Dirty: Significant for Photo detectors only. Brand new
detectors should be around 000%. A value near 100%
means that device must be cleaned or replaced.
·
Standard value: “StdValue” followed by a number.
Significant for detectors only, normal value is around 32.
Value 0 or a value over 192 (alarm threshold) may indicate
a defective or dirty device.
·
Firmware version: “FrmVer” followed by number.
·
Operation mode: “Op Mode” followed by Enter. Pressing
on the “Read” key will display a number showing the
operational mode of the device. This parameter should
only be accessed when requested by a Mircom Tech
Support operator. Modifying this parameter may make the
device unusable.
·
Programmer messages:
The programmer can display the following messages during
operation:
·
“Fatal Error”: Device or programmer has failed and may
need replacement.
·
“Storing”: A parameter is written into the device.
·
Do not disconnect a device during this operation!
·
“Address Stored”: Address has been successfully stored
on device.
·
“Failed”: Current operation (first line of display) has failed.
·
“Miss Dev”: The device has not responded to current
operation. Check connections or replace device.
·
“No Addr”: No address is programmed. This may happen
for brand new devices address is read without prior
address write.
·
“Low Batt”: Battery should be replaced.
Table 1: Device type returned by MIX-4090 programmer.
Table 2: Compatible devices
Display
Device
Photo
Photo Electric smoke detector
Thermal
Heat detector
PhtTherm
Photo Electric smoke and heat detector
I Module
Input module
O Module
Relay output module
OModSup
Supervised output module
Conv Zon
Conventional zone module
Multiple
Multiple I/O device
CallPnt
Call point
Sounder
Wall or ceiling audible NAC
Beacon
Strobe
Sound B
Combined audible NAC and strobe
Remote L
Remote visible indicator
Special
This message can be returned for newer
devices not yet in the programmer’s list
Device
Model number
Photoelectric smoke detector
MIX-4010(-ISO)
Photo smoke/Heat Multi-sensor
MIX-4020(-ISO)
Heat detector
MIX-4030(-ISO)
Multi-use output module
MIX-4046
Dual input module
MIX-4040
Dual input mini-module
MIX-4041
Conventional zone module and 4-20mA
interface
MIX-4042
Dual relay module
MIX-4045