AC INPUT

Set J501 to either 115 VAC or 230 VAC depending on your input voltage.

The HTL Series is calibrated at the factory. Adjusting trimpots may be neces-
sary to fine tune the drive to your motor and application.

FWD ACCEL:

 Sets the time required to ramp up to a set speed in the forward 

direction. Sets the time required to ramp down to a set speed in the reverse 
direction. Turning the trimpot clockwise adds more time.

REV ACCEL:

 Sets the time required to ramp up to a set speed in the reverse 

direction. Sets the time required to ramp down to a set speed in the forward 
direction. Turning the trimpot clockwise adds more time.

FWD MAX SPD: 

Sets the maximum forward voltage to the motor when the 

speed pot or external reference signal is set to maximum. Turning the trimpot 
clockwise adds more voltage.

REV MAX SPD:

 Sets the maximum reverse voltage to the motor when the 

speed pot or external reference signal is set to a maximum. Turning the trim pot 
clockwise adds more voltage.

FWD CURR LIMIT:

 Sets the maximum amount of current the motor can draw in 

the forward direction. Turning the trimpot clockwise allows more current.

REV CURR LIMIT:

 Sets the maximum amount of current the motor can draw in 

the reverse direction. Turning the trimpot clockwise allows more current.

IR COMP:

 Determines the degree to which motor speed is held constant as 

the motor load changes. It is factory set for optimum motor regulation. Too high 
(clockwise) of a setting may cause motor oscillation.

MIN SPEED:

 Sets the minimum voltage to the motor when the speed pot or 

external reference signal is set to a minimum. (Uni directional only)

DC OUTPUT

Set J502 to 12 V or 24 V to match your motor’s rated voltage.

ANALOG CONTROL

Set J503 to 10 V or 5 V to match the analog voltage used to control speed. Set 
to 5 V (pins 2 & 3) if using a speed pot to control speed.

POTENTIOMETER

Set J504 to BI DIRECTION (wig wag) to control both speed and direction using 
the speed pot. Set J504 to UNI DIRECTION (pins 2 & 3) to control only speed 
using the speed pot.

INHIBIT PERSONALITY

Set J505 to INVERT (pins 1 & 2) to set the inhibit as open to stop. Set J505 to 
NORMAL (pins 2 & 3) to set the inhibit as close to stop.

A:

 Connect Speed potentiometer to 1, 2, and 3. Connect optional Direction switch to terminals 4 and 5. 

     Connect optional Inhibit (start/stop) switches to 6, 7, and 8. Pin 6 (FWI) is the forward inhibit. Pin 7 (RVI) is the

   reverse inhibit. Limit switches can be used with pins 6, 7, and 8. Pins 6 and 7 can be tied together for use with

 only one Inhibit switch.

B:

 Connect motor to A1 and A2

C:

 Connect AC line voltage to L1 (hot) and L2 (neutral).

J501

J502

J503

J504

J505

230 VAC

115 VAC

24 V    12 V 

10 V 

5 V 

BI DIRECTION 

UNI DIRECTION 

INVERT 

NORMAL

1

2

3

1        2        3 

1

2

3

1

2

3

1

2

3

S T E P  O N E :   S E T  J U M P E R S

S T E P T W O :   W I R E   D R I V E

S T E P T H R E E :   C A L I B R AT I O N

M I N A R I K   D R I V E S

w w w. m i n a r i k d r i v e s . c o m

14300 De La Tour Drive, South Beloit, IL 61080

Phone: (800) MINARIK (646-2745); Fax: (815) 624-6960

Document Number: 250-0408, Revision 3

Printed in the U.S.A. --October  2006