7.3 Downlink Commands
AM100 series sensors support downlink commands to configure the device. Application port is
85 by default.
Appendix
Carbon Dioxide Levels and Guidelines
CO
2
Level
Description
400ppm
Normal outdoor air level.
400-1000ppm
Typical level indoors with good ventilation.
1000-2000ppm
Poor air quality - requires ventilation.
≥2000ppm
Headaches, sleepiness and stagnant, stale, stuffy
air. Poor concentration, loss of attention, increased
heart rate and slight nausea may also be present.
06
65(Illumination)
1c 00 79 00
14 00
Illumination: 1c 00 => 00 1c =28 lux
V Infrared: 79 00=> 00 79= 121
Infrared: 14 00=> 00 14= 20
07
7d
(
CO
2
)
67 04
67 04 => 04 67 =1127
CO
2
= 1127 ppm
08
7d(TVOC)
07 00
07 00 => 00 07=7
TVOC = 7 ppb
09
73
(
Barometric
Pressure
)
68 27
68 27=>27 68=10088
Pressure=10088*0.1=1008.8hPa
Channel
Type
Data Example
Description
ff
03(Set Reporting Interval)
b0 04
b0 04 => 04 b0 = 1200s
18 (Enable/disable
sensor)
01 01
(Enable
Temperature)
Byte 1: Select Sensor
01: Temperature
02: Humidity
03: PIR
04: Light
05: CO
2
06: TVOC
07: Barometric Pressure
Byte 2: 00=disable, 01=enable