- 4 -  

BPS-602

Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:

•  For all Class B, Style W, X, Y, hookups SW1 & SW2 on the AL800LGK9E logic board must be open.

  For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK9E logic board must be closed.

Output Programming Selection Table:

Outputs must be programmed independently (OUT1 - OUT4)

Function

Switch Positions

Descriptions

ON

OFF

Input to Output Follower 

Mode

1

2, 3

Output follows signal it receives from the corresponding input 

(i.e. FACP Sync module - maintains synchronization of

notification appliance circuit).

Temporal Code 3 Mode

3

1, 2

Enables Temporal Code 3 signal generation output. 

This mode will accept a steady or a pulsing input.

Steady Mode

1, 2, 3 A steady output signal will be generated. 

This mode will accept steady or pulsing input.

For the above modes Dip Switch 4 determines which Input controls 

the corresponding output:

Switch 4 in the ON position causes output(s) to be controlled by Input 1.

Switch 4 in the OFF position causes output(s) to be controlled by Input 2.

Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1) 

and audible notification appliances (horns) via Input 2 (IN2). This allows audible 

notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. The 

FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the 

BPS-602 (NAC Power Extender) is connected.

Sync Mode Selection Table:

Function

Switch Positions

Descriptions

ON

OFF

Amseco Sync 

Mode*

1, 3,

4

2

This mode is designed to work with the Amseco series of horns, strobes, and 

horn/strobes to provide a means of synchronizing the Temporal-coded horns, 

synchronizing the flash timing of the strobe, and silencing the horns of the horn/

strobe combination over a two-wire circuit while leaving strobes active.

Faraday
Sync Mode*

2, 4

1, 3

This mode is designed to work with the Faraday series of horns, strobes, and horn/

strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz-

ing the flash timing of the strobe, and silencing the horns of the horn/strobe combi-

nation over a two-wire circuit while leaving strobes active.

Gentex

®

Sync Mode*

Gentex is a registered 
trademark of Gentex Corporation.

1, 2,

3, 4

This mode is designed to work with the Gentex

®

 series of horns, strobes, and horn/

strobes to provide a means of synchronizing the Temporal-coded horns, synchroniz-

ing the flash timing of the strobe, and silencing the horns of the horn/strobe combi-

nation over a two-wire circuit while leaving strobes active.

System Sensor

®

Sync Mode*

System Sensor is a registered
trademark of Honeywell.

1, 2, 4

3

This mode is designed to work with the System Sensor

®

 series of horns, strobes, 

and horn/strobes to provide a means of synchronizing the Temporal-coded horns, 

synchronizing the one-second flash timing of the strobe, and silencing the horns of 

the horn/strobe combination over a two-wire circuit while leaving strobes active.

CooperWheelock

®

Sync Mode*

CooperWheelock is a 
registered trademark of 
Cooper Wheelock.

2, 3, 4

1

This mode is designed to work with the CooperWheelock series of horns, strobes, 

and horn/strobes to provide a means of synchronizing the Temporal-coded horns, 

synchronizing the one-second flash timing of the strobe, and silencing the horns of 

the horn/strobe combination over a two-wire circuit while leaving strobes active.

(AL800LGK9E Board)

Output Dip Switches

INPUT SELECT

TEMPORAL

STROBE SYNC

IN>OUT SYNC

Содержание BPS-602

Страница 1: ...Rev 042209 BPS 602 NAC Power Extender Installation Guide see Application Guide for additional information...

Страница 2: ...ry helps identify intermittent loop problems Common trouble input and output for external trouble signals tie in Ground fault detection Unit includes power supply red enclosure cam lock and battery le...

Страница 3: ...ection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount unit in the desired location Mark and predrill holes in the wall to line...

Страница 4: ...provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving str...

Страница 5: ...sen to drive notification appliances The designated outputs are set by output switches OUT1 through OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not repor...

Страница 6: ...ds Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will repor...

Страница 7: ...NC OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC IN1 IN1 IN2 IN2 C DRY1 NC RET1 RET1 RET2 RET2 C DRY2 NC OUT2 OUT3 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC AUX UPPER TERM...

Страница 8: ...nnect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to...

Страница 9: ...mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5 amp 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes lin...

Страница 10: ...sor DH400ACDCI Ionization Duct 25 95 System Sensor DH400ACDCP Photoelectric Duct 25 95 System Sensor 1112 24 D Ionization 0 05 50 System Sensor 1424 Ionization 0 10 41 System Sensor 1451 w B402B Base...

Страница 11: ...05 System Sensor 6424 Projected Beam 10 28 4 System Sensor Beam 1224 S Projected Beam 17 38 5 Contact manufacturer for current draws A 2 Door Holders Table A 2 below lists door holders compatible with...

Страница 12: ...CW RSSP 24150W RSSP 24177W RSSP 24185W STW Appliances with Sychronizing Strobes AMT 241575W AMT 2475W AMT 241575W NYC AMT 2475W NYC MT 12575W MT 241575W MTWP 2475W CH70 24MCW CH70 24MCC CH70 2415C CH7...

Страница 13: ...MB G10 24 MIZ TC24 Gentex Devices Models GE3 Series GES GEC Series GCS GCC Series SSPK Wall and Ceiling Mount Series GX93 Series WGE and color lense units System Sensor Devices Wall Horn Strobes P2R P...

Страница 14: ...SET HMC W SET S17R WP SET S17 W WP SET S17 CW WP SET MC CW SET MC CR SET HMC CW SET HMC CR SET 177 CR WP SET 177 CW WP SET 185 R WP SET 185 W WP SEF MC R SEF MC W SEF HMC R SEF HMC W SEF MC CW SEF HM...

Страница 15: ...BPS 602 15 Notes...

Страница 16: ...31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 61...

Отзывы: