Description

The Minco TI334 is a two-wire, loop-powered digital meter that accepts a 4 to 20 milliamp DC
signal.  The meter measures the input current and accurately displays the corresponding
temperature in °C or °F.  The meter derives power from the current loop, so no external power
supply is required.  With only a 2.8 volt drop across the meter, it can operate from lower-
voltage DC power supplies and you can connect the meter in series with other loop-powered
devices.

The TI334 case is a 3” X 5” Polycarbonate NEMA 4X electrical case with knockouts.

Wiring

Use this meter to monitor temperature anywhere from the control room to the sensing location.
Wire it into the current loop anywhere observing the +/- polarity of the loop.  Remove screws
which hold the front cover in place.  Pull terminal block off from PC board, screw wires onto
block then re-plug block onto board. On the meter, terminal 1 is positive and terminal 2 is
negative.  Wiring in Figure 1 below is typical.

°F and the °C stickers are supplied and can be applied to the front of the case.
Most Minco transmitters can be mounted inside the meter’s housing.
For more information about the use of Temptran

TM

 current transmitters, request Minco

Application Aid #15.

COPPER LEADS,
TWISTED PAIR

METER

Transmitter

Temperature
Sensor

R1

OPTIONAL
COMPUTER OR
CONTROLLER INPUT

DC
SUPPLY

CONTROL SITE

S

Z

+

-

+

-

2

1

V-

V+

Figure 1

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Содержание TI334

Страница 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Страница 2: ...MODEL TI334 Current Loop Meter Installation and Operation Instructions Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Страница 3: ...anywhere from the control room to the sensing location Wire it into the current loop anywhere observing the polarity of the loop Remove screws which hold the front cover in place Pull terminal block o...

Страница 4: ...ting the meter to the same range perform steps 1 and 4 7 only Procedure 1 Hook up the equipment as shown in the Figure 2 Pull terminal block off from PC board screw wires onto block then re plug block...

Страница 5: ...ansmitter Example If your span 20mA temperature is 200 F and your zero temperature 4mA is 100 F then the Span Reading value is 200 F 100 F 300 F Per Table 2 below the appropriate switch settings are t...

Страница 6: ...h settings to correspond to your desired temperature range as described in Method 1 steps 2 and 3 3 Set the calibrator to output 4 000 mA 4 Adjust the meter s Zero potentiometer Fig 3 until the meter...

Страница 7: ...00 ohm Platinum RTD s are about 110 ohms at room temperature and 1000 ohm Platinum RTD s are about 1100 ohms at room temperature Replace bad sensor 1 displayed Valid or invalid loop current signal cau...

Страница 8: ...of any other obligations or liability of the seller or its employees or agents Model Code TI334 Model Number TI334 Polycarbonate NEMA 4X case 25 200 Temperature Range Specify temperature range in eit...

Страница 9: ...MINCO 2 950 74 9 2 930 74 4 4 950 125 7 TRANSPARENT COVER HOUSING Temperature Meter Range Switches Zero Span www minco com KNOCKOUT 6 Artisan Technology Group Quality Instrumentation Guaranteed 888 8...

Страница 10: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Отзывы: