OM-264 278 Page 15
3-13. Electrical Service Guide
Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated circuit that applies to the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
STR 400
3-Phase
Input Voltage (V)
230
400
Input Amperes (A) At Rated Output
57
33
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
70
40
Normal Operating
Fuses3
90
50
Min Input Conductor Size In mm
2
(AWG)
4
10 (8)
6 (10)
Max Recommended Input Conductor Length In Meters (Feet)
30 (98)
60 (196)
Min Grounding Conductor Size In mm
2
(AWG)
4
10 (8)
6 (10)
** Power cord supplied with the unit is sized for 230V operation. Larger power cord may be required for cable lengths greater than 3 meters.
Consult national and local regulations.
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These
recommendations are for a dedicated circuit that applies to the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
STR 500
3-Phase
Input Voltage (V)
230
400
Input Amperes (A) At Rated Output
82
47
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
100
50
Normal Operating
Fuses3
125
70
Min Input Conductor Size In mm
2
(AWG)
4
16 (6)
6 (10)
Max Recommended Input Conductor Length In Meters (Feet)
33 (107)
42 (138)
Min Grounding Conductor Size In mm
2
(AWG)
4
16 (6)
6 (10)
** Power cord supplied with the unit is sized for 230V operation. Larger power cord may be required for cable lengths greater than 3 meters.
Consult national and local regulations.
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Содержание STR 400
Страница 4: ......
Страница 27: ...A complete Parts List is available at www MillerWelds com OM 264 278 Page 23 956172121 A...
Страница 29: ...A complete Parts List is available at www MillerWelds com OM 264 278 Page 25 956172123 A...
Страница 33: ...Notes Work like a Pro Pros weld and cut safely Read the safety rules at the beginning of this manual...
Страница 34: ...Notes Work like a Pro Pros weld and cut safely Read the safety rules at the beginning of this manual...