Dirty: Significant for Photo detectors only. Brand new 
detectors should be around 000%. A value near 100% 
means that device must be cleaned or replaced.

·

Standard value: “StdValue” followed by a number. 
Significant for detectors only, normal value is around 32. 
Value 0 or a value over 192 (alarm threshold) may indicate 
a defective or dirty device. 

·

Firmware version: “FrmVer” followed by number. 

·

Operation mode: “Op Mode” followed by Enter. Pressing 
on the “Read” key will display a number showing the 
operational mode of the device. This parameter should 
only be accessed when requested by a Mircom Tech 
Support operator.  Modifying this parameter may make the 
device unusable.

·

Programmer messages:

The programmer can display the following messages during 
operation:

·

“Fatal Error”:  Device or programmer has failed and may 
need replacement.

·

“Storing”: A parameter is written into the device. 

·

Do not disconnect a device during this operation!

·

“Address Stored”: Address has been successfully stored 
on device.

·

“Failed”: Current operation (first line of display) has failed.

·

“Miss Dev”: The device has not responded to current 
operation. Check connections or replace device.

·

“No Addr”: No address is programmed. This may happen 
for brand new devices address is read without prior 
address write.

·

“Low Batt”: Battery should be replaced.

Table 1: Device type returned by MIX-4090 programmer.  

Table 2: Compatible devices

Display

Device

Photo

Photo Electric smoke detector

Thermal

Heat detector 

PhtTherm

Photo Electric smoke and heat detector

I Module

Input module

O Module

Relay output module

OModSup 

Supervised output module

Conv Zon

Conventional zone module

Multiple

Multiple I/O device 

CallPnt

Call point 

Sounder

Wall or ceiling audible NAC

Beacon

Strobe

Sound B

Combined audible NAC and strobe

Remote L

Remote visible indicator

Special 

This message can be returned for newer 
devices not yet in the programmer’s list

Device

Model number

Photoelectric smoke detector

MIX-4010(-ISO)

Photo smoke/Heat Multi-sensor

MIX-4020(-ISO)

Heat detector

MIX-4030(-ISO)

Multi-use output module

MIX-4046

Dual input module

MIX-4040

Dual input mini-module

MIX-4041

Conventional zone module and 4-20mA 
interface

MIX-4042

Dual relay module

MIX-4045