OUTLINE AND CONNECTION
DO’S AND DON’TS
VERY IMPORTANT
Do not route cable openly in raceways.
For optimum isolation against electrical noise, run cable in a grounded metal conduit with no
other cabling (except temperature sensor). Ground shield only at transceiver. Insulate shield
at junctions to prevent inadvertent grounding.
Transducer wiring must be done in conjunction with approved conduit, boxes and fittings
and to procedures in accordance with all governing regulations.
Seal all thread connections to prevent ingress of moisture.
Do not run cable near high voltage or current runs, contactors and SCR control drives.
For BASEEFA Zone 0, cable must be terminated externally to Zone 0 in an appropriate
manner. the cable must be protected against mechanical damage, and arrangements sealed
to prevent migration of atmosphere from Zone 0.
To reduce risk of electrostatic discharge, housing (except face) must be covered with copper
mesh and grounded.
95/07/11
152 mm
(6.0")
284 mm
(11.2")
229 mm
(9.0")
mounting holes
13 mm (0.5") dia.
(3 places)
radiating face
1/2" NPT
internal
thread
23 mm
(0.9")
102 mm
(4.0")
51mm
(2.0")
S
H
L
D
H
O
T
terminal block
in junction box
red (hot)
black
transducer cable
green
shield
to approved
ground of junction
box and conduit
shield
hot
RG62 A/U cable
Milltronics
transceiver
PL-419
2