Figure 3 

Output Settings 

The Output Settings group contains Device Name, parameters which directly control the Heater Output, and parameters which 
define Status/Comm LED behavior.   

Device Name:

 A string of up to 20 characters that the user may use to name the device.  This may be useful to identify 

multiple units. 

Pulse Rate:

 The period of time between Measurement Pulses with which the CT398 tests the heater resistance while the 

output is off, i.e. while the heater resistance is above the Setpoint.  This value is in milliseconds.  When the heater’s resistance 

is below the Setpoint, the heater is energized and its resistance is checked continuously at a high, fixed rate. 

Generally a lower Pulse Rate period is better since it should theoretically result in tighter control; however, the lower the Pulse 

Rate period, the greater the Pulse Heating effect.  A Pulse Rate period of 1000ms is a recommended starting point. 

LED Behavior: 

Determines the LED behavior when used as a status indicator (when not being used for PC communication).  

The options are as follows: 

 

Mode 1: LED to remain off during normal operation. 

 

Mode 2: LED indicates when output is on for the purpose of heating, but not including the Measurement Pulses.   

 

Mode 3: LED indicates when output is on for the purpose of heating, including the Measurement Pulses.   

 

Mode 4: LED displays a “fade on-fade off” behavior when the heater resistance / temperature falls within the 

Process Value Range and there are no errors.  This is useful as a quick visual check to ensure the CT398 is 

operating as desired. 

Additionally, if the Heater Shutdown range is violated or Analog to Digital Converter fails, the associated error code will be 

displayed on the LED regardless of the Mode chosen. 

Control Units: 

Selectable between Resistance and Temperature.  This setting controls whether resistance or temperature is 

used to configure the Setpoint, Process Value Range, and Heater Shutdown limits.  If Temperature is used, the Heater 

Settings information must be entered.  If Resistance is used, no information about the heater is required by the utility program.  

The Setpoint, Process Value Range, and Heater Shutdown values on the same screen will be displayed / entered in the 
selected units. 

Содержание Heaterstat CT398

Страница 1: ...CT398 HeaterstatTM Temperature Controller Technical User Guide...

Страница 2: ...atus 2 Heater Settings 3 Output Settings 4 General Usage 5 Status Communication LED 5 Frequently Asked Questions FAQ 6 Specifications 7 Inputs 7 Outputs 7 Communication 7 General 7 Glossary 8 Document...

Страница 3: ...easurement Pulse and Pulse Heating Depending on the characteristics of the thermal system the difference between the heater element temperature and the heat sink may vary significantly Since the CT398...

Страница 4: ...agram for the CT398 Figure 1 Configuration A separate programmer model AC221332 is necessary to configure the CT398 This device optically communicates with the CT398 though the Status Comm LED To use...

Страница 5: ...ature Resistance Data or Equation defines which method the program uses to convert resistance to temperatures Heater Code A string of characters which if provided with the heater fully describes the h...

Страница 6: ...when not being used for PC communication The options are as follows Mode 1 LED to remain off during normal operation Mode 2 LED indicates when output is on for the purpose of heating but not including...

Страница 7: ...ed to set these to values that would indicate a problem with the heater This feature is temporarily suppressed when HeaterStat Utilities is connected to a CT398 Figure 4 General Usage Status Communica...

Страница 8: ...ification states the retention is at least 20 years and will withstand at least 1 million writes Q Why isn t the measured temperature of the heater surface the same as what is reported in the utility...

Страница 9: ...esistance Temperature Setpoint Resolution 1 milliohm Resistance Measurement Accuracy 3 up to 55 C and at least 0 25 amp load 4 up to 70 C and at least 0 5 amp load Dimensions 1 50 L x 1 00 W x 1 00 D...

Страница 10: ...request for heat but due to the heater being energized momentarily to check its temperature SSR Solid State Relay A type of relay without mechanical contacts constructed from solid state components TC...

Отзывы: