OM-220 812 Page 15
3-8. Stick DCEP (Direct Current Electrode Positive) Connections
Ref. 802 888 / Ref. 803 080
1
Negative (
−
) Weld Output
Terminal
Connect work lead to negative weld
output terminal.
2
Positive (+) Weld Output
Terminal
Connect electrode holder to
positive weld output terminal.
1
2
3-9. Electrical Service Guide
CAUTION:
INCORRECT INPUT POWER can damage this welding power source. This welding
power source requires a CONTINUOUS supply of 50/60 Hz power at
+
10% of rated input voltage. Do
not use a generator with automatic idle device (that idles engine when no load is sensed) to supply
input power to this welding power source.
Actual input voltage cannot exceed
±
10% of indicated required input voltage. If
actual input voltage is outside of this range, no output is available.
NOTE
50/60 Hz Single-Phase,
50% Duty Cycle
50/60 Hz Three-Phase,
50% Duty Cycle
Input Voltage
220
220
400
440
Input Amperes At Rated Output
45
32
18
16
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay
2
50
40
20
20
Normal Operating 3
70
50
25
25
Min Input Conductor Size In AWG/Kcmil
8
10
14
14
Max Recommended Input Conductor Length
In Feet (Meters)
129 (39)
132 (40)
174 (53)
210 (64)
Min Grounding Conductor Size In AWG/Kcmil
8
10
14
14
Reference: 2002 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose
−
no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.