REPLACE BATTERY
The UPS automatically tests the battery’s condition and will illuminate the replace battery
LED and emit a short beep. This tone will be repeated every hour until the battery passes a
self test. It is recommended that the UPS be allowed to charge overnight before performing
a battery test to confirm a replace battery condition.
LOW BATTERY WARNING
The UPS will emit a steady tone when the battery reserve runs low. It continues to emit the
steady tone until AC returns or the UPS shuts down from battery exhaustion.
TROUBLESHOOTING CHART
Symptom
Possible Cause
What To Do
UPS will not turn on
On/Off button not pushed
Press On button
momentarily (one beep) to
start UPS
UPS operates in battery
mode only, even though
there is normal AC present
Input AC breaker is tripped
Reset circuit breaker by
pressing the plunger back
in. Circuit breaker trips
after UPS starts up, reduce
the load on the UPS
Fault LED is illuminated
UPS has detected an
internal fault
Call for service
The Site Wiring Fault LED
is illuminated
Incorrect service wiring
Have a qualified electrician
correct the service wiring
The Online/On Battery LED
is illuminated, but there is
no output
The UPS is being
controlled via its
communications port
Disconnect the
communications cable
from the UPS and press
the On button
momentarily. If the UPS
works normally, software
has control of the UPS
UPS does not provide
expected backup time
The batteries may be weak
or at the end of useful
service life
Charge the batteries for 8
hours and retest. If the
backup time is still less
than expected, the
batteries may need to be
replaced, even though the
Replace Battery LED is not
illuminated
Replace Battery LED is
illuminated
Weak or bad batteries, or
bad battery connection
Check the battery
connection and/or replace
the batteries. Follow
battery replacement
procedures in Section 6
The UPS occasionally
emits a beep
Normal operation
The UPS is performing its
intended function