Startup and Shutdown 

Prior to start-up, read and fully understand the 

MAXIM 

Owner’s Manual section.  

 

Initial Start-up / Seasonal Re-start 

 

Always inspect the filter system prior to start-up or after an extended shutdown period. 

 

1.  Before pressurizing the system, check that all clamps, bolts, lids, and system accessories are properly fastened. 
2.  Load the sand media - see procedure on page 8. (Disregard for seasonal re-start) 
3. 

MAXIM

 Controller Settings:   With the pump starter HOA switch in the “OFF” position, turn the MAXIM controller 

switch to the ON position.  Check the controller’s settings by scrolling through the menu screens.  See the     
controller recommendations in the 

Adjustable Values

 section. After verifying settings, scroll thru the menu to the 

Status screen. When the controller is powered ON, the valves are allowed to rotate to the Filtration position. After 
60 seconds, the Status will be AUTO. 

4.  Open all isolation valves and allow the system to fill with water.  Make sure the backflush drain is not restricted.   
5.  Open the air vent located on top of the sand filter housing. 
6.  Prime the pump by filling the suction line and pump volute with water.  If the main pump does not have a flooded      

suction, then a foot or check valve is required to maintain a prime after shutoff.   For a flooded suction, prime the 
pump if needed. 

7.  Close the Outlet Throttle Valve by turning the handle fully clockwise, 

then open the valve 2 turns

8.  Refer to the System Labels on the Maxim Controller box. There is a duplicate label on the inside cover.         

Maximum operating pressure (50 PSI) and Maximum flow are listed on this label. These must be adhered to  
during start up. 

9.  Using the pump starter HOA switch, momentarily bump start the motor by switching to “HAND” position, only 

long enough to verify that the motor is wired to rotate in the direction shown by the arrow. 

10. After confirming that the motor is rotating in the right direction. 
11. Turn on the system by switching the pump starter HOA switch to “AUTO” mode.  AUTO mode will allow the   

controller to turn the pump ON/OFF as required.  Note that the controller power switch must be ON in order for 
the pump to start. 

12. While observing the pressure gauge on the top of the filter, rotate the Outlet Throttle Valve until the gauge is 

reading approximately 25 PSI. 

13. Due to variances at site locations such as installation pipe sizes, pipe lengths, elevation, etc., the Outlet Throttle 

Valve may require further adjustment to optimize the desired flow. 

Never exceed the specified maximum pres-

sure or specified maximum flow

.  

14. Check the setting of the Pressure Differential Gauge. Factory and initial setting should be 12 PSID. See the   

Differential Pressure Gauge information in the Maxim Owner’s Manual section. 

15. Close the air vent once there is a steady stream of water. 
16. Check all system components to ensure there are no leaks. 
17. If the system has new sand media installed, run a complete backwash cycle.  This will purge any excess fine 

particles from the system.  To start a cycle, press OK on the controller’s Status Screen. See the “

Monitoring the 

System Status and Initiating a Backflush

”  section in the Maxim Owner’s Manual section of this manual for 

information on normal Backflush sequence. 

18. Once the backflush is complete, the system will automatically resume normal filtration.  
 
 

Содержание TOWER GUARD TGSS-20T

Страница 1: ...OWNER S MANUAL Operation and Maintenance Guide TGSS 20T TGSS 24T and TGSS 30T...

Страница 2: ...n any form mechanical electronic Internet or in any form without the written permission of Miller Leaman Inc Toll Free 800 881 0320 Phone 386 248 0500 Fax 386 248 3033 E mail sales millerleaman com We...

Страница 3: ...ny questions concerning the system please contact our application specialists at 386 248 0500 or e mail us at sales millerleaman com The MAXIM Controller also contains a serial number to ID the softwa...

Страница 4: ...ct damage may occur Your filter was designed for specific applications It should not be modified and or used for any application other than originally specified If there are any questions regarding it...

Страница 5: ...the TowerGuard systems come in multiple sizes depend ing upon the desired flow rate Introduction to TowerGuard Automatic Filtration System Components Frame Skid The T304 stainless steel welded frame s...

Страница 6: ...ush timer or manually by the user Backflush Once a backflush is initiated the pump will turn off while the valves rotate to the backflush position When the valves are in the backflush position the pum...

Страница 7: ...30T inch with 2 1 2 inch piping Reducing the piping size may result in loss of flow Make sure to support all piping to and from the filter to eliminate stress on the filter components 2 Manual valves...

Страница 8: ...sand media bed depth which shall extend to an approximate level below the top of the hydraulic distribution lenses See Figure 1 4 For TGSS 20T and TGSS 24T inch Sand Filter models Remove the top diffu...

Страница 9: ...PSI and Maximum flow are listed on this label These must be adhered to during start up 9 Using the pump starter HOA switch momentarily bump start the motor by switching to HAND position only long eno...

Страница 10: ...s are factory preset at average values and do not necessarily reflect the individual needs for your system Below are recommendations on how to adjust the controller to fit your system s needs 1 The Pr...

Страница 11: ...e all of the union couplings The O rings should be lubricated with silicon gasket grease to prevent them from drying and cracking Check all of the 3 way valves to make sure they are operating properly...

Страница 12: ...12 Figure 5 TowerGuard Sand Filter Vessel Parts List TowerGuard Side Mount Sand Filter...

Страница 13: ...120 volts AC or 12 volts DC Additional connections to the Outputs should be made to the corresponding Output and a Common ter minal on the circuit board The Pressure Differential Gauge and Timer ON En...

Страница 14: ...ves pump starter etc Note Any Common connection may be used for the common negative terminals of the solenoids valves Output 1 Spare Output 2 Backflush valves actuate for backflush flow This output is...

Страница 15: ...pump is turned off for the valves to be turned back to the filtration position Status ON Valves to Filtration Screen after the pump has been turned off the valves will be turned back to the filtration...

Страница 16: ...rd from screen 8 Company Contact Information screen causes the display to cycle back around to the beginning and display the Screen 1 Status Screen Also pressing the A button to scroll backwards from...

Страница 17: ...ting values These values should be adjusted to meet the filters backflush requirements Refer ence the filter manufacturer s owners manual for additional information Backflush Interval The user defined...

Страница 18: ...splayed at the beginning of a backflush cycle as the valves are redirecting water from normal flow to backflush flow The controller will automatically turn the pump off while it is changing the valve...

Страница 19: ...ime displayed is in hours and min utes This value does not include the elapsed time when the backflush frequency timer is off either when the Status Screen reads Status Off or when the controller is p...

Страница 20: ...NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PUR POSE The warranty set forth above is the only warranty applicable to Miller Leaman products Our maximum liability...

Отзывы: