However, if you do not want a direct grounding of the negative connection, and in the case of
Ex applications where the DCS measures in the negative connection, and that wire cannot be
grounded, a barrier type as shown in Example 3 is required.
Example 3
This barrier is also used in case of XP (Cenelec) applications. The barrier is then placed in the
transmitter housing. Grounding is not always direct in this case, because of a possible
installation on cathodically protected tanks, as in Example 4.
Example 4
In case of Ex applications where the DCS have galvanically separated inputs, both types of
barriers can be used. See Examples 2 and 5.
Stahl barrier: 9002/13-280-110-00
(or equal)
Stahl barrier: 9002/13-280-110-00
(or equal)