.

2.

Connect the black (

) wire leading the next station to the 

other side of the terminal that is connected to the black 
(

) wire from the addressable module. 

Note:

The wires must be on opposite sides of the set screw. 
Refer to Figure 2 for the location of the wires.

3.

Tighten the (

) terminal.

4.

Connect the red (+) wire from the previous station to the 
terminal that is connected to the red (+) wire from the 
addressable module.

5.

Connect the red (+) wire leading to the next station to the 
other side of the terminal that is connected to the red (+) 
wire from the addressable module.

Note:

The wires must be on opposite sides of the set screw. 
Refer to Figure 2 for the location of the wires.

6.

Tighten the (+) terminal.

Figure 1: Wiring Diagram

Figure 2: Close-up of terminals showing correct wiring

Notes

• Wire as shown so that supervision of connections is 

maintained.

• Maximum wire size: 12 AWG
• ADA compliant. To be installed per ADA 4.27.1 to 4.27.4 

inclusive.

• All manual fire alarm stations shall be installed as per the 

specific requirements outlined in the UL/ULC codes, as well 
as all other applicable national or local codes. Final 
acceptance is subject to the local authority having 
jurisdiction.

FROM

TO NEXT STATION OR END 

OF LINE DEVICE

+

+

PREVIOUS

STATION

{

{

  BLACK

+

 RED

ADDRESSABLE

MODULE

TO ADDRESSABLE
MODULE

WRONG: BOTH 
WIRES ON THE 
SAME SIDE OF
THE SET SCREW

TO ADDRESSABLE
MODULE

CORRECT: BOTH 
WIRES ON
OPPOSITE SIDES 
OF THE SET SCREW

X

Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 1-888-647-2665

U.S.A
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Tel: 1-888-647-2665