background image

e.

Parameters Setting

Step 1: Press [RESET] button to step to desired [FUNC] or parameter.

Step  2:  Press [

] and  [

] buttons  simultaneously  and  hold  for  1.5s  to  enter  programming  mode. 

The [FUNC] digit blink to indicate the relay has enter into the programming mode.

Step 3: Press [

] or [

] button to increase or decrease the parameter value.

Step 4: To save the selected value, press [

] and [

] buttons simultaneously and hold for 1.5s. It 

will exit the programming mode with [DATA] displaying the new setting.

To exit programming mode without saving the selected setting, press the [[RESET] button once.

4.

DIGITAL INPUT PORT *

a.

This digital port is for remotely reset the relay when tripped or ZCT connection fault.

b.

To reset the relay, make a connection between terminals 4 and 5 of the relay.

5.

OUTPUT CONTACTS

Trip  Contact

Activated and latch by leakage fault trip, manual test trip or ZCT connection fault

Positive Safety 
Contact *

Activated when the relay is power up and function correctly with no tripping.

Pre-fault Alarm 
Contact *

Activated when the measured leakage current > 50% of the I

n and self reset when the 

measured leakage current < 45% of the I

n. 

Activated and latch when the relay is tripped.

Table 3: Output contact description

6.

RECORDS

a.

Record the 3 latest tripped faults current or “tSt” for manual trip test.

b.

The records are stored in non-volatile memory.

c.

To clear the entire record database:

Step 1: When the relay is healthy, press [RESET] button to step to most recent trip fault record or 
[FUNC] digit shown “A”.

Step 2: Press [

] and [

] buttons simultaneously and hold for 3.5s or the [DATA] show “0”. It will 

clear the entire fault records database.

7.

TECHNICAL DATA

AUXILIARY SUPPLY

DIN310-230A(6)............................................................. 184~276 VAC
DIN310E-230A(6)........................................................... 184~276 VAC
Rated frequency............................................................. 50Hz or 60Hz
VA rating......................................................................... 3 VA typical

SETTING RANGES

Sensitivity adjustment..................................................... 30mA, 50mA, 

0.10~1.00A (step=50mA),
1.00~10.0A (step=1.00A)

Delay time adjustment.................................................... Instantaneous, 

0.1~3.0s (step=0.1s)

RECORD

Fault record.................................................................... 3 latest trip fault current or “tSt” for manual trip test
Storage........................................................................... Non-volatile memory

DIGITAL INPUT PORT

Remote reset.................................................................. N.O. Dry contact

OUTPUT CONTACTS

Contact rating................................................................. 5A(NO) / 3A(NC) / 250V AC1
Contact arrangement...................................................... Change over
Expected electrical life.................................................... 10,000 at rated current
Expected mechanical life................................................ 5,000,000 operations

 

 

 

 

 

Содержание DIN310

Страница 1: ...es comes with a pre fault alarm contact and a positive safety contact The pre fault alarm contact is activated whenever the leakage current exceed 50 of the sensitivity setting While the positive safety contact is activated if the relay is power up and function correctly The DIN310E series also built in a digital input port for remotely reset the relay after leakage fault trip manual test trip or ...

Страница 2: ... fault alarm condition then follow by 1 5s testing on the trip time delay End of time delay relay trip b Leakage Fault Trip Reset Manual Test Trip Reset Press the RESET button once or through digital input port c ZCT Connection Fault Reset Press the RESET button once or through digital input port Reset is inhabited if the fault is not rectify d Parameters Viewing When the relay is operate normal a...

Страница 3: ...measured leakage current 50 of the I n and self reset when the measured leakage current 45 of the I n Activated and latch when the relay is tripped Table 3 Output contact description 6 RECORDS a Record the 3 latest tripped faults current or tSt for manual trip test b The records are stored in non volatile memory c To clear the entire record database Step 1 When the relay is healthy press RESET but...

Страница 4: ...tandard 35mm DIN rail mounting Approximate weight 0 38kg excluding ZCT 9 CONNECTION DIAGRAMS 10 CASE DIMENSION Applicable to DIN310E series only TRIP CONTACT LOAD L1 L2 L3 N PE 6 2 3 4 5 7 1 8 9 10 11 12 13 14 L N AUX SHUNT TRIP MIKRO ZCT DIN310 TRIP CONTACT SAFETY CONTACT LOAD 6 2 3 4 5 7 1 8 9 10 11 12 13 14 L N AUX CONTACTOR MIKRO ZCT DIN310E REMOTE RESET Typical application diagram for DIN310 ...

Отзывы: