Troubleshooting 

Symptom 

Possible cause 

Check 

Action Required 

No display on 
the meter 

Improper connection to 
power supply or power 
supply not turned on 

Check wiring and power supply. 

Correct wiring according to 
diagram or Repair wires  

Temperature sensor 
does not match the 
type which the 
transmitter requires  

Check for the correct temperature sensor type 

Replace with correct 
temperature sensor 

Temperature of the 
temperature sensor 
may be higher or lower 
than the Temptran

TM

 

transmitter's 
temperature range 

Verify the sensor’s operating temperature and that 
this temperature is within the range of the 
transmitter 

Replace transmitter with a 
range suitable for the 
temperatures; recalibrate 
meter to match new range 

Improper wiring to the 
meter supply terminals  

Check wires supplying power to meter. 

Repair wires  

Improper wiring to the 
temperature sensor 

Check wires between sensor and transmitter 

Repair wires  

Meter display 
is higher or 
lower than 
expected and 
the reading is 
steady 

Temperature sensor 
may be burned out 

Examine the temperature sensor and wires for 
damage. 

Disconnect sensor from transmitter and ohm the 
RTD; 100 ohm Platinum RTD’s are about 110 ohms 
at room temperature and 1000 ohm Platinum RTD’s 
are about 1100 ohms at room temperature. 

Replace bad sensor 

1     

” 

displayed  

Valid or invalid loop 
current signal causing 
meter reading to 
exceed maximum of 
+1999 

Check for open or shorted temperature sensor. 

An open temperature sensor will not necessarily 
cause an overrange display of “

1     

”; for example, 

when you have set the meter for a 0 to 500 °F 
display, but a wiring problem causes the transmitter 
to put out its overrange signal of 25 mA, the meter 
will display about "656." 

If transmitter is sending 
proper 4-20mA signal, adjust 
meter range. 

If meter range is correct, fix 
problem initiated by 
temperature transmitter. 

-1     

“ 

displayed 

Valid or invalid loop 
current signal causing 
meter reading to be 
below minimum of 
-1999 

Figure out what should be displayed based on meter 
setup. 

When wiring to an RTD temperature sensor is 
accidentally shorted it causes the transmitter to 
produce a current between 3 and 4 mA.  For 
example, when you have set the meter for a 0 to 
500 °F display, it may give a reading like "-25" for a 
3 mA current, not a “

-1      

.” 

If transmitter is sending 
proper 4-20mA signal, adjust 
meter range. 

If meter range is correct, fix 
problem initiated by 
temperature transmitter. 

 

Note:

  For further information on Minco temperature transmitters go to the following web link 

http://www.minco.com/site/transmitter.php

 

 
 
 
 