Action of the master
Slave reaction
Write value in
Write_Data
(bytes 0-3).
Write function number to
Write_Value_Select
.
Read data from
Write_Data
(bytes
0-3).
Set the
Write_Active
bit.
Wait until
Write_Active
has been set.
Write 0 in
Write_Value_Select
.
Reset the
Write_Active
bit.
7.2.2.3
Writing bits
In addition to the control bits in bytes 6/7, further bits can be set and, if necessary, reset
directly with
Write_Value_Select
.
To set bits 80 to 127, the corresponding function number is written to
Write_Value_Select
(see Chapter
To reset bits 80 to 89, the corresponding function 128 (208 to 217) is written to
Write_Value_Select
.
Action of the master
Slave reaction
Writing the bit address as a function
number to
Write_Value_Select
.
The bit from
Write_Value_Select
is
set and the corresponding function
carried out.
Set the
Write_Active
bit.
Wait until
Write_Active
has been set.
Write 0 in
Write_Value_Select
.
Reset the
Write_Active
bit.
7.2.2.4
Reading bits
Reading individual bits which are not contained directly in the read window is only
possible with a corresponding function number and the data in
Read_Data
(Byte 0-3) of
the read window. In those bytes, the bits must be evaluated individually.
The procedure is the same as that described in Chapter
7.2.3
Reading and writing bits directly
For reading status bits and for writing direct control bits, no procedure is required. The
general status bits are always provided and need not be requested. The direct control bits
are also available continuously.
7.2.3.1
Reading status bit
The status bits in bytes 5-7 of the read window are always available and can be read
directly by the master.
7 ProfiBus interface
Transmitter Series PR 5211
EN-65
Minebea Intec